LREQ5~20B7Y1

Air cooled refrigeration condensing unit

4PW74302-1D – 2016.11

Installation manual

14

Remote switch wiring connections

• When installing a remote switch, clamp as indicated by the 

following diagram:

X3M wire specifications

Wiring connection for low-noise mode

• Wiring connection for low-noise mode: clamp as indicated by the 

following diagram:

X1M (A5P) wire specifications

CAUTION

• For Remote switch, use non-voltage contact for microcurrent (not 

more than 1 mA, 12 V DC)

• If the remote switch will be used to start and stop the unit, set the 

operating switch to “REMOTE”.

Precautions for terminal connections

• Be sure to use ring-type crimp-style terminals provided with 

insulation sleeves.

• Use specified electric wires for the wiring and secure the wiring so 

that external force will not be imposed on the terminal block.

• Use an appropriate screwdriver to tighten the terminal screws.

 

Small-sized screwdriver will damage the screw heads and cannot 
tighten the screws properly.

• Do not tighten the terminal screws in excess, otherwise the screws 

may be damaged.

• Refer to the following table for the tightening torque values of the 

terminal screws.

• Take out the earth wire from the notch of the cup washer and lay 

the wire carefully so that other wires will not be caught by the 
washer. Otherwise, the earth wire may not contact sufficiently and 
the earthing effect of the wire may be lost.

• Do not finish strand wire with solder.

7-4 Procedure for wiring inside units

• Referring to the following figure, secure and wire the power and 

transmission wiring using the accessory clamp (1), (2).

• Lay the ground wire so that it will not come in contact with the lead 

wires of the compressor. Other equipment will be adversely 
affected if the ground wire comes in contact with the lead wires of 
the compressor.

• Make sure all wiring do not contact to the pipes (hatching parts in 

the figure).

• The transmission wiring must be at least 50 mm away from the 

power wiring.

• After wiring work is completed, check to make sure there are no 

loose connections among the electrical parts in the control box.

Electric wire thickness

0.75~1.25 mm

2

Max. wiring length

130 m

Electric wire thickness

0.75~1.25 mm

2

Max. wiring length

130 m

X3M

2

1

Secure remote 
switch wiring to the 
resin block using a 
clamp (field supply).

Wiring for low-noise 
mode: wiring to the 
resin block using a 
clamp (field supply).

X1A

X1M

A5P

A B C

Crimp-style terminal

Insulating sleeve

Power wire

Screw size

Tightening torque (N•m)

M8 (Power supply terminal block)

5.5 - 7.3

M8 (Earth)
M4 (X2M)

2.39 - 2.91

M3.5 (X3M)

0.79 - 0.97

Crimp-style terminal

Cup washer

Cut out section 

LREQ5, LREQ6

1

9

10

4

A1P

X3M

X2M

6

14

7

2

12

A5P

5

8

X1M

13

3

11

LREQ8~20

8

11

12

13

15

16

9

6

X1M

X1M

X3M

A5P

A1P

X2M

14

3

1

2

10

5

4

7

13

14

4PWEN74302-1D.book  Page 14  Thursday, April 27, 2017  9:01 PM

Summary of Contents for LREQ-BY1

Page 1: ...INSTALLATION MANUAL LREQ5B7Y1 LREQ6B7Y1 LREQ8B7Y1 LREQ10B7Y1 LREQ12B7Y1 LREQ15B7Y1 LREQ20B7Y1 Air cooled refrigeration condensing unit 4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Page 2: ...det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bed mmelse av E Anvendt modul F G Risikokategori H Se ogs neste side 13 jotka on esitetty asiakirjassa A ja jotka B on hyv ksynyt...

Page 3: ...peratuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimalus leistinas sl gis PS K...

Page 4: ...lectric shocks or fire When installing the unit in a small room take measures so that the refrigerant may not exceed the limiting concentration in the event of refrigerant leakage Contact your dealer...

Page 5: ...connected indoor unit to know the climate class EN60335 2 89 EMC CHARACTERISTICS This system is a class A product In a domestic environment this product may cause radio interference in which case the...

Page 6: ...d on the size specified by the solenoid valve and mechanical thermostatic expansion valve being used Route the path to the indoor unit heat exchanger so that the flow of refrigerant is from top to bot...

Page 7: ...l height on the suction side no higher than 500 mm Wall height for sides no limit If the height is exceeded the above calculate h1 and h2 shown in the figure below and add h1 2 to the service space of...

Page 8: ...be attached attach it to the whole face of the base The height of the base should be at least 150 mm from the floor Secure the unit to its base using foundation bolts Use four commercially available M...

Page 9: ...adverse influence of residual substances such as the oxidation of refrigerant oil and the generation of scale is considered If the indoor unit or outdoor unit is disconnected from the piping for a lo...

Page 10: ...is required at 5 m intervals from outdoor unit d1 e B d2 C c D1 F E f D2 A b a Outdoor unit Showcase Unit cooler Gas piping Liquid piping H Refrigerant piping size Unit mm Outdoor unit side Piping siz...

Page 11: ...yer 6 5 Connecting the refrigerant piping CAUTION In addition to gas and liquid shutoff valves this unit has a maintenance shutoff valve see diagram below Do not operate the maintenance shutoff valve...

Page 12: ...proceed with connection of the field piping 1 Service port 2 Stop valve 3 Point of pipe cutting just above brazing point or above marking A Pinched piping B Pinched piping CAUTION Precautions when con...

Page 13: ...the screw thread Do not apply a screw lock agent for flare nut use to the sealing part Be sure to tighten the cap securely after the work Refer to Operation Method of Shutoff Valves on page 9 for the...

Page 14: ...effect but also may cause capacitor abnormal heating accident due to high frequency waves Only proceed with wiring work after blocking off all power Always ground wires in accordance with relevant lo...

Page 15: ...aker 14 Earth leakage circuit breaker 15 Panel 16 Run input 17 Earth 18 OFF Normal mode ON Low noise mode Note Use conduit for power supply wiring Make sure the weak electric wiring i e for the remote...

Page 16: ...provided that the system impedance Zsys is less than or equal to Zmax and EN IEC61000 3 12 2 provided that the short circuit power Ssc is greater than or equal to the minimum Ssc value at the interfac...

Page 17: ...arth wire may not contact sufficiently and the earthing effect of the wire may be lost Do not finish strand wire with solder 7 4 Procedure for wiring inside units Referring to the following figure sec...

Page 18: ...s no decrease in the pressure over a period of 24 hours If there is a decrease in the pressure check for and repair leaks Vacuum drying Operate the vacuum pump for more than three hours from the servi...

Page 19: ...7 2 Make sure insulation work is done See 8 2 Thermal insulation work on page 15 3 Make sure there is no faulty refrigerant piping See 6 REFRIGERANT PIPING on page 6 9 CHECKS AFTER WORK COMPLETION Mak...

Page 20: ...peration switch of the outdoor unit after the speci fied amount of refrigerant is replenished To prevent liquid compression e Caution Fully open the shutoff valves on the gas and liquid sides promptly...

Page 21: ...ion code items can be displayed on the condensing unit 1 Make sure that the LED H1P is off If the LED is on press the MODE button BS1 once 2 Press the MODE button BS1 once The LED H1P starts blinking...

Page 22: ...3 7 10 Calculate the amount of all refrigerant in this system 8 Table 1 Capacity and amount of refrigerant of the indoor unit Show case and Blower coil Note 1 Case of showcase the condition of capaci...

Page 23: ...4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Page 24: ...4PW74302 1D 2016 11 Copyright 2012 Daikin 4PW74302 1 D 0000000L 4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Reviews: