LREQ5~20B7Y1

Air cooled refrigeration condensing unit

4PW74302-1D – 2016.11

Installation manual

10

Tightening torque

Check with the following table the sizes of shutoff valves incorporated 
by each model and the tightening torque values of the respective 
shutoff valves.
Shutoff valve sizes

Opening method

1. Remove the valve cover and turn the shaft anticlockwise with a 

hexagon wrench.

(1) Turn the shaft until the shaft stops.
(2) Tighten the valve cover securely. Refer to the above table for the 

tightening torque according to the size.

Closing method

1. Remove the valve cover and turn the shaft clockwise with a hexa-

gon wrench.

(3) Tighten the shaft until the shaft comes in contact with the sealing 

part of the valve.

(4) Tighten the valve cover securely. Refer to the above table for the 

tightening torque according to the size.

Handling precautions for valve cover

• Be careful not to damage the sealing part.
• At the time of mounting the valve cover, apply a screw lock agent to 

the screw thread.

• Do not apply a screw lock agent (for flare nut use) to the sealing 

part.

• Be sure to tighten the valve cover securely after operating the 

valve. Refer t

"Operation Method of Shutoff Valves" on page 9

 for 

the tightening torque of the valve.

Handling Precautions for Service Port

• Work on the service port with a charge hose provided with a 

pushing rod.

• At the time of mounting the cap, apply a screw lock agent to the 

screw thread.

• Do not apply a screw lock agent (for flare nut use) to the sealing 

part.

• Be sure to tighten the cap securely after the work. Refer to 

"Operation Method of Shutoff Valves" on page 9

 for the tightening 

torque of the cap.

CAUTION

Apply a screw lock agent to the valve cover mount and the screw 
thread of the service port.

 

Otherwise, dew condensation water will intrude inside and freeze. 
Therefore, refrigerant gas leakage or a compressor malfunction may 
result from the cap deformation or damage.

3.

Connecting refrigerant piping to outdoor units

If connected to the front

Remove the shutoff valve cover to connect.

LREQ

5

6

8

10

12

15

20

Liquid side 
shutoff valve

Ø9.5

Ø12.7

Gas side 
shutoff valve

Ø19.1

Ø25.4

Ø31.8

Shutoff 

valve sizes

Tightening torque N•m (closes clockwise)

Shaft (valve body)

Valve cover Service port

Ø9.5

5.4~6.5

Hexagon 

wrench: 4mm

13.5~16.5

11.5~13.9

Ø12.7

8.1~9.9

18.0~22.0

Ø19.1

27.0~33.0

Hexagon 

wrench: 8 mm

22.5~27.5

Ø25.4

Ø31.8

26.5~29.4

Hexagon 

wrench: 10 mm

44.1~53.9

Service port

Valve cover

Hexagon hole

Shaft

Sealing part

Screw thread

Apply a screw lock agent

Sealing part

Not apply a screw lock agent

Shutoff valve 
Part of mounting the 
valve cover.

Valve cover

Sealing part
Not apply a screw 
lock agent

Screw thread
Apply a screw lock 
agent

Cap

Liquid side shutoff valve

Gas side shutoff valve

Gas side 
accessory pipe (1)

Brazing

Liquid side 
accessory pipe (1)

Brazing

LREQ5~12

Liquid side 
shutoff valve

Gas side 
shutoff valve

Gas side 
accessory pipe (1)

Brazing

Liquid side 
accessory pipe (1)

Brazing

LREQ15, LREQ20

4PWEN74302-1D.book  Page 10  Thursday, April 27, 2017  9:01 PM

Summary of Contents for LREQ-BY1

Page 1: ...INSTALLATION MANUAL LREQ5B7Y1 LREQ6B7Y1 LREQ8B7Y1 LREQ10B7Y1 LREQ12B7Y1 LREQ15B7Y1 LREQ20B7Y1 Air cooled refrigeration condensing unit 4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Page 2: ...det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bed mmelse av E Anvendt modul F G Risikokategori H Se ogs neste side 13 jotka on esitetty asiakirjassa A ja jotka B on hyv ksynyt...

