background image

Installation manual

3

LREQ5~20B7Y1

Air cooled refrigeration condensing unit

4PW74302-1D – 2016.11

2. BEFORE INSTALLATION

CAUTION

• When installing the indoor unit, refer to the installation manual 

provided for the indoor unit.

• Optional accessories are required for the installation of the 

product. Refer to the information on optional accessory.

2-1 Standard supplied accessories

The following accessories are included. The storage location of the 
accessories is shown in the figure.

Note

Do not throw away any of the accessories until installation is complete.

2-2 Model series

LREQ5~20

2-3 Example of system configuration

1

Operation manual 

2

Installation manual 

3

Clamps

4

Accessory pipes (Installed on bottom frame)

2-4 Indoor unit constraints

• Install an R410A mechanical thermostatic expansion valve on 

each indoor unit.

• Insulate the feeler block of the mechanical thermostatic expansion 

valve.

• Install an R410A solenoid valve (Max. operating differential 

pressure of 3.5 MPa [35 bars] or over) on the primary side of the 
mechanical thermostatic expansion valve described above for 
each indoor unit.

• Install a filter on the primary side of the solenoid valve described 

above for each indoor unit. Determine the filter mesh count based 
on the size specified by the solenoid valve and mechanical 
thermostatic expansion valve being used.

• Route the path to the indoor unit heat exchanger so that the flow of 

refrigerant is from top to bottom.

• When installing a number of indoor units, be sure to install them at 

the same level.

• Use either off-cycle defrosting or electric heater defrosting as the 

defrosting type. Hot-gas defrosting models cannot be used.

• Set the total value of the internal volume for the evaporator 

(Refrigerator/Freezer) to connect and the amount of refrigerant 
inside the evaporator that can be recovered in the condenshing 
unit by closing the liquid solenoid valve installed on the 
refrigeration-side to the below amount or lower.

 

LREQ5, 6: 22 l or lower

 

LREQ8, 10, 12: 33 l or lower

 

LREQ15, 20: 42 l or lower

Name

Clamp (1)

Clamp (2)

Gas side 

accessory 

pipe (1)

Gas side 

accessory 

pipe (2)

Quantity

9 pcs.

2 pcs.

1 pc.

1 pc.

Shape

Small

Name

Liquid side acces-

sory 

pipe (1)

Liquid side acces-

sory 

pipe (2)

Operation manual

Quantity

1 pc.

1 pc.

1 pc.

Shape

Thin

Name

Installation manual

Fluorinated green-

house gases label

 Multilingual fluori-
nated greenhouse 

gases label

Quantity

1 pc.

1 pc.

1 pc.

Shape

Name

Outdoor unit

Indoor unit

Unit cooler

Showcase

Shape

Name

Indoor unit

Control panel 

(Defrost)

Warning 

panel

Unit cooler

Showcase

Shape

1, 2, 3

1, 2, 3

4

4

LREQ5, LREQ6

LREQ8, LREQ10, LREQ12

1, 2, 3

4

LREQ15, LREQ20

4PWEN74302-1D.book  Page 3  Thursday, April 27, 2017  9:01 PM

Summary of Contents for LREQ-BY1

Page 1: ...INSTALLATION MANUAL LREQ5B7Y1 LREQ6B7Y1 LREQ8B7Y1 LREQ10B7Y1 LREQ12B7Y1 LREQ15B7Y1 LREQ20B7Y1 Air cooled refrigeration condensing unit 4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Page 2: ...det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bed mmelse av E Anvendt modul F G Risikokategori H Se ogs neste side 13 jotka on esitetty asiakirjassa A ja jotka B on hyv ksynyt...

Page 3: ...peratuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimalus leistinas sl gis PS K...

Page 4: ...lectric shocks or fire When installing the unit in a small room take measures so that the refrigerant may not exceed the limiting concentration in the event of refrigerant leakage Contact your dealer...

Page 5: ...connected indoor unit to know the climate class EN60335 2 89 EMC CHARACTERISTICS This system is a class A product In a domestic environment this product may cause radio interference in which case the...

Page 6: ...d on the size specified by the solenoid valve and mechanical thermostatic expansion valve being used Route the path to the indoor unit heat exchanger so that the flow of refrigerant is from top to bot...

Page 7: ...l height on the suction side no higher than 500 mm Wall height for sides no limit If the height is exceeded the above calculate h1 and h2 shown in the figure below and add h1 2 to the service space of...

Page 8: ...be attached attach it to the whole face of the base The height of the base should be at least 150 mm from the floor Secure the unit to its base using foundation bolts Use four commercially available M...

Page 9: ...adverse influence of residual substances such as the oxidation of refrigerant oil and the generation of scale is considered If the indoor unit or outdoor unit is disconnected from the piping for a lo...

Page 10: ...is required at 5 m intervals from outdoor unit d1 e B d2 C c D1 F E f D2 A b a Outdoor unit Showcase Unit cooler Gas piping Liquid piping H Refrigerant piping size Unit mm Outdoor unit side Piping siz...

Page 11: ...yer 6 5 Connecting the refrigerant piping CAUTION In addition to gas and liquid shutoff valves this unit has a maintenance shutoff valve see diagram below Do not operate the maintenance shutoff valve...

Page 12: ...proceed with connection of the field piping 1 Service port 2 Stop valve 3 Point of pipe cutting just above brazing point or above marking A Pinched piping B Pinched piping CAUTION Precautions when con...

Page 13: ...the screw thread Do not apply a screw lock agent for flare nut use to the sealing part Be sure to tighten the cap securely after the work Refer to Operation Method of Shutoff Valves on page 9 for the...

Page 14: ...effect but also may cause capacitor abnormal heating accident due to high frequency waves Only proceed with wiring work after blocking off all power Always ground wires in accordance with relevant lo...

Page 15: ...aker 14 Earth leakage circuit breaker 15 Panel 16 Run input 17 Earth 18 OFF Normal mode ON Low noise mode Note Use conduit for power supply wiring Make sure the weak electric wiring i e for the remote...

Page 16: ...provided that the system impedance Zsys is less than or equal to Zmax and EN IEC61000 3 12 2 provided that the short circuit power Ssc is greater than or equal to the minimum Ssc value at the interfac...

Page 17: ...arth wire may not contact sufficiently and the earthing effect of the wire may be lost Do not finish strand wire with solder 7 4 Procedure for wiring inside units Referring to the following figure sec...

Page 18: ...s no decrease in the pressure over a period of 24 hours If there is a decrease in the pressure check for and repair leaks Vacuum drying Operate the vacuum pump for more than three hours from the servi...

Page 19: ...7 2 Make sure insulation work is done See 8 2 Thermal insulation work on page 15 3 Make sure there is no faulty refrigerant piping See 6 REFRIGERANT PIPING on page 6 9 CHECKS AFTER WORK COMPLETION Mak...

Page 20: ...peration switch of the outdoor unit after the speci fied amount of refrigerant is replenished To prevent liquid compression e Caution Fully open the shutoff valves on the gas and liquid sides promptly...

Page 21: ...ion code items can be displayed on the condensing unit 1 Make sure that the LED H1P is off If the LED is on press the MODE button BS1 once 2 Press the MODE button BS1 once The LED H1P starts blinking...

Page 22: ...3 7 10 Calculate the amount of all refrigerant in this system 8 Table 1 Capacity and amount of refrigerant of the indoor unit Show case and Blower coil Note 1 Case of showcase the condition of capaci...

Page 23: ...4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Page 24: ...4PW74302 1D 2016 11 Copyright 2012 Daikin 4PW74302 1 D 0000000L 4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Reviews: