Unit Operation
www.DaikinApplied.com 79
IM 1287-4 • REBEL APPLIED ROOFTOP
Keypad and Display Menu Structure
The following is a description of the MicroTech 4 menu structure. These menus and items can all be displayed with the keypad/
display. Menu items displayed will change based on the selected unit configuration. Refer to
Figure 135: Main Menu – Keypad/Display Menu Structure
Figure 136: Main Menu – Keypad/Display Menu Structure
Main Menu
Enter Password
►
Quick Menu
►
View Status
►
Unit State=_________
Unit Status=________
MWU Status=_______
System Mode= ______
ClgIntrLock= _______
Dehum Status=______
Ctrl Mode= Off
Occ Mode= Auto
Commission Unit
►
Manual Control
►
Service Menus
►
Advanced Menus
►
Trending Set-Up
►
Unit Maintenance
►
BMS Communications
►
Alarm Lists
►
About This Unit
►
Enter Password
Enter Password
*******
About This Unit
SO_Item= 123456_12345
Unit SN= FBOU123456789
App Version= 2506018xxx
Cf1-15= xxxxxxxxxxxxxxxx
Cf6-29= xxxxxxxxxxxxxxxx
Main BSP= X.XX
LON BSP= X.XX
LON App Ver= X.XX
BACnet BSP= X.XX
HMI GUID=
xxxxxxxx-xxxx-xxxx-xxxx-
xxxxxxxxxxxx
OBH GUID=
xxxxxxxx-xxxx-xxxx-xxxx-
xxxxxxxxxxxx
Quick Menu
Unit State=_____________
Min DAT Limit= 55.0°F
Unit Status=____________
Unocc Clg Spt= 85.0°F
MWU Status=___________
Unocc Htg Spt= 55.0°
Dehum Status=__________
SAF Capacity= XXX%
System Mode= Local
SAF Duct Press= X.Xin
ClgIntrLock=____________
SAF DSP Spt= 1.0in
DH Bleeddown=_________
RF/EF Cap = XXX%
Ctrl Mode= Off
Bldg Press= X.XXin
Occ Mode= Auto/Net
BldgSP Spt= 0.05in
Clg Capacity= XXX%
RAF DuctPress=X.XX in
OAD Position= XXX%
RAF DSP Spt= -1.0 in
Htg Capacity= XXX%
CO2 PPM = XXXXppm
Rht Cap= XXX%
OA Flow= XXXXXCFM
Control Temp= XXX°F
MinOAFlw Spt= 2000CFM
Occ Clg Spt= 72.0°F
SAF Flow= XXXXXCFM
Occ Htg Spt= 68.0°F
SAF Flow Spt= 2000CFM
Disch Air= XXX°F
OA Temp = XXX°F
DAT Clg Spt= 55.0°F
Rel Hum1 = XXX%
DAT Htg Spt= 85.0°F
Rel Hum2 = XXX%
Manual Control
Manual Ctrl= Normal
CondSolCirc1= Off
Supply Fan= Off
CondSolCirc2= Off
SAF Cap Cmd= 0%
EVI1 Cap= 0%
OAF1 Circ1 = Off
EVI2 Cap= 0%
OAF2 Circ1 = Off
EHGBP1 Cap=0%
OAFs Circ1 = Off
EHGBP2 Cap=0%
OF2 Ovrd Circ1 = Off
CW Valve=0%
OAFCap Circ1= 0%
Heat Enable= Off
OAF1 Circ2 = Off
Htg Valve= 0
OAF2 Circ2 = Off
SCR Capacity= 0%
OAFs Circ2 = Off
F&BP Damper= 0%
OF2 Ovrd Circ2 = Off
Htg Stg 1= Off
OAFCap Circ2= 0%
Htg Stg 2= Off
Exh Dampers= 0%
Htg Stg 3= Off
Ret/Exh Fan= Off
Htg Stg 4= Off
RF/EF Cap Cmd= 0%
MHGRht Valve= 0%
OADamperPos= 0%
RH Bleed Valve= Off
VCmp1= Off
LSCRht Valve= 0%
VCmp1 Cmd= 0%
ER Wheel= Off
VCmp2= Off
ER Whl CapCmd= 0%
VCmp2 Cmd= 0%
ERBP Dmpr Cl= Off
FCmp1= Off
ERBP Dmpr Op= Off
FCmp2= Off
SCR Preheat= 0%
FCmp3= Off
Alm Output= Off
FCmp4= Off
Aux Output= Off
FCmp5= Off
FCmp6= Off
Trending Set-Up
Apply Chgs= No
Sample Time= 60s
TrendOnOff= On
Enable Trend1= Yes
Enable Trend2= No
Enable Trend3= No
Enable Trend4= No
EnaFreeTrend= No
AutoExpTime=1440 min
Export Data= No
Clear Trend= Done
TrendFull = Wrap
Unit Maintenance
Operating Hours
►
Air Filters
►
Operating Hours
Supply Fan= XXXXXh
Ret/Exh Fan= XXXXXh
Cooling= XXXXXh
Heating= XXXXXh
Economizer= XXXXXh
Tnt Override= XXXXXh
VCmp1= XXXXXh
VCmp2= XXXXXh
FCmp1= XXXXXh
FCmp2= XXXXXh
FCmp3= XXXXXh
FCmp4= XXXXXh
FCmp5= XXXXXh
FCmp6= XXXXXh
Dehumid= XXXXXh
Reheat= XXXXXh
ER Wheel= XXXXXh
ER Preheat= XXXXXh
Air Filters
MainFltrSpt1= 0.5in
MainFltrPres1= _________
MainFltrSpt2= 0.5in
MainFltrPres2= _________
MainFltrSw= ____________
FinalFltrSpt= 0.5in
FinalFltrPres= __________
FinalFltrSw= ____________