background image

Low-energy ventilation unit with heat recovery and 

demand-controlled automatic melting

© Vallox
1.09.602 EN
3.12.2013

1  Extract air fan 

 

(behind protective cover)

2  Supply air fan 

 

(behind extract air duct)

3  Outdoor air fi lter F7
4  Heat recovery cell
5  Summer/winter damper
6  Outdoor air fi lter G4
7  Extract air fi lter G4
8  Post-heating radiator 

 

(behind extract air duct)

9  Safety switch
10  Control panel DIGIT SED
11  Carbon dioxide sensor 
12  Humidity sensor 

Code   

3720

Models

VALLOX 096 SE R

VALLOX 096 SE L

Operating, maintenance and technical 

instructions

Electrical connection 

230 V, 50 Hz, 

 5.1 A (plug)

Degree of protection provided by enclosures 

IP 34

Fans 

Extract air 

89 dm

3

/s 100 Pa

direct current (DC)  Supply air 

86 dm

3

/s 100 Pa

Heat recovery  

 

Cross-counter fl ow cell, > 80%

Heat recovery bypass 

Automatic

Electric post-heating unit (standard) 

900 W 3.9 A

Filters 

Supply air 

G4 and F7

 

Extract air 

G4

Weight 

 

53 kg

Ventilation power adjustment 

- Control panel control

 

 

- CO

2

 and %RH control

 

 

- Remote monitoring control (voltage signal)

Options 

 

- CO

2

 sensor 

 

 

- %RH sensor

 

 

- Insulated attic fl oor penetration plate

 

 

- Ceiling mounting plate Vallox 096

TECHNICAL DATA

10

11

The fi gure shows the R model

12

1

6

9

8
2

7

3

5
4

Vallox

096

SE

Summary of Contents for 096 SE R

Page 1: ...erating maintenance and technical instructions Electrical connection 230 V 50 Hz 5 1 A plug Degree of protection provided by enclosures IP 34 Fans Extract air 89 dm3 s 100 Pa direct current DC Supply...

Page 2: ...ring result 1 to 2 carbon dioxide sensors can be connected as options to the VALLOX 096 SE unit The adjustment is switched on off and if needed the setpoint 500 2000 ppm is set at the control panel Th...

Page 3: ...heating indicator light Maintenance reminder symbol Maintenance reminder The maintenance reminder switches on the maintenance reminder symbol on the main display of the control panel at defined interv...

Page 4: ...menu you can change setpoints for the ventilation unit 2 3 Week clock control Week program on Week clock control can be switched on with the button and off with the button Week clock control is on wh...

Page 5: ...water or electric radiator is selected with the and buttons depending on the type of post heating radiator the unit is equipped with Note Choosing the wrong type of post heating may cause a faulty pos...

Page 6: ...ttons The rotation speed of the extract air fan can be decreased by decreasing the percentage Move the cursor with the arrow keys and change values with the and buttons Note that to exit and save when...

Page 7: ...By using original Vallox filters you ensure good operation of the ventilation unit and the best filtering result The replacement interval of filters depends on dust content in ambient air It is recomm...

Page 8: ...you wish to detach the fan lift it upwards and crank the plastic lock to the right using for instance a chisel gure 6 The fan then falls down and can be pulled out of the unit Disconnect the quick co...

Page 9: ...t message is displayed and the unit operates at speed 1 check the fan speed Wiring fault in the carbon dioxide sensor in the control panel or in the humidity sensor or the cable is of the wrong type C...

Page 10: ...ing range E Extract air fan S Supply air fan Input power total W Air flow max dm3 s SFP SFP Specific Fan Power recommended value 2 5 kW m3 s At a lower total pressure SFP will be smaller at this speed...

Page 11: ...P W M 5 4 3 2 1 M 2x0 25 3x0 25 BN WT BN GN connection box on top of the unit 5 3 10 1 FAN CONTROL 0 10 V DC A B M S S 1 2 S S RH1 RH2 RS 485 BUS FAULT SIGNAL FIREPLACE SWITCH 12x0 25mm2 N GND L1 L 1...

Page 12: ...t state In this case remove one of the control panels and change the address of the other panel The above mentioned situation can arise in connection with the later installation of an additional contr...

Page 13: ...t protective enclosure the unit must be located in a place with no acoustic disturbance storerooms technical rooms etc Wall mounting VALLOX 096 SE is mounted on the wall with a mounting plate as shown...

Page 14: ...ting plate in place Then 4 332 544 600 600 push a rubber damper and washer to each thread bar all the way into the cup of the plate and turn the nut Shorten the lower ends of the thread bars so that t...

Page 15: ...l 3467200 10 Filter stand 3464500 No Part Code 11 G4 coarse filter 978045 extract air 12 Bypass duct assembly 3475100 indicate if right or left handed 13 Damper motor 930613 14 Extract air outlet 9850...

Page 16: ...1 09 602E 3 12 2013 PDF...

Reviews: