Components
Service manual
61
RXQ25+3 3 3
35AMV1B
Split Sensira R32 BBOP
ESIE21-16 – 2022.02
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
3.3 Compressor thermal protector
3.3.1 Checking procedures
To perform a mechanical check of the compressor thermal protector
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
94].
Prerequisite:
Remove the compressor insulation.
1
Remove the cover of the compressor wire terminals.
a
a
Compressor wire terminals cover
2
Remove the compressor thermal protection with bracket from the
compressor.