IM 1287-4 • REBEL APPLIED ROOFTOP 118 www.DaikinApplied.com
Unit Maintenance
Table 20: 400 MBH Analog Staging Information
400 MBH
2 stage
5:1 turn down
10:1 turndown
VDC signal
Total Input
(BTUH)
Section
VDC signal
Total Input
(BTUH)
Section
VDC Signal
Total Input
(BTUH)
Section
4
200,000
A
2.00
80000
A
2.00
40000
A
9.5
400,000
B
2.94
120000
2.41
60000
3.88
160000
2.83
80000
4.83
200000
3.24
100000
5.77
240000
3.66
120000
6.67
280000
4.07
140000
7.62
320000
4.49
160000
8.56
360000
4.90
180000
9.50
400000
5.32
200000
6.18
240000
B
6.60
260000
7.01
280000
7.43
300000
7.84
320000
8.26
340000
8.67
360000
9.09
380000
9.50
400000
Table 21: 600 MBH Analog Staging Information
600 MBH
4 stage
5:1 turn down
10:1 turndown
VDC signal
Total Input
(BTUH)
Section
VDC signal
Total Input
(BTUH)
Section
VDC Signal
Total Input
(BTUH)
Section
3.0
165,000
A - Low
2.00
120000
A
2.00
60000
A
4.0
330,000
A - Low, B -
Low
2.41
142500
2.41
90000
6.0
465000
A - High, B -
Low
2.83
165000
2.83
120000
9.5
600000
A - High, B -
High
3.24
187500
3.24
150000
3.66
210000
3.66
180000
4.07
232500
4.07
210000
4.49
255000
4.49
240000
4.90
277500
4.90
270000
5.32
300000
5.32
300000
6.18
360000
A,B
6.18
360000
A,B
6.60
390000
6.60
390000
7.01
420000
7.01
420000
7.43
450000
7.43
450000
7.84
480000
7.84
480000
8.26
510000
8.26
510000
8.67
540000
8.67
540000
9.09
570000
9.09
570000
9.50
600000
9.50
600000