![background image](http://html1.mh-extra.com/html/daikin/rxq25amv1b/rxq25amv1b_service-manual_4205016101.webp)
3
|
Components
Service manual
101
RXQ25+3 3 3
35AMV1B
Split Sensira R32 BBOP
ESIE21-16 – 2022.02
To remove the front panel
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
1
Open the front panel, see
94].
2
Remove the front panel by sliding it to the left or the right and pulling it
toward you.
Result:
The front panel shaft on 1 side will be disconnected.
3
Disconnect the front panel shaft on the other side in the same manner.
a
a
Front panel shaft
To remove the front grille
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…)
when installing, maintaining or servicing the system.
1
Remove the front panel to remove the air filter.
2
Remove 2 screws from the front grille.
3
Push down the 3 upper hooks marked with a symbol with 3 circles.
a
b
a
a
Upper hook
b
Symbol with 3 circles
4
We recommend opening the flap before removing the front grille.