background image

LREQ5~20B7Y1

Air cooled refrigeration condensing unit

4PW74302-1D – 2016.11

Installation manual

12

• If not factory installed, a main switch or other means for 

disconnection, having a contact separation in all poles providing 
full disconnection under overvoltage category III condition, shall be 
installed in the fixed wiring.

• Electrical wiring must be done in accordance with the wiring 

diagrams and the description herein.

• Do not operate until refrigerant piping work is completed.

 

(If operated before complete the piping work, the compressor may 
be broken down.)

• Never remove thermistor, sensor or etc. when connecting power 

wiring and transmission wiring.

 

(If operated with thermistor, sensor or etc. removed, the 
compressor may be broken down.)

• This product have reversed phase protection detector that only 

works when the power is turned on. If there exists black out or the 
power goes on and off which the product is operating, attach a 
reversed phase protection circuit. Running the product in reversed 
phase may break the compressor and other parts.

• Attach the power wire securely. Introducing power with a missing 

N-phase or with a mistaken N-phase will break the unit.

• Never connect the power supply in reversed phase. 

 

The unit can not operate normally in reversed phase.

 

If you connect in reversed phase, replace two of the three phases.

• Make sure the electrical unbalance ratio is no greater than 2%. If it 

is larger than this, the unit’s lifespan will be reduced.

 

If the ratio exceeds 4%, the unit will shut down and an malfunction 
code will be displayed on the indoor remote controller.

• Connect the wire securely using designated wire and fix it with 

attached clamp without applying external pressure on the terminal 
parts (terminal for power wiring, terminal for transmission wiring 
and earth terminal).

• Install a switch that allows you to switch OFF all poles from the 

main power supply.

7-1 Example of wiring entire system 

1

3 phase 50 Hz 380~415 V

 

Earth leakage circuit breaker (high-frequency type) (for earth 
fault, overload, and short-circuit protection)

2

Outdoor units

3

Earth leakage circuit breaker (for earth fault, overload, and 
short-circuit protection)

4

Remote switch (See Note 1.)

5

High-voltage AC 220~240 V (See Note 2.)

 

Warning output

 

Caution output

 

Operation output

 

Run output

6

Caution input

7

Warning input

8

Alarm panel

9

Control board (field supply)

10

Timer

11

Indoor unit

12

Indoor unit

13

Earth leakage circuit breaker

14

Earth leakage circuit breaker

15

Panel

16

Run input

17

Earth

18

OFF: Normal mode

 

ON : Low noise mode

Note

• Use conduit for power supply wiring.
• Make sure the weak electric wiring (i.e. for the remote controller, 

between units, etc.) and the power wiring do not pass near each 
other, keeping them at least 50 mm apart.

 

Proximity may cause electrical interference, malfunctions, and 
breakage.

• Be sure to connect the power wiring to the power wiring terminal 

block and secure it as described in 

"7-2 Procedure for incoming 

wiring" on page 12

.

• Do not connect the power supply to the terminal block for the 

transmission wiring for warning, alarm, operation output, and 
remote operation switch. Otherwise the entire system will be 
damaged.

• Transmission wiring should be secured as described 

 

in  

"7-3 Procedure for power supply wiring" on page 13

.

• Secure wiring with clamp such as insulation lock ties to avoid 

contact with piping.

• Shape the wires to prevent the structure such as the control box lid 

deforming.  And close the cover firmly.

7-2 Procedure for incoming wiring

• Route high-voltage wiring (power supply wiring, earth wires, and 

warning/alarm/operation wiring) through wiring openings located 
on the side or front of the unit (knock holes) or on the bottom frame 
(knock holes).

• Route low-voltage wiring (for remote operating switches) through 

wiring openings (knock holes) located on the front of the unit or 
through wiring intakes.

Note

• Open the knock holes with a hammer or the like.
• After knocking out the holes, we recommend you remove any burrs 

and paint them using the repair paint to prevent rusting.

• When passing electrical wiring through the knock holes, protect the 

wiring with a conduit or bushings, making sure not to damage the 
wiring.

