Installation manual

9

LREQ5~20B7Y1

Air cooled refrigeration condensing unit

4PW74302-1D – 2016.11

2.

Removing Pinch Piping

WARNING

Never remove the pinched piping by brazing.

 

Failure to observe the instructions in procedure below properly may 
result in property damage or personal injury, which may be serious 
depending on the circumstances.

CAUTION

Use the following procedure to remove the pinched piping:
1

Remove the valve lid and make sure that the stop 
valves are fully closed.

2

Connect a charge hose to service ports of all stop valves.

3

Recover gas and oil from the pinched piping by using a recovery 
unit. 

4

When all gas and oil is recovered from the pinched piping, 
disconnect the charge hose and close the service ports.

5

In case the pinched piping lower part looks like detail 

 in the 

figure below, follow instructions as per procedure steps 7+8.

 

In case the pinched piping lower part looks like detail 

 in the 

figure below, follow instructions as per procedure steps 6+7+8.

6

Cut off the lower part of the smaller pinched piping with an 
appropriate tool (e.g. a pipe cutter, a pair of nippers, ...) so 
that a cross-section is open, allowing remaining oil to drip 
out in case the recovery was not complete.

 

Wait until all oil is dripped out.

7

Cut the pinched piping off with a pipe cutter just above the brazing 
point or just above the marking in case there is no brazing point. 

8

Wait until all oil is dripped out in case the recovery was not 
complete, and only then proceed with connection of the field 
piping.

1 Service port
2 Stop valve
3 Point of pipe cutting just above brazing point or above marking
A Pinched piping 

B Pinched piping 

CAUTION

Precautions when connecting field piping.

• Perform brazing at the gas stop valve before brazing at the liquid 

stop valve.

• Add brazing material as shown in the figure.

CAUTION

• Be sure to use the supplied accessory pipes when carrying out 

piping work in the field.

• Be sure that the field installed piping does not touch other pipes, 

the bottom panel or side panel. Especially for the bottom and side 
connection, be sure to protect the piping with suitable insulation, to 
prevent it from coming into contact with the casing.

• Make sure the field piping and connections are not subjected to 

stress.

Operation Method of Shutoff Valves

Follow the instructions below when operating each shutoff valve.

CAUTION

• Do not open the shutoff valve until the steps specified in 

 

8-3 Checking of device and installation conditions

” is 

completed.

 

Do not leave the shutoff valve opened without turning the power 
on, otherwise refrigerant may be condensed in the compressor and 
the insulation of the main power supply circuit may be degraded.

• Be sure to use an exclusive tool to handle the shutoff valve. The 

shutoff valve is not of back sheet type. Excessive force imposed 
may break the valve.

• Use a charge hose when using the service port.
• Make sure that there is no refrigerant gas leakage after the valve 

cover and cap are securely tightened.

CAUTION

Do not vent gases into the atmosphere.

CAUTION

Never remove the pinched piping by brazing.

1

2

3

2

3

B

A

4PWEN74302-1D.book  Page 9  Thursday, April 27, 2017  9:01 PM

Summary of Contents for LREQ-BY1

Page 1: ...INSTALLATION MANUAL LREQ5B7Y1 LREQ6B7Y1 LREQ8B7Y1 LREQ10B7Y1 LREQ12B7Y1 LREQ15B7Y1 LREQ20B7Y1 Air cooled refrigeration condensing unit 4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Page 2: ...det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bed mmelse av E Anvendt modul F G Risikokategori H Se ogs neste side 13 jotka on esitetty asiakirjassa A ja jotka B on hyv ksynyt...

Page 3: ...peratuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimalus leistinas sl gis PS K...

Page 4: ...lectric shocks or fire When installing the unit in a small room take measures so that the refrigerant may not exceed the limiting concentration in the event of refrigerant leakage Contact your dealer...

Page 5: ...connected indoor unit to know the climate class EN60335 2 89 EMC CHARACTERISTICS This system is a class A product In a domestic environment this product may cause radio interference in which case the...

Page 6: ...d on the size specified by the solenoid valve and mechanical thermostatic expansion valve being used Route the path to the indoor unit heat exchanger so that the flow of refrigerant is from top to bot...

Page 7: ...l height on the suction side no higher than 500 mm Wall height for sides no limit If the height is exceeded the above calculate h1 and h2 shown in the figure below and add h1 2 to the service space of...

Page 8: ...be attached attach it to the whole face of the base The height of the base should be at least 150 mm from the floor Secure the unit to its base using foundation bolts Use four commercially available M...

Page 9: ...adverse influence of residual substances such as the oxidation of refrigerant oil and the generation of scale is considered If the indoor unit or outdoor unit is disconnected from the piping for a lo...

Page 10: ...is required at 5 m intervals from outdoor unit d1 e B d2 C c D1 F E f D2 A b a Outdoor unit Showcase Unit cooler Gas piping Liquid piping H Refrigerant piping size Unit mm Outdoor unit side Piping siz...

Page 11: ...yer 6 5 Connecting the refrigerant piping CAUTION In addition to gas and liquid shutoff valves this unit has a maintenance shutoff valve see diagram below Do not operate the maintenance shutoff valve...

Page 12: ...proceed with connection of the field piping 1 Service port 2 Stop valve 3 Point of pipe cutting just above brazing point or above marking A Pinched piping B Pinched piping CAUTION Precautions when con...

Page 13: ...the screw thread Do not apply a screw lock agent for flare nut use to the sealing part Be sure to tighten the cap securely after the work Refer to Operation Method of Shutoff Valves on page 9 for the...

Page 14: ...effect but also may cause capacitor abnormal heating accident due to high frequency waves Only proceed with wiring work after blocking off all power Always ground wires in accordance with relevant lo...

Page 15: ...aker 14 Earth leakage circuit breaker 15 Panel 16 Run input 17 Earth 18 OFF Normal mode ON Low noise mode Note Use conduit for power supply wiring Make sure the weak electric wiring i e for the remote...

Page 16: ...provided that the system impedance Zsys is less than or equal to Zmax and EN IEC61000 3 12 2 provided that the short circuit power Ssc is greater than or equal to the minimum Ssc value at the interfac...

Page 17: ...arth wire may not contact sufficiently and the earthing effect of the wire may be lost Do not finish strand wire with solder 7 4 Procedure for wiring inside units Referring to the following figure sec...

Page 18: ...s no decrease in the pressure over a period of 24 hours If there is a decrease in the pressure check for and repair leaks Vacuum drying Operate the vacuum pump for more than three hours from the servi...

Page 19: ...7 2 Make sure insulation work is done See 8 2 Thermal insulation work on page 15 3 Make sure there is no faulty refrigerant piping See 6 REFRIGERANT PIPING on page 6 9 CHECKS AFTER WORK COMPLETION Mak...

Page 20: ...peration switch of the outdoor unit after the speci fied amount of refrigerant is replenished To prevent liquid compression e Caution Fully open the shutoff valves on the gas and liquid sides promptly...

Page 21: ...ion code items can be displayed on the condensing unit 1 Make sure that the LED H1P is off If the LED is on press the MODE button BS1 once 2 Press the MODE button BS1 once The LED H1P starts blinking...

Page 22: ...3 7 10 Calculate the amount of all refrigerant in this system 8 Table 1 Capacity and amount of refrigerant of the indoor unit Show case and Blower coil Note 1 Case of showcase the condition of capaci...

Page 23: ...4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Page 24: ...4PW74302 1D 2016 11 Copyright 2012 Daikin 4PW74302 1 D 0000000L 4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Reviews: