6
|
Technical data
Service manual
150
RXQ25+3 3 3
35AMV1B
Split Sensira R32 BBOP
ESIE21-16 – 2022.02
6.7 Field settings
6.7.1 Field settings: Indoor unit
To control the indoor unit fan during thermostat off in cooling
INFORMATION
As this field setting is NOT available on the standard remote controller of this unit,
order one of the following remote controllers and perform as described below:
▪
ARC480A11
▪
ARC480A53
▪
ARC466A33
▪
ARC466A58
▪
ARC466A67
Using remote controller ARC480A11 or ARC480A53
1
Press
,
, and
simultaneously.
2
Press
.
3
Select SU.
4
Press
to confirm.
5
Press
.
6
Select 4.
7
Press
to confirm.
8
Press
.
9
Select 0 (0: fan ON, 1: fan OFF (factory setting)).
10
Press
to confirm.
Using remote controller ARC466A33, ARC466A58 or ARC466A67
11
Press
,
, and
simultaneously.
12
Press
.
13
Select SU.
14
Press
to confirm.
15
Press
.
16
Select 4.
17
Press
to confirm.
18
Press
.
19
Select 0 (0: fan ON, 1: fan OFF (factory setting)).
20
Press
to confirm.