Troubleshooting by Remote Controller
SiUS281117
Service Diagnosis
141
2.28 Discharge Pipe Temperature Control Error
Remote
Controller
Display
F3
Applicable
Models
RZR, RZQ
Method of Error
Detection
Abnormality is detected according to the temperature detected by the discharge pipe thermistor.
Error Decision
Conditions
When the discharge pipe temperature rises to an abnormally high level
When the discharge pipe temperature rises suddenly
When the discharge pipe temperature does not rise after operation start
Supposed
Causes
Refrigerant shortage
Defective compressor
Defective discharge pipe thermistor
Defective connection of discharge pipe thermistor
Disconnection of discharge pipe thermistor
Defective outdoor unit PCB