Parameter settings
Daikin RoCon
Daikin Control unit
008.1543999_00 – 03/2017 – EN
Operating instructions
39
MF 1 Config
Configuration of the multi-function output (230 V, J14 connection):
0: The output is without function.
1: Header pump – The output becomes active as soon as a system heating circuit reports
a heat requirement to the heat generator.
2: Circulation pump – The output is activated either after the time program of the circu-
lation pump or after the time program of the hot water generation, depending on the par-
ametrisation (see chap. 3.6.9).
3: Feeder pump – The output becomes active as soon as a heat requirement is pending
for the direct heating circuit of the heat generator.
N
E
0 - 3
2
1
Storage Pump
: Configuration of the storage charging circuit:
1: The hot water loading is carried out using a separate pump.
2: The hot water loading is carried out using a switching valve.
N
E
1 - 2
2
1
Air Purge
Activation of the automatic venting of the hydraulic circuit to which this Daikin heat gen-
erator is connected (see chap. 3.6.4).
Off: Deactivated
On: Start of the Air Purge
N
E
Off
On
Off
-
PWM Config
Min Perform Pump
Lower limit for modulation of the pump power
N
E
0 - 100 %
50 %
1 %
Max Perform Pump
Upper limit for modulation of the pump power
N
E
0 - 100 %
100 %
1 %
Sensor Config
Outside Config
Configuration of the outside temperature sensor:
Off: No sensor evaluation
On: Sensor evaluation activated (if no outside temperature sensor is connected, an error
message is generated.)
N
E
Off
On
On
-
Storage Config
Configuration of the hot water generation:
Inactive: No function for hot water generation.
Sensor: Function for hot water generation is activated. A storage temperature sensor is
evaluated for hot water generation (if no storage temperature sensor is connected, an
error message is generated).
Thermostat: Function for hot water generation is activated. A thermostatic switch
(ON/OFF) is evaluated for hot water generation, where an "open terminal" is evaluated
as "not required".
N
E
Inactive
Sensor
Thermostat
Inactive
:Sensor
-
Exhaust Config
Configuration of the flue gas temperature sensor:
Off: No sensor evaluation
On: Sensor evaluation activated (if no flue gas temperature sensor is connected, an error
message is generated.)
N
E
Off
On
On
-
MixerConfig
: Configuration of the t
V2
internal mixer sensor for control of the heating support.
Off: No sensor evaluation; heating support deactivated
On: Sensor evaluation activated (if no mixer sensor is connected, an error message is
generated).
N
E
Off
On
On
-
Pressure Config
Configuration of the sensor for detection of the water pressure of the system:
Off: No sensor evaluation
On: Sensor evaluation activated (if no pressure sensor is connected, an error message
is generated.)
N
E
Off
On
On
-
Outside Temp Adap Individual adjustment for the measured value of the outside temperature relevant for the
control unit.
N
E
-5.0 - 5.0 K
0.0 K
0.1 K
Terminaladress
Setting of the terminal ID of the control unit for system access. The set value must be
unique throughout the entire system. Confirmation of this parameter with the rotary but-
ton effects new initialisation of the control unit.
All settings except for "Off" authorise the user of the control unit to activate the terminal
function and thus to operate all RoCon system components with a valid device ID (see
chap. 3.4.9 and 4.1).
N
E
Off, 0 - 9
0
1
System Config
See chap. 6.12
N
E
Inactive,
Active,
Delete
Active
-
HC Assignment
Display only on connected
room station:
Setting of the heating circuit ID for the room station (see chap. 4.1). This parameter de-
termines which heating circuit should be operated with this value.
The direct heating circuit of the Daikin heat generator is set to heat circuit ID "0" as stand-