SiUS281117
Troubleshooting by Remote Controller
142
Service Diagnosis
Troubleshooting
Abnormality in refrigerant
system such as refrigerant
shortage, defective
compressor, etc.
Conduct inspection
Is the
discharge pipe
temperature high?
(248
°
F)
YES
Replace the discharge pipe
thermistor.
Is the discharge pipe
thermistor characteristic
normal?
Replace the outdoor unit
control PCB (A1P).
NO
YES
NO
Connect correctly, and
operate the unit again.
Is the
discharge pipe
thermistor correctly
connected to PCB
(A1P)?
NO
YES
Attach the thermistor, and
operate the unit again.
Is the
discharge pipe
thermistor attached to
the discharge
pipe?
NO
YES
CHECK 5
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Caution
CHECK 5