4.6
Information on RoCon UFH as per EN 60730-1:2016
•
RoCon UFH is an electronic control type C as per EN 60730-1.
•
RoCon UFH is suitable for continuous operation.
•
The type of disconnection of the actuators and pumps is micro disconnection.
•
The PTI value of the insulation (PCBs) is 175.
•
RoCon UFH corresponds to installation category 3.
•
RoCon UFH corresponds to overvoltage category 2.
•
The limit value for the SELV circuit is DC 5 V.
•
The maximum permissible click rate is 1/minute.
•
The test voltage for the EMC noise immunity tests is ±1 kV (±2 kV).
4.7
Information on RoCon UFH as per EN 15500:2017
•
Type: Fixed point function.
•
Zone type: Constant conditions.
•
Application groups: Individual zone control equipment.
•
Output types: On/off actuators.
•
Sensor type: NTC ±5 %.
•
Certified value of control accuracy: 0.6 K (0.5 K).