Unit Operation
www.DaikinApplied.com 77
IM 1287-4 • REBEL APPLIED ROOFTOP
MicroTech 4 Field Installed Sensors
The MicroTech 4 unit controller can be connected to a variety
of field installed sensors.
• Space Sensor with tenant override – Daikin PN:
113117701
• DDC Space Sensor with Setpoint Adjust and Tenant
Override – Daikin PN: 910143408
• Combo DDC Temp and Humidity Sensor with Setpoint Adj
and Tnt Ovrd – Daikin PN: 910191961
• Communicating Network Space Sensors – Daikin PN:
910279216 and 910278050
• Space Humidity Sensor – Daikin PN: 910202119
• Wall Mounted CO
2
Sensor – Daikin PN: 107287012
• Duct Mounted CO
2
Sensor – Daikin PN: 910111672
Space Temperature Sensors
The Rebel Applied MicroTech 4 works with 10kohm Type 2
thermistors and can support up to 3 sensors. These sensors
can drive cooling and heating based on the highest, lowest, or
average space sensor reading.
DDC Space Sensors
The Rebel Applied MicroTech 4 works with 10kohm Type 2
thermistors and can support up to 3 sensors. These sensors
can drive cooling and heating based on the highest, lowest,
or average space sensor reading. A Combo sensor version
provides Temperature and humidity.
NOTE:
Only one sensor can drive the Setpoint adjustment.
Figure 132: Daikin Space Sensor
Communicating Network Space Sensors
The MicroTech 4 unit controller can be connected to a Network
of the 3 space sensors as either a temperature sensor only
or a temeprature, Humidity and CO
2
combo sensor. Each
Sensor comes with a backlit LCD screen to show current
space conditions, allow setpoint adjustment and commupance
commands.
• Network Temperature Sensor – Part Number 910279216
• Network Combo Temeprature Sensor – Part Number
910278050
Figure 133: Network Space Sensor
The MicroTech 4 can support up to 3 Network (QMX) sensors
wired to the Process Bus terminals with a Daisy Chain Twisted
pair. Refer to
for MicroTech 4 configuration and set-
up instructions
NOTE:
The sensor is available in English units only and does
not show SI units.
Figure 134: QMX Sensor
for MicroTech 4 configuration and
set-up instruction
NOTE:
The sensor is available in English units and does
not show SI units.