background image

LREQ5~20B7Y1

Air cooled refrigeration condensing unit

4PW74302-1D – 2016.11

Installation manual

2

• Do not touch the refrigerant piping, water piping or internal parts 

during and immediately after operation. It could be too hot or too 
cold. Give it time to return to normal temperature. If you must touch 
it, wear protective gloves.

• Works executed on the outdoor unit are best done under dry 

weather conditions to avoid water ingress.

• In accordance with the applicable legislation, it might be necessary 

to provide a logbook with the product containing at least: 
information on maintenance, repair work, results of tests, stand-by 
periods,…

 

Also, at least, following information must be provided at an 
accessible place at the product:
• Instructions for shutting down the system in case of an 

emergency

• Name and address of fire department, police and hospital
• Name, address and day and night telephone numbers for 

obtaining service

• In Europe, EN378 provides the necessary guidance for this 

logbook.

CAUTION

• Carry out drain piping properly following this installation manual 

and insulate the pipe to prevent condensation.

 

Improper drain piping may result in indoor water leakage and 
property damage.

• Install the indoor and outdoor units, power cord and connecting 

wires at least 1 meter away from televisions or radios to prevent 
picture interference and noise. 

 

(Depending on the incoming signal strength, a distance of 1 meter 
may not be sufficient to eliminate noise.)

• Do not install the condensing unit in the following locations:

1. Where there is a high concentration of mineral oil spray or 

vapour (e.g. a kitchen). 

 

Plastic parts may deteriorate and cause parts to fall off or water 
to leak.

2. Where corrosive gas, such as sulphurous acid gas, is produced.

 

Corrosion of copper pipes or brazed parts may occur and cause 
refrigerant leakage. 

3. Where there is a machine that generates electromagnetic wave 

and where voltage fluctuation often occurs such as a factory.

 

Control system may malfunction and as a result the unit may 
not properly operate.

4. Where flammable gas may leak, where carbon fibre or ignitable 

dust is suspensions in the air, or where volatile flammables 
such as paint thinner or gasoline are handled.

 

Operating the unit in such conditions may result in fire.

5. Vehicles, ships, or other places that generate vibration or cause 

the condensing unit to move.

 

The condensing unit may malfunction or cause oxygen 
deficiency accidents as a result of refrigerant leakage.

6. Places with excessive voltage fluctuations.

 

The condensing unit may malfunction.

7. Places where fallen leaves accumulate or weeds grow thick.
8. Places that become small animals’ shelter.

 

Small animals coming in contact with electrical parts can cause 
malfunctions, smoke, or ignition.

• The condensing unit is not intended for use in a potentially 

explosive atmosphere.

1-2 Special notice of product

This condensing unit comes under the term “appliances not 
accessible to the general public”.
[CLASSIFICATION]

This condensing unit comes under the term “appliances not 
accessible to the general public”.
Refer to the connected indoor unit to know the climate class 
(EN60335-2-89).

[EMC CHARACTERISTICS]

This system is a class A product. In a domestic environment this 
product may cause radio interference in which case the user may be 
required to take adequate measures.

[REFRIGERANT]
This System use R410A refrigerant.

CAUTION

This unit is already filled with a certain amount of R410A.

 

Never open liquid and gas shutoff valve until the step specified in 

"9. CHECKS AFTER WORK COMPLETION" on page 16

.

• The refrigerant R410A requires that strict precautions be observed 

for keeping the system clean, dry and tightly sealed.

 

Read the chapter 

"6. REFRIGERANT PIPING" on page 6

 carefully 

and follow these procedures correctly.
A.Clean and dry

 

Strict measures must be taken to keep impurities (including SUNISO 
oil and other mineral oils as well as moisture) out of the system.

B.Tightly sealed

 

Take care to keep the system tight when installing.

 

R410A contains no chlorine, does not destroy the ozone layer 
and so does not reduce the earth’s protection against harmful 
ultraviolet radiation. R410A will contribute only slightly to the 
greenhouse effect if released into the atmosphere.

• Since R410A is a mixed refrigerant, the required additional 

refrigerant must be charged in its liquid state. If the refrigerant is 
charged in a state of gas, its composition changes and the system 
will not work properly.

Be sure to perform refrigerant replenishment. 

 

Refer to

  

"9. CHECKS AFTER WORK COMPLETION" on page 16

the label of instructions on refrigerant replenishment on the cover 
surface of the control box, and 

"12-1 Calculation method" on page 19

.

Important information regarding the refrigerant used

This product contains fluorinated greenhouse gases. Do not vent 
gases into the atmosphere.
Refrigerant type: R410A

 

Global warming potential (GWP) value: 2087.5

To fix the fluorinated greenhouse gases label

1.

Fill in the label as follows:

1

If a multilingual fluorinated greenhouse gases label is delivered 
with the unit (see accessories), peel off the applicable language 
and stick it on top of 

1

.

2

Factory refrigerant charge: see unit name plate

3

Additional refrigerant amount charged

4

Total refrigerant charge

5 Greenhouse gas emissions

 of the total refrigerant charge 

expressed as tonnes CO

2

-equivalent

6

GWP = Global warming potential

CAUTION

In Europe, the 

greenhouse gas emissions

 of the total 

refrigerant charge in the system (expressed as tonnes CO

2

-

equivalent) is used to determine the maintenance intervals. 
Follow the applicable legislation.

Formula to calculate the greenhouse gas emissions:

 GWP 

value of the refrigerant × Total refrigerant charge [in kg] / 1000

2.

