Installation
www.DaikinApplied.com 49
IM 1287-4 • REBEL APPLIED ROOFTOP
Fan Block-off Plates
Optional fan block-off plates may be ordered to HELP maintain
reduced capacity functionality in the case of a supply or return
fan failure. A until replacement can be procured and installed.
Fan block-off plates come in two styles, upstream and
downstream.
Upstream Fan Block-off Plate
Upstream fan block-off plates are an option that can be
assembled and applied without having to remove the failed
fan. This block-off plate comes in two pieces which can be
assembled outside the unit with the screws provided and
installed on the upstream side of the fan bulkhead.
shows the proper assembly of the two pieces.
Figure 100: Upstream Block-off Plate Assembly
Once assembled, the upstream block-off plate can be installed
into the unit to cover the inlet of the fan opening. The failed
fan can be left in place for storage until a replacement fan can
shows the proper installation of the
upstream fan block-off plate.
Figure 101: Installing Upstream Block-off Plate
Downstream Fan Block-off Plate
Downstream fan block-off plates are an option that requires
removing the failed fan. This block off plate comes in two
pieces which can be assembled outside the unit with the
screws provided and installed on the downstream side of the
shows the proper assembly of the
two pieces.
Figure 102: Downstream Block-off Plate Assembly
Once assembled, the downstream block-off plate can be
installed in the unit, on the downstream side of the fan wall
bulkhead. The failed fan must be removed in order to install the
downstream block-off plate. However, as an added feature, the
failed supply fan can be reinstalled over the block-off plate, if it
is deemed more convenient for storage purposes.
Figure 103: Installing Downstream Block-off Plate