Troubleshooting by Remote Controller
116
Service Diagnosis
Troubleshooting
Note:
1. Connector and indoor unit PCB
Connect correctly.
Is the connector (
∗
1)
correctly connected?
NO
YES
Connect correctly.
Is
the limit
switch
'
s transfer
connector correctly
connected?
NO
Replace the indoor unit
PCB.
Replace the indoor unit
PCB.
220-240 VAC?
NO
YES
Does the swing flap
motor swing?
Does
continuity/no continuity
reverse?
NO
NO
Turn the power supply OFF
once and back ON, and check
whether the swing flap motor
swings when the power
supply is turned back ON.
Turn the power supply OFF
once and restart, and measure
the output voltage of connector
(
∗
3) when the power supply is
restarted.
Disconnect the connector
(
∗
2), turn the power supply
OFF once and restart, and
check if the limit switch has
continuity when the power
supply is restarted.
YES
YES
Replace the swing flap
motor.
YES
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Caution
Model
Connector for swing flap motor
PCB
1
2
3
FCQ
X36A
X36A
X36A
A1P
FHQ
X6A, X9A
X9A
X6A
A1P
FAQ
X36A
X36A
X36A
A1P