background image

Installation manual

17

LREQ5~20B7Y1

Air cooled refrigeration condensing unit

4PW74302-1D – 2016.11

[The evaporation temperature setting]

Refer to the following table for the evaporation temperature.

• The evaporation temperature is set up by dip switches (DS1).

WARNING

• Use protective gear (e.g., protective gloves and glasses) at the 

time of refrigerant filling.

• Pay attention to the rotation of the fan whenever the front panel is 

opened while working.

 

The fan can rotate continuously for a while after the outdoor unit 
stops operating.

• Make sure there is no oxygen in the system. Refrigerant may only 

be charged after performing the leak test and the vacuum drying.

[Refrigerant replenishment work]

CAUTION

• Refer to the 

"Operation Method of Shutoff Valves" on page 9

 for the 

control method of the shutoff valves.

• Never replenish liquid refrigerant directly from a gas line. Liquid 

compression may cause the compressor to fail.

• When the refrigerant charging procedure is done or when pausing, 

close the valve of the refrigerant tank immediately. If the valve is 
not closed immediately, remaining pressure might charge 
additional refrigerant. 

Possible consequence:

 Incorrect 

refrigerant amount.

1. The refrigerant must be noted for this product. Calculate the amount 

of refrigerant replenishment according to the label for the calcula-
tion of the amount of refrigerant replenishment or according to the 

"12. ADDITIONAL REFRIGERANT AMOUNT" on page 19

.

 

In case re-charge is required, refer to the nameplate of the unit. It 
states the type of refrigerant and necessary amount.

(5) Take the following procedure for refrigerant replenishment.

 

Refer to 

"8-1 Airtight test/vacuum drying" on page 15

 for the 

connection of the refrigerant cylinder.

(6) Turn on the indoor unit and control panel.

 

Do not turn on the outdoor unit.

(7) Replenish refrigerant from the service port of the shutoff valve on 

the liquid side.

(8) If the calculated amount of refrigerant cannot be filled, take the 

following steps to operate the system and continue refrigerant 
replenishment.
a. Open the gas shutoff valve all the way and adjust the opening of 

the liquid shutoff valve (*1).

b.

[Warning/electric shock warning]

 

Turn on the outdoor unit.

c.

[Warning/electric shock warning]

 

Turn on the operation switch of the outdoor unit and replenish 
refrigerant while the outdoor unit is in operation.

d.Turn off the operation switch of the outdoor unit after the speci-

fied amount of refrigerant is replenished. (To prevent liquid 
compression)

e.

[Caution]

 

 

Fully open the shutoff valves on the gas and liquid sides 
promptly. Otherwise, a piping explosion may result from liquid 
sealing.

*1The cylinder’s internal pressure will drop when there is little 

refrigerant remaining in the cylinder, making it impossible to charge 
the unit, even if the liquid shutoff valve opening is adjusted. In this 
situation, replace the cylinder with one that has more refrigerant 
remaining.

 

Additionally, if the piping length is long, replenishing while the liquid 
shutoff valve is fully closed may lead to activation of the protection 
system, causing the unit to stop operation.

1. After the work is completed, apply a screw lock agent (for flare nuts) 

to the screws of the shutoff valves and service ports. Refer to the 

"Handling precautions for valve cover" on page 10

 and 

"Handling 

Precautions for Service Port" on page 10

 in 

"6-5 Connecting the 

refrigerant piping" on page 8

 for the handling of the valve covers 

and service ports.

(9) After the refrigerant replenishment is completed, fill out the item 

“total amount of refrigerant replenishment” on the label of 
instructions on refrigerant replenishment of the outdoor unit with 
the actual amount of refrigerant replenishment.

 

Refer to the illustration of the label pasting position for instructions 
on refrigerant replenishment (see the illustration on the above).

[Precautions for refrigerant cylinder]

At the time of refrigerant filling, check whether the siphon tube is 
provided. Then locate the cylinder so that the refrigerant will be filled in 
the state of liquid (see table below).
R410A is a mixed refrigerant, the composition of which may change 
and the normal operation of the system may not be possible if the 
refrigerant is filled in the state of gas.

+10°C

    the position 
of switches

–10°C

–15°C

–20°C

DS1

–5°C

(Factory Set)

0°C

–35°C

The evaporation 
temperature setting

–25°C

+5°C

–45°C

–30°C

–40°C

DS1

DS1

ON

OFF

( )

4

2

1

3

2

4

1

3

1

3

2

4

Cylinder provided with siphon tube.

Other cylinders

Label of instructions on 
refrigerant replenishment

Label pasting position

Control box

Stand the cylinder upright and fill the refrigerant.
(There is a siphon tube inside, which makes it 
possible to replenish the refrigerant in the state of 
liquid without setting the cylinder upside down.)