T1

Timer

Ry0, Ry1

Relay

K1M

Electromagnetic contactor (Defrosting heater)

E1H

Defrosting heater

S1T

Thermostat for inner temperature adjustment

S2T

Defrost completion thermostat

Y1S

Solenoid valve

H1P

Defrost lamp

1

17

15

16

13

11

14

12

4

18

3

9

10

5

2

8

6
7

Note: 1.  In case of used remote switch, use non-voltage contact for 

microcurrent (not more than 1mA, 12VDC).

Note: 2.  Total capacity for caution, warning : 0.5A or less at AC 220 to 240V.

Capacity for operation output run output : 0.5A or less at AC 220 to 240V.

K1M

Y1S

Ry0

X1M

L2

L1

L3 N

C

C1

X2M

W1

P1

P2

R

Y1S

RY0

RY1

K1M

RY0

2

1

X3M

Ry0

No

H1P

K1M

Ry0

Ry0

T1

S2T

A5P

T1

K1M

E1H

H1P

S1T

C

NC

B

S1T

X1M

A

Ry0

TeS1

S2T

Ry1

E1H

Through-hole cover

Cut the shaded area

Electric wiring label

(Rear side of control 
box lid)

Conduit

Piping outlet

High-voltage wiring

Low-voltage wiring

4PWEN74302-1D.book  Page 12  Thursday, April 27, 2017  9:01 PM

Summary of Contents for LREQ-BY1

Page 1: ...INSTALLATION MANUAL LREQ5B7Y1 LREQ6B7Y1 LREQ8B7Y1 LREQ10B7Y1 LREQ12B7Y1 LREQ15B7Y1 LREQ20B7Y1 Air cooled refrigeration condensing unit 4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Page 2: ...det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bed mmelse av E Anvendt modul F G Risikokategori H Se ogs neste side 13 jotka on esitetty asiakirjassa A ja jotka B on hyv ksynyt...

Page 3: ...peratuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimalus leistinas sl gis PS K...

Page 4: ...lectric shocks or fire When installing the unit in a small room take measures so that the refrigerant may not exceed the limiting concentration in the event of refrigerant leakage Contact your dealer...

Page 5: ...connected indoor unit to know the climate class EN60335 2 89 EMC CHARACTERISTICS This system is a class A product In a domestic environment this product may cause radio interference in which case the...

Page 6: ...d on the size specified by the solenoid valve and mechanical thermostatic expansion valve being used Route the path to the indoor unit heat exchanger so that the flow of refrigerant is from top to bot...

Page 7: ...l height on the suction side no higher than 500 mm Wall height for sides no limit If the height is exceeded the above calculate h1 and h2 shown in the figure below and add h1 2 to the service space of...

Page 8: ...be attached attach it to the whole face of the base The height of the base should be at least 150 mm from the floor Secure the unit to its base using foundation bolts Use four commercially available M...

Page 9: ...adverse influence of residual substances such as the oxidation of refrigerant oil and the generation of scale is considered If the indoor unit or outdoor unit is disconnected from the piping for a lo...

Page 10: ...is required at 5 m intervals from outdoor unit d1 e B d2 C c D1 F E f D2 A b a Outdoor unit Showcase Unit cooler Gas piping Liquid piping H Refrigerant piping size Unit mm Outdoor unit side Piping siz...

Page 11: ...yer 6 5 Connecting the refrigerant piping CAUTION In addition to gas and liquid shutoff valves this unit has a maintenance shutoff valve see diagram below Do not operate the maintenance shutoff valve...

Page 12: ...proceed with connection of the field piping 1 Service port 2 Stop valve 3 Point of pipe cutting just above brazing point or above marking A Pinched piping B Pinched piping CAUTION Precautions when con...

Page 13: ...the screw thread Do not apply a screw lock agent for flare nut use to the sealing part Be sure to tighten the cap securely after the work Refer to Operation Method of Shutoff Valves on page 9 for the...

Page 14: ...effect but also may cause capacitor abnormal heating accident due to high frequency waves Only proceed with wiring work after blocking off all power Always ground wires in accordance with relevant lo...

Page 15: ...aker 14 Earth leakage circuit breaker 15 Panel 16 Run input 17 Earth 18 OFF Normal mode ON Low noise mode Note Use conduit for power supply wiring Make sure the weak electric wiring i e for the remote...

Page 16: ...provided that the system impedance Zsys is less than or equal to Zmax and EN IEC61000 3 12 2 provided that the short circuit power Ssc is greater than or equal to the minimum Ssc value at the interfac...