Troubleshooting by Remote Controller
SiUS281117
Service Diagnosis
157
2.39 Inverter Startup Error
Remote
Controller
Display
L9
Applicable
Models
RZR, RZQ
Method of Error
Detection
The error is detected from the current flowing to power transistor into voltage with CT1 (DC
current sensor).
Inverter PCB detects the disorder of position signal.
Error Decision
Conditions
When compressor overload (when startup) is detected
Supposed
Causes
The stop valve is not opened.
Pressure differential startup
Defective outdoor unit inverter PCB
Defective compressor (lock)