Stand the cylinder upside down and fill the 
refrigerant.
(Pay attention so that the cylinder 
will not topple down.)

4PWEN74302-1D.book  Page 17  Thursday, April 27, 2017  9:01 PM

Summary of Contents for LREQ-BY1

Page 1: ...INSTALLATION MANUAL LREQ5B7Y1 LREQ6B7Y1 LREQ8B7Y1 LREQ10B7Y1 LREQ12B7Y1 LREQ15B7Y1 LREQ20B7Y1 Air cooled refrigeration condensing unit 4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Page 2: ...det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bed mmelse av E Anvendt modul F G Risikokategori H Se ogs neste side 13 jotka on esitetty asiakirjassa A ja jotka B on hyv ksynyt...

Page 3: ...peratuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimalus leistinas sl gis PS K...

Page 4: ...lectric shocks or fire When installing the unit in a small room take measures so that the refrigerant may not exceed the limiting concentration in the event of refrigerant leakage Contact your dealer...

Page 5: ...connected indoor unit to know the climate class EN60335 2 89 EMC CHARACTERISTICS This system is a class A product In a domestic environment this product may cause radio interference in which case the...

Page 6: ...d on the size specified by the solenoid valve and mechanical thermostatic expansion valve being used Route the path to the indoor unit heat exchanger so that the flow of refrigerant is from top to bot...

Page 7: ...l height on the suction side no higher than 500 mm Wall height for sides no limit If the height is exceeded the above calculate h1 and h2 shown in the figure below and add h1 2 to the service space of...

Page 8: ...be attached attach it to the whole face of the base The height of the base should be at least 150 mm from the floor Secure the unit to its base using foundation bolts Use four commercially available M...

Page 9: ...adverse influence of residual substances such as the oxidation of refrigerant oil and the generation of scale is considered If the indoor unit or outdoor unit is disconnected from the piping for a lo...

Page 10: ...is required at 5 m intervals from outdoor unit d1 e B d2 C c D1 F E f D2 A b a Outdoor unit Showcase Unit cooler Gas piping Liquid piping H Refrigerant piping size Unit mm Outdoor unit side Piping siz...

Page 11: ...yer 6 5 Connecting the refrigerant piping CAUTION In addition to gas and liquid shutoff valves this unit has a maintenance shutoff valve see diagram below Do not operate the maintenance shutoff valve...

Page 12: ...proceed with connection of the field piping 1 Service port 2 Stop valve 3 Point of pipe cutting just above brazing point or above marking A Pinched piping B Pinched piping CAUTION Precautions when con...

Page 13: ...the screw thread Do not apply a screw lock agent for flare nut use to the sealing part Be sure to tighten the cap securely after the work Refer to Operation Method of Shutoff Valves on page 9 for the...

Page 14: ...effect but also may cause capacitor abnormal heating accident due to high frequency waves Only proceed with wiring work after blocking off all power Always ground wires in accordance with relevant lo...

Page 15: ...aker 14 Earth leakage circuit breaker 15 Panel 16 Run input 17 Earth 18 OFF Normal mode ON Low noise mode Note Use conduit for power supply wiring Make sure the weak electric wiring i e for the remote...

Page 16: ...provided that the system impedance Zsys is less than or equal to Zmax and EN IEC61000 3 12 2 provided that the short circuit power Ssc is greater than or equal to the minimum Ssc value at the interfac...

Page 17: ...arth wire may not contact sufficiently and the earthing effect of the wire may be lost Do not finish strand wire with solder 7 4 Procedure for wiring inside units Referring to the following figure sec...

Page 18: ...s no decrease in the pressure over a period of 24 hours If there is a decrease in the pressure check for and repair leaks Vacuum drying Operate the vacuum pump for more than three hours from the servi...

Page 19: ...7 2 Make sure insulation work is done See 8 2 Thermal insulation work on page 15 3 Make sure there is no faulty refrigerant piping See 6 REFRIGERANT PIPING on page 6 9 CHECKS AFTER WORK COMPLETION Mak...

Page 20: ...peration switch of the outdoor unit after the speci fied amount of refrigerant is replenished To prevent liquid compression e Caution Fully open the shutoff valves on the gas and liquid sides promptly...

Page 21: ...ion code items can be displayed on the condensing unit 1 Make sure that the LED H1P is off If the LED is on press the MODE button BS1 once 2 Press the MODE button BS1 once The LED H1P starts blinking...

Page 22: ...3 7 10 Calculate the amount of all refrigerant in this system 8 Table 1 Capacity and amount of refrigerant of the indoor unit Show case and Blower coil Note 1 Case of showcase the condition of capaci...

Page 23: ...4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Page 24: ...4PW74302 1D 2016 11 Copyright 2012 Daikin 4PW74302 1 D 0000000L 4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Reviews: