background image

Installation manual

19

LREQ5~20B7Y1

Air cooled refrigeration condensing unit

4PW74302-1D – 2016.11

12. ADDITIONAL REFRIGERANT AMOUNT

12-1 Calculation method

This product must fill the refrigerant in the field.

 

Calculate the amount of refrigerant replenishment according 
to the following points and note the amount of the refrigerant 
in the list shown below.

1

The amount of the refrigerant for the liquid piping is calculated 
from the liquid piping size and the piping length of the system.

 

(Calculate the refrigerant additional charging quantity by rounding 
off to the number in 0.1 kg.)

2

Total each piping size amount of the refrigerant.---(1)

3

The amount of the refrigerant for the indoor unit of the refrigeration 
is calculated from the capacity of the connected showcase as 
below table 1).

1. Total all the refrigeration showcase capacities.
2. Total all the freezer showcase capacities.
3. Total all the blower coil capacities.
4. Calculate the amount of the refrigerant by the total capacities 

and the table 1 below of each indoor unit.

4

Total each indoor unit amount of the refrigerant.---(2)

5

Add a constant amount depending on outdoor unit capacity class 
(see table 2).---(3)

6

Total the amount of the refrigerant of table below(1), (2), and (3).

 

---(4)

7

Check sealing conditions through the sight glass at the time of test 
run(see Figure 1).

 

If the sight glass has not been sealed yet (due to the shortage of 
refrigerant), charge additional refrigerant.---(5)

Note

The upper limit quantity of refrigerant adjustment at the time of 
the test run assumes 0.1 times of the quantity of refrigerant cal-
culated based on piping length(1), on indoor unit capacity(2) 
and outdoor unit capacity class (3).

 

(5)≤(4)×0.1

8

Calculate the total additional charging amount.---(6)

9

Determine the factory charge (see table 3).---(7)

10 Calculate the amount of all refrigerant in this system.---(8)

Table 1: Capacity and amount of refrigerant of the indoor unit (Show-

case and Blower coil)

Note

1.Case of showcase, the condition of capacity

(evaporating temperature).
Refrigeration:-10°C
Frozen:-35°C

2.Case of blower coil, the condition of capacity is 10°C (Td).

Table 2: Additional reftigerant amount based on outdoor unit 

 

capacity class

Figure 1

Table 3: Factory charge

Inch piping

Metric piping

Liquid 
pipe size

Refri-

 

gerant 
amount

Liquid 
pipe size

Refri-

 

gerant 
amount

Pipe 
length
(m)

Total 
amount 

 

of refri-
gerant
(kg)

Ø6.4

0.02

Ø6.0

0.018

(a)

Ø9.5

0.06

Ø10.0

0.066

(b)

Ø12.7

0.12

Ø12.0

0.097

(c)

Ø15.9

0.19

Ø16.0

0.19

(d)

(1) Subtotal [(a)+(b)+(c)+(d)]

Indoor unit

Total 

 

capacity 
(kW)

Amount of 

 

refrigerant 
(Refer to 
table 1)

Refrigeration showcase

(A)

Frozen showcase

(B)

Blower coil

(C)

(2) Subtotal [(A)+(B)+(C)]
(3) Constant amount based on outdoor unit

 

capacity class (table 2)

(4) Total of the amount of refrigerant 

 

replenishment [(1)+(2)+(3)]

(5) Amount of refrigerant replenishment at the time 

of test run.

(6) Total additional charging amount [(4)+(5)]
(7) Factory charge (table 3)
(8) Total amount of refrigerant [(6)+(7)]

Total capacity of showcase or 
blower coil
 (*Note.)

Amount of refrigerant (kg)

Showcase

Blower coil

Refrigeration

Frozen

Less than 5kW

1.1

1.4

0.6

From 5kW to less than 10kW

2.3

3.2

1.2

From 10kW to less than 15kW

3.4

5.2

1.7

From 15kW to less than 20kW

4.6

2.3

From 20kW to less than 25kW

5.9

3.0

From 25kW to less than 30kW

7.0

3.5

From 30kW to less than 35kW

8.2

4.1

From 35kW to less than 40kW

9.7

4.9

40kW or more

11.0

5.5

Outdoor unit

Amount of refrigerant (kg)

LREQ(5/6)B7Y1

1.0

LREQ(8/10/12)B7Y1

3.0

LREQ(15/20)B7Y1

3.5

Outdoor unit

Factory charge (kg)

LREQ(5/6)B7Y1

5.2

LREQ(8/10/12)B7Y1

7.9

LREQ(15/20)B7Y1

11.5

Outdoor unit

Blower coil

Booster unit

Refrigeration 
showcase

Frozen 
showcase

Full of 
liquid

Bubbles come 
out at all times.

