background image

LREQ5~20B7Y1

Air cooled refrigeration condensing unit

4PW74302-1D – 2016.11

Installation manual

16

• Liquid pipe arrival minimum temperature 0°C

 

Gas pipe arrival minimum temperature –45°C

• Reinforce the insulation material for the refrigerant piping 

according to the environment of thermal installation. Otherwise, the 
surface of the insulation material may result in dew condensation.

• If the dew condensation water on the shutoff valves is likely to flow 

to the indoor unit side through the clearance between the insulation 
material and piping because the outdoor unit is installed above the 
indoor unit or for some other reasons, perform appropriate 
treatment such as the caulking of the joints (see the illustrations 
below).

• Attach the cover of the piping outlet with a knock hole opened. If 

there is a feature of small animals intruding through the piping 
outlet, cover the piping outlet with a blocking material (field supply) 
on completion of the steps of 

"10. REFRIGERANT 

REPLENISHMENT" on page 16

 (see the illustrations below).

 

Use the piping outlet for jobs required during the steps of 

"10. REFRIGERANT REPLENISHMENT" on page 16

 (e.g., a job 

of taking in the charge hose).

Note

• After knocking out the holes, we recommend you remove burrs in 

the knock holes and paint the edges and areas around the edges 
using the repair paint.

8-3 Checking of device and installation conditions

Be sure to check the followings.

For those doing electrical work

See 

"7-2 Procedure for incoming wiring" on page 12

.

1.

Make sure there is no faulty power wiring or loosing of a nut.

 

See 

"7-3 Procedure for power supply wiring" on page 13

.

2.

Has the insulation of the main power circuit deteriorated?

 

Measure the insulation and check the insulation is above regular 
value in accordance with relevant local and national regulations.

For those doing pipe work

1.

Make sure piping size is correct.

 

See 

"6-1 Selection of piping material" on page 7

.

2.

Make sure insulation work is done. 

 

See 

"8-2 Thermal insulation work" on page 15

.

3.

Make sure there is no faulty refrigerant piping.

 

See 

"6. REFRIGERANT PIPING" on page 6

.

9. CHECKS AFTER WORK COMPLETION

• Make sure the following works are complete in accordance with the 

installation manual.

Piping work

Wiring work

Air tight test/vacuum drying

Installation work for indoor unit

10. REFRIGERANT REPLENISHMENT

For refrigerant filling contractor

Use R410A for refrigerant replenishment.
The R410A refrigerant cylinder is painted with a pink belt.

Warning

Electric Shock Warning

• Securely close the control box lid before turning power on.
• Before turning power on, check through the inspection hole (on the 

left-hand side) of the control box lid that the operation switch is set 
to OFF.

 

If the operation switch is set to ON, the fan may rotate.

• Check the LED indicators on the PCB (A1P) of the outdoor unit 

through the inspection hole (on the right-hand side) of the control 
box lid after the outdoor unit is turned on (see the illustration).

 

(The compressor will not operate for approximately 2 minutes after 
the outdoor unit is turned on.

 

H2P blinks for the first five seconds when the power supply is 
turned on. If the equipment is normal, H2P will be turned off in five 
seconds. H2P lights for abnormality.)

Liquid side 
shutoff valve

Gas side 
shutoff valve

Indoor/Outdoor 
interunit piping

Insulation material

Coking, etc.

Piping lead-out 
hole lid

Gas side piping

Liquid side piping

Open a knock 
hole at

Block 

Inspection hole 
(left-hand side)

Inspection hole 
(right-hand side)

Control box

Inspection hole (left-hand side) 
(upper left-hand side of control box)

Inspection hole (right-hand side) 
(upper right-hand side of control box)

Control box lid

LED

(H1P~8P)

Lift up this tab and 
open the cover.

Inspection 
hole cover

REMOTE OFF

ON

Operation switch 

(factory set: OFF)

( )

Setting of spare parts

For details please refer to the 
INSTRUCTION FOR REPAIR 
WITH SPARE PARTS

OFF

ON

ON

OFF

The evaporation 
temperature setting

Setting by dip switches

It is not used

1

3

DS1

2

3

4

1

2

4

DS2

4PWEN74302-1D.book  Page 16  Thursday, April 27, 2017  9:01 PM

Summary of Contents for LREQ-BY1

Page 1: ...INSTALLATION MANUAL LREQ5B7Y1 LREQ6B7Y1 LREQ8B7Y1 LREQ10B7Y1 LREQ12B7Y1 LREQ15B7Y1 LREQ20B7Y1 Air cooled refrigeration condensing unit 4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Page 2: ...det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bed mmelse av E Anvendt modul F G Risikokategori H Se ogs neste side 13 jotka on esitetty asiakirjassa A ja jotka B on hyv ksynyt...

Page 3: ...peratuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimalus leistinas sl gis PS K...

Page 4: ...lectric shocks or fire When installing the unit in a small room take measures so that the refrigerant may not exceed the limiting concentration in the event of refrigerant leakage Contact your dealer...

Page 5: ...connected indoor unit to know the climate class EN60335 2 89 EMC CHARACTERISTICS This system is a class A product In a domestic environment this product may cause radio interference in which case the...

Page 6: ...d on the size specified by the solenoid valve and mechanical thermostatic expansion valve being used Route the path to the indoor unit heat exchanger so that the flow of refrigerant is from top to bot...

Page 7: ...l height on the suction side no higher than 500 mm Wall height for sides no limit If the height is exceeded the above calculate h1 and h2 shown in the figure below and add h1 2 to the service space of...

Page 8: ...be attached attach it to the whole face of the base The height of the base should be at least 150 mm from the floor Secure the unit to its base using foundation bolts Use four commercially available M...

Page 9: ...adverse influence of residual substances such as the oxidation of refrigerant oil and the generation of scale is considered If the indoor unit or outdoor unit is disconnected from the piping for a lo...

Page 10: ...is required at 5 m intervals from outdoor unit d1 e B d2 C c D1 F E f D2 A b a Outdoor unit Showcase Unit cooler Gas piping Liquid piping H Refrigerant piping size Unit mm Outdoor unit side Piping siz...

Page 11: ...yer 6 5 Connecting the refrigerant piping CAUTION In addition to gas and liquid shutoff valves this unit has a maintenance shutoff valve see diagram below Do not operate the maintenance shutoff valve...

Page 12: ...proceed with connection of the field piping 1 Service port 2 Stop valve 3 Point of pipe cutting just above brazing point or above marking A Pinched piping B Pinched piping CAUTION Precautions when con...

Page 13: ...the screw thread Do not apply a screw lock agent for flare nut use to the sealing part Be sure to tighten the cap securely after the work Refer to Operation Method of Shutoff Valves on page 9 for the...

Page 14: ...effect but also may cause capacitor abnormal heating accident due to high frequency waves Only proceed with wiring work after blocking off all power Always ground wires in accordance with relevant lo...

Page 15: ...aker 14 Earth leakage circuit breaker 15 Panel 16 Run input 17 Earth 18 OFF Normal mode ON Low noise mode Note Use conduit for power supply wiring Make sure the weak electric wiring i e for the remote...

Page 16: ...provided that the system impedance Zsys is less than or equal to Zmax and EN IEC61000 3 12 2 provided that the short circuit power Ssc is greater than or equal to the minimum Ssc value at the interfac...

Page 17: ...arth wire may not contact sufficiently and the earthing effect of the wire may be lost Do not finish strand wire with solder 7 4 Procedure for wiring inside units Referring to the following figure sec...

Page 18: ...s no decrease in the pressure over a period of 24 hours If there is a decrease in the pressure check for and repair leaks Vacuum drying Operate the vacuum pump for more than three hours from the servi...

Page 19: ...7 2 Make sure insulation work is done See 8 2 Thermal insulation work on page 15 3 Make sure there is no faulty refrigerant piping See 6 REFRIGERANT PIPING on page 6 9 CHECKS AFTER WORK COMPLETION Mak...

Page 20: ...peration switch of the outdoor unit after the speci fied amount of refrigerant is replenished To prevent liquid compression e Caution Fully open the shutoff valves on the gas and liquid sides promptly...

Page 21: ...ion code items can be displayed on the condensing unit 1 Make sure that the LED H1P is off If the LED is on press the MODE button BS1 once 2 Press the MODE button BS1 once The LED H1P starts blinking...

Page 22: ...3 7 10 Calculate the amount of all refrigerant in this system 8 Table 1 Capacity and amount of refrigerant of the indoor unit Show case and Blower coil Note 1 Case of showcase the condition of capaci...

Page 23: ...4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Page 24: ...4PW74302 1D 2016 11 Copyright 2012 Daikin 4PW74302 1 D 0000000L 4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Reviews: