Operating instructions
48
Daikin RoCon
Daikin Control unit
008.1543999_00 – 03/2017 – EN
6
x
Parameter settings
6.11 Exit key: Special Level
6.12 "Basic Configuration" parameter level
This parameter level only appears:
– during initial commissioning if "No" was selected as the
answer to the "Use Standard Config" query, or
– after the [System Config] parameter has been set to "Inactive"
or "Delete" in the "
"Configuration"
rotary switch setting,
"Setup"
level.
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Incre-
ment
BE
HF
Emission Measure-
ment
Time-limited heat requirement for checking the burner settings (see chap. 3.5.1).
E
E
Off
Base Load
Full Load
Off
-
Manual Operation
The internal heating circuit is constantly regulated to an adjustable T-HS (see chap. 3.5.2).
E
E
20 - 80 °C
50 °C
1 °C
STL Test
Carrying out an STL test. The heat requirement is active for as long as the Exit key is pressed.
The set temperature for the limiting ([Max T-Module] parameter) is ignored during the STL test
(see chap. 3.5.3).
N
E
Off
On
Off
-
Res Emission Mon
: Display and resetting of a fault due to exceeding the maximum permitted flue gas tempera-
ture
N
E
Off
On
Off
-
FA failure
Display and resetting of the current error of the heat generator.
If "----" is displayed, no error is pending (see chap. 7.3).
E
E
-
-
-
Protocol
Display of the error protocol. Here, the saved error messages of the heat generator and the con-
nected data bus devices with date and error code are displayed accordingly as a menu item. By
selecting an entry by means of rotary button, all further information on the selected error mes-
sage is displayed accordingly:
- Date and time of the occurrence of the error
- Error code (see chap. 7.3)
- Location information (device) of the detected error
- Bus ID of the device causing the error
In the event of specific errors, the heat request must be taken back. This is done by activating
the [Standby] operating mode.
There are, however, conditions under which the control unit does not accept the error reset.
E
E
-
-
-
Delete message
By setting this parameter to "On" and briefly pressing on the rotary button, all entries of the error
protocol incl. the error are deleted by connected data bus devices.
N
E
Off
On
Off
-
RoCon B1/U1 Reset Resets all parameter settings to the factory setting. Required for software updates. Complete re-
configuration then necessary.
N
E
Off
On
Off
-
Parameter Reset
Resets all customer-specific parameter settings to the factory settings.
N
E
Off
On
Off
-
Timeprog Reset
Resets all permanent time programs to the factory settings (see tab. 3-9).
E
E
Off
On
Off
-
Return
This parameter is used only to exit the special level.
E
E
-
-
-
Tab. 6-15 Parameters at the "Special Level" level
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Incre-
ment
BE
HF
Boiler Function
Setting of the system functionality of the device in the RoCon system (do not change the factory
setting).
The default value of this parameter is "Single" and thus applies for a Daikin heat generator in
autonomous operating mode.
When setting the values "Slave 1" to "Slave 8", the Daikin heat generator works as a heating
module and expects an optional cascade controller for the request.
Internal hot water generation cannot be used further when operating as a heating module.
E
(N)*
E
Single
(Master)*
Slave 1
…
Slave 8
Single
-
Unmixed Circ Config Setting of the heating circuit ID for the direct heating circuit of the Daikin heat generator. The
heating circuit ID must be unique throughout the entire RoCon system. There must not be any
overlap with the heating circuit IDs of optional mixer circuits ([HC Assignment] parameter, see
tab. 6-17).
E
E
Off,
0 - 15
0
1
BUS ID HS
The setting must not be changed if more than 1 heat generator is integrated in the RoCon sys-
tem. Several heat generators integrated in the heating installation must be regarded as a special
application. If necessary contact a Daikin service technician.
E
E
0 - 7
0
1
Time Master
Activation of a system-wide time master. The time master synchronises all controllers in the
RoCon system with the time and date set on the time master. For all other control units in the
system, it is no longer possible to enter the time and date. There must only be one time master
in the entire system. The parameter is not available if the time master parameter is activated on
another controller in the RoCon system.
S
E
Off
On
On
-
System Config
The system configuration of the device, consisting of sensor configuration and data bus config-
uration, can be deleted, activated or deactivated with this parameter. If, when first starting up,
the query for use of the standard configuration is answered with "Yes", settings suitable the basic
configuration of the heat generator are automatically activated (see chap. 6.2.1, tab. 6-1).
S
E
Inactive,
Active,
Delete
Inactive
-
Tab. 6-16 Parameters of the Basic Configuration