A few 
bubbles 
flow.

Sealed state (    )

Shortage of refrigerant (    )

4PWEN74302-1D.book  Page 19  Thursday, April 27, 2017  9:01 PM

Summary of Contents for LREQ-BY1

Page 1: ...INSTALLATION MANUAL LREQ5B7Y1 LREQ6B7Y1 LREQ8B7Y1 LREQ10B7Y1 LREQ12B7Y1 LREQ15B7Y1 LREQ20B7Y1 Air cooled refrigeration condensing unit 4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Page 2: ...det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bed mmelse av E Anvendt modul F G Risikokategori H Se ogs neste side 13 jotka on esitetty asiakirjassa A ja jotka B on hyv ksynyt...

Page 3: ...peratuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimalus leistinas sl gis PS K...

Page 4: ...lectric shocks or fire When installing the unit in a small room take measures so that the refrigerant may not exceed the limiting concentration in the event of refrigerant leakage Contact your dealer...

Page 5: ...connected indoor unit to know the climate class EN60335 2 89 EMC CHARACTERISTICS This system is a class A product In a domestic environment this product may cause radio interference in which case the...

Page 6: ...d on the size specified by the solenoid valve and mechanical thermostatic expansion valve being used Route the path to the indoor unit heat exchanger so that the flow of refrigerant is from top to bot...

Page 7: ...l height on the suction side no higher than 500 mm Wall height for sides no limit If the height is exceeded the above calculate h1 and h2 shown in the figure below and add h1 2 to the service space of...

Page 8: ...be attached attach it to the whole face of the base The height of the base should be at least 150 mm from the floor Secure the unit to its base using foundation bolts Use four commercially available M...

Page 9: ...adverse influence of residual substances such as the oxidation of refrigerant oil and the generation of scale is considered If the indoor unit or outdoor unit is disconnected from the piping for a lo...

Page 10: ...is required at 5 m intervals from outdoor unit d1 e B d2 C c D1 F E f D2 A b a Outdoor unit Showcase Unit cooler Gas piping Liquid piping H Refrigerant piping size Unit mm Outdoor unit side Piping siz...

Page 11: ...yer 6 5 Connecting the refrigerant piping CAUTION In addition to gas and liquid shutoff valves this unit has a maintenance shutoff valve see diagram below Do not operate the maintenance shutoff valve...

Page 12: ...proceed with connection of the field piping 1 Service port 2 Stop valve 3 Point of pipe cutting just above brazing point or above marking A Pinched piping B Pinched piping CAUTION Precautions when con...

Page 13: ...the screw thread Do not apply a screw lock agent for flare nut use to the sealing part Be sure to tighten the cap securely after the work Refer to Operation Method of Shutoff Valves on page 9 for the...

Page 14: ...effect but also may cause capacitor abnormal heating accident due to high frequency waves Only proceed with wiring work after blocking off all power Always ground wires in accordance with relevant lo...

Page 15: ...aker 14 Earth leakage circuit breaker 15 Panel 16 Run input 17 Earth 18 OFF Normal mode ON Low noise mode Note Use conduit for power supply wiring Make sure the weak electric wiring i e for the remote...

Page 16: ...provided that the system impedance Zsys is less than or equal to Zmax and EN IEC61000 3 12 2 provided that the short circuit power Ssc is greater than or equal to the minimum Ssc value at the interfac...

Page 17: ...arth wire may not contact sufficiently and the earthing effect of the wire may be lost Do not finish strand wire with solder 7 4 Procedure for wiring inside units Referring to the following figure sec...

Page 18: ...s no decrease in the pressure over a period of 24 hours If there is a decrease in the pressure check for and repair leaks Vacuum drying Operate the vacuum pump for more than three hours from the servi...

Page 19: ...7 2 Make sure insulation work is done See 8 2 Thermal insulation work on page 15 3 Make sure there is no faulty refrigerant piping See 6 REFRIGERANT PIPING on page 6 9 CHECKS AFTER WORK COMPLETION Mak...

Page 20: ...peration switch of the outdoor unit after the speci fied amount of refrigerant is replenished To prevent liquid compression e Caution Fully open the shutoff valves on the gas and liquid sides promptly...

Page 21: ...ion code items can be displayed on the condensing unit 1 Make sure that the LED H1P is off If the LED is on press the MODE button BS1 once 2 Press the MODE button BS1 once The LED H1P starts blinking...

Page 22: ...3 7 10 Calculate the amount of all refrigerant in this system 8 Table 1 Capacity and amount of refrigerant of the indoor unit Show case and Blower coil Note 1 Case of showcase the condition of capaci...

Page 23: ...4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Page 24: ...4PW74302 1D 2016 11 Copyright 2012 Daikin 4PW74302 1 D 0000000L 4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Reviews: