3
|
Components
Service manual
95
RXQ25+3 3 3
35AMV1B
Split Sensira R32 BBOP
ESIE21-16 – 2022.02
1×
To remove the top plate
INFORMATION
This procedure is just an example and may differ on some details for your actual unit.
Prerequisite:
Stop the unit operation via the user interface.
1
Turn OFF the respective circuit breaker.
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
2
Loosen and remove the screws that fix the top plate.
a
b
a
a
a
a
a
a
Screw
b
Top plate
3
Remove the top plate.
To remove the front plate
INFORMATION
This procedure is just an example and may differ on some details for your actual unit.
Prerequisite:
Remove the top plate, see
94].
1
Loosen and remove the screws that fix the front plate.