SiUS281117
Troubleshooting by Remote Controller
162
Service Diagnosis
2.43 Power Supply Voltage Abnormality
Remote
Controller
Display
U2
Applicable
Models
RZR, RZQ
Method of Error
Detection
The error is detected according to the voltage of main circuit capacitor built in the inverter and
power supply voltage.
Error Decision
Conditions
When the abnormal voltage of main circuit capacitor built in the inverter and abnormal power
supply voltage are detected
Supposed
Causes
Drop in power supply voltage
Instantaneous power failure
Defective outdoor unit fan motor
Defective outdoor control PCB (A1P)
Defective main circuit wiring