Page 3: ...peratuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimalus leistinas sl gis PS K...

Page 4: ...lectric shocks or fire When installing the unit in a small room take measures so that the refrigerant may not exceed the limiting concentration in the event of refrigerant leakage Contact your dealer...

Page 5: ...connected indoor unit to know the climate class EN60335 2 89 EMC CHARACTERISTICS This system is a class A product In a domestic environment this product may cause radio interference in which case the...

Page 6: ...d on the size specified by the solenoid valve and mechanical thermostatic expansion valve being used Route the path to the indoor unit heat exchanger so that the flow of refrigerant is from top to bot...

Page 7: ...l height on the suction side no higher than 500 mm Wall height for sides no limit If the height is exceeded the above calculate h1 and h2 shown in the figure below and add h1 2 to the service space of...

Page 8: ...be attached attach it to the whole face of the base The height of the base should be at least 150 mm from the floor Secure the unit to its base using foundation bolts Use four commercially available M...

Page 9: ...adverse influence of residual substances such as the oxidation of refrigerant oil and the generation of scale is considered If the indoor unit or outdoor unit is disconnected from the piping for a lo...

Page 10: ...is required at 5 m intervals from outdoor unit d1 e B d2 C c D1 F E f D2 A b a Outdoor unit Showcase Unit cooler Gas piping Liquid piping H Refrigerant piping size Unit mm Outdoor unit side Piping siz...

Page 11: ...yer 6 5 Connecting the refrigerant piping CAUTION In addition to gas and liquid shutoff valves this unit has a maintenance shutoff valve see diagram below Do not operate the maintenance shutoff valve...

Page 12: ...proceed with connection of the field piping 1 Service port 2 Stop valve 3 Point of pipe cutting just above brazing point or above marking A Pinched piping B Pinched piping CAUTION Precautions when con...

Page 13: ...the screw thread Do not apply a screw lock agent for flare nut use to the sealing part Be sure to tighten the cap securely after the work Refer to Operation Method of Shutoff Valves on page 9 for the...

Page 14: ...effect but also may cause capacitor abnormal heating accident due to high frequency waves Only proceed with wiring work after blocking off all power Always ground wires in accordance with relevant lo...

Page 15: ...aker 14 Earth leakage circuit breaker 15 Panel 16 Run input 17 Earth 18 OFF Normal mode ON Low noise mode Note Use conduit for power supply wiring Make sure the weak electric wiring i e for the remote...

Page 16: ...provided that the system impedance Zsys is less than or equal to Zmax and EN IEC61000 3 12 2 provided that the short circuit power Ssc is greater than or equal to the minimum Ssc value at the interfac...

Page 17: ...arth wire may not contact sufficiently and the earthing effect of the wire may be lost Do not finish strand wire with solder 7 4 Procedure for wiring inside units Referring to the following figure sec...

Page 18: ...s no decrease in the pressure over a period of 24 hours If there is a decrease in the pressure check for and repair leaks Vacuum drying Operate the vacuum pump for more than three hours from the servi...

Page 19: ...7 2 Make sure insulation work is done See 8 2 Thermal insulation work on page 15 3 Make sure there is no faulty refrigerant piping See 6 REFRIGERANT PIPING on page 6 9 CHECKS AFTER WORK COMPLETION Mak...

Page 20: ...peration switch of the outdoor unit after the speci fied amount of refrigerant is replenished To prevent liquid compression e Caution Fully open the shutoff valves on the gas and liquid sides promptly...

Page 21: ...ion code items can be displayed on the condensing unit 1 Make sure that the LED H1P is off If the LED is on press the MODE button BS1 once 2 Press the MODE button BS1 once The LED H1P starts blinking...

Page 22: ...3 7 10 Calculate the amount of all refrigerant in this system 8 Table 1 Capacity and amount of refrigerant of the indoor unit Show case and Blower coil Note 1 Case of showcase the condition of capaci...

Page 23: ...4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Page 24: ...4PW74302 1D 2016 11 Copyright 2012 Daikin 4PW74302 1 D 0000000L 4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Reviews: