20
Product description
EN
RoCon UFH
Table 4-6: Technical specifications for actuators
Daikin recommends the use of Daikin UFH-Sat8 actuators to ensure optimum system
performance. If actuators from other manufacturers are used, the following limit val-
ues must be met:
Operating voltage
AC 230 V ±10 %, 50/60 Hz
Max. operating current
9 mA
Max. inrush current
140 mA / 200 ms
Max. operating power
2 W
Special characteristic
Short-circuit proof, protected against overvolt-
age
Actuators of other manufacturers
connected per control circuit
Max. 2