Unit Wiring
www.DaikinApplied.com 55
IM 1287-4 • REBEL APPLIED ROOFTOP
Field Control Wiring
DANGER
LOCKOUT/TAGOUT all power sources prior to wiring or servicing the unit.
Electrical shock hazard that may cause severe injury or death. Connect only
low voltage NEC Class II circuits to the Error! Reference source not found.
Error! Reference source not found.. Reinstall and secure all protective front
panels when the wiring installation is complete.
Rebel Applied units are available with several control schemes
which may require low voltage field wiring. Use the Unit
Specific Electrical Schematics to determine which control
connections will be required for installation. Check unit specific
electrical documentation in the door of the control panel.
is a graphical representation of TB2 and
shows
the possible field connections that can be made.
Figure 110: Graphical Representation of TB2
Table 12: Potential field Connections and Locations on TB2
Terminal Block Number
Description
Signal
200
Power
24V AC
201
Signal for Tennant Override
Contact Closure
202
Condensate Overflow Switch Contact 1
Contact Closure
203
Condensate Overflow Switch Contact 2 & feed into
SD2 E-stop series
Contact Closure
204
Feed from SD2 into E-Stop Series
Contact Closure
205
Field Provisions for E-Stop
Contact Closure
206
Field Provisions for E-Stop
Contact Closure
207E
Relative Humidity Sensor #1 (ZRH1)
4-20mA
208E
Humidity Sensor
4-20mA
208G
Relative Humidity Sensor #2 (ZRH2)
4-20mA
210
Space Temperature Sensor 1
Thermistor
210E
Space Temperature Sensor 2
thermistor
210G
Space Temperature Sensor 3
thermistor
212
Setpoint Adjustment, Wallstat
Signal
214
CO2 / Ext OA Reset
0-10V DC
215
Alarm Output
24VAC relay
216
Alarm Return
24VAC relay
217
Fan Operation
24VAC relay
220
Freezestat Sensor Terminal 1
Contact Closure
221
Freezestat Sensor Terminal 2
Contact Closure
231
Alarm Reset
Contact Closure
236
Controller Common
240
Local / Remote Status
relay output
240C
System Ready Output
relay output
242
Cooling system Interlock (From Field)
Contact Closure
246
Reheat Valve Cmd
0-10V DC
247
Cooling Capacity Input
0-10V DC
250
Cooling Actual Capacity Output
0-10V DC
267
SAF1 Capacity Cmd (From Field)
0-10V DC
275
EF Capacity Cmd (From Field)
0-10V DC
296A
Return Air SD Aux Contact
relay output
296B
Return Air SD Aux Contact
relay output
296C
Supply Air SD Aux Contact
relay output
296D
Supply Air SD Aux Contact
relay output
297
Passive Ventilation Input
Contact Closure
297A
Passive Ventilation Input
Contact Closure
2100
Smoke Purge - Purge
Contact Closure
2101
Smoke Purge - Pressurize
Contact Closure
2102
Smoke Purge - Vent
Contact Closure
2103
Smoke Purge - Shutdown
Contact Closure