3
|
Components
Service manual
52
RXQ25+3 3 3
35AMV1B
Split Sensira R32 BBOP
ESIE21-16 – 2022.02
a
a
a
Damper
INFORMATION
The compressor dampers may look different.
Compressor dampers are in a good
condition?
Action
Yes
Perform an electrical check of the
compressor, see
50].
No
Replace the compressor and/or
damaged dampers, see
56].
To perform an electrical check of the compressor
1
First perform a mechanical check of the compressor, see
50].
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
2
Remove the cover of the compressor wire terminals.