Fix the label on the inside of the outdoor unit near the gas and 
liquid stop valves.

[DESIGN PRESSURE]

Since design pressure is 3.8 MPa or 38 bar (for R407C units : 
3.3 MPa or 33 bar), the wall thickness of pipes should be more 
carefully selected in accordance with the relevant local and national 
regulations.

1-3 Disposal requirements

Dismantling of the unit, treatment of the refrigerant, of oil and of other 
parts must be done in accordance with relevant local and national 
legislation.

2

Contains fluorinated greenhouse gases

2

1

1

1

2

2

kg

tCO

2

eq

GWP × kg

1000

=

=

+

kg

=

kg

=

GWP: XXX

RXXX

1

6

3

4

5

4PWEN74302-1D.book  Page 2  Thursday, April 27, 2017  9:01 PM

Summary of Contents for LREQ-BY1

Page 1: ...INSTALLATION MANUAL LREQ5B7Y1 LREQ6B7Y1 LREQ8B7Y1 LREQ10B7Y1 LREQ12B7Y1 LREQ15B7Y1 LREQ20B7Y1 Air cooled refrigeration condensing unit 4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Page 2: ...det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bed mmelse av E Anvendt modul F G Risikokategori H Se ogs neste side 13 jotka on esitetty asiakirjassa A ja jotka B on hyv ksynyt...

Page 3: ...peratuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimalus leistinas sl gis PS K...

Page 4: ...lectric shocks or fire When installing the unit in a small room take measures so that the refrigerant may not exceed the limiting concentration in the event of refrigerant leakage Contact your dealer...

Page 5: ...connected indoor unit to know the climate class EN60335 2 89 EMC CHARACTERISTICS This system is a class A product In a domestic environment this product may cause radio interference in which case the...

Page 6: ...d on the size specified by the solenoid valve and mechanical thermostatic expansion valve being used Route the path to the indoor unit heat exchanger so that the flow of refrigerant is from top to bot...

Page 7: ...l height on the suction side no higher than 500 mm Wall height for sides no limit If the height is exceeded the above calculate h1 and h2 shown in the figure below and add h1 2 to the service space of...

Page 8: ...be attached attach it to the whole face of the base The height of the base should be at least 150 mm from the floor Secure the unit to its base using foundation bolts Use four commercially available M...

Page 9: ...adverse influence of residual substances such as the oxidation of refrigerant oil and the generation of scale is considered If the indoor unit or outdoor unit is disconnected from the piping for a lo...

Page 10: ...is required at 5 m intervals from outdoor unit d1 e B d2 C c D1 F E f D2 A b a Outdoor unit Showcase Unit cooler Gas piping Liquid piping H Refrigerant piping size Unit mm Outdoor unit side Piping siz...

Page 11: ...yer 6 5 Connecting the refrigerant piping CAUTION In addition to gas and liquid shutoff valves this unit has a maintenance shutoff valve see diagram below Do not operate the maintenance shutoff valve...

Page 12: ...proceed with connection of the field piping 1 Service port 2 Stop valve 3 Point of pipe cutting just above brazing point or above marking A Pinched piping B Pinched piping CAUTION Precautions when con...

Page 13: ...the screw thread Do not apply a screw lock agent for flare nut use to the sealing part Be sure to tighten the cap securely after the work Refer to Operation Method of Shutoff Valves on page 9 for the...

Page 14: ...effect but also may cause capacitor abnormal heating accident due to high frequency waves Only proceed with wiring work after blocking off all power Always ground wires in accordance with relevant lo...

Page 15: ...aker 14 Earth leakage circuit breaker 15 Panel 16 Run input 17 Earth 18 OFF Normal mode ON Low noise mode Note Use conduit for power supply wiring Make sure the weak electric wiring i e for the remote...

Page 16: ...provided that the system impedance Zsys is less than or equal to Zmax and EN IEC61000 3 12 2 provided that the short circuit power Ssc is greater than or equal to the minimum Ssc value at the interfac...

Page 17: ...arth wire may not contact sufficiently and the earthing effect of the wire may be lost Do not finish strand wire with solder 7 4 Procedure for wiring inside units Referring to the following figure sec...

Page 18: ...s no decrease in the pressure over a period of 24 hours If there is a decrease in the pressure check for and repair leaks Vacuum drying Operate the vacuum pump for more than three hours from the servi...

Page 19: ...7 2 Make sure insulation work is done See 8 2 Thermal insulation work on page 15 3 Make sure there is no faulty refrigerant piping See 6 REFRIGERANT PIPING on page 6 9 CHECKS AFTER WORK COMPLETION Mak...

Page 20: ...peration switch of the outdoor unit after the speci fied amount of refrigerant is replenished To prevent liquid compression e Caution Fully open the shutoff valves on the gas and liquid sides promptly...

Page 21: ...ion code items can be displayed on the condensing unit 1 Make sure that the LED H1P is off If the LED is on press the MODE button BS1 once 2 Press the MODE button BS1 once The LED H1P starts blinking...

Page 22: ...3 7 10 Calculate the amount of all refrigerant in this system 8 Table 1 Capacity and amount of refrigerant of the indoor unit Show case and Blower coil Note 1 Case of showcase the condition of capaci...

Page 23: ...4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Page 24: ...4PW74302 1D 2016 11 Copyright 2012 Daikin 4PW74302 1 D 0000000L 4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Reviews: