Troubleshooting by Remote Controller
SiUS281117
Service Diagnosis
109
2.6
Error of External Protection Device
Remote
Controller
Display
A0
Applicable
Models
All indoor models
Method of Error
Detection
Detect open or short circuit between external input terminals in indoor unit.
Error Decision
Conditions
When an open circuit occurs between external input terminals with the remote controller set to
"external ON/OFF terminal".
Supposed
Causes
Actuation of external protection device
Improper field setting
Defective indoor unit PCB
Troubleshooting
Actuation of external
protection device.
External
protection
device is connected to
terminals T1 and T2 of the
indoor unit terminal
block.
Replace the indoor unit PCB.
YES
Change the second code No.
to "01" or "02".
External
ON/OFF input
(mode No. 12, first
code No. 1) has been
set to external protection
device input (second
code No. 03) by
remote
controller.
YES
NO
Check the setting state of the
ON/OFF input from outside by
remote controller.
NO
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Caution