3
|
Components
Service manual
107
RXQ25+3 3 3
35AMV1B
Split Sensira R32 BBOP
ESIE21-16 – 2022.02
Prerequisite:
Remove the required plate work, see
94].
1
Disconnect the swing flap motor connector from the indoor unit main PCB.
2
Measure the resistance between the following pins of the motor connector.
Result:
The measurements MUST be as shown in the table below.
Pins
Measured resistance (Ω)
1-2
232.5~267.5
1-3
1-4
1-5
2-3
465~535
2-4
2-5
3-4
3-5
4-5
Swing flap motor resistance
measurements are correct?
Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next procedure.
No
Replace the swing flap motor, see
107].
3.12.2 Repair procedures
To remove the swing flap motor
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
94].
1
Remove the cover.
a
b c
a
Cover
b
Screw
c
Swing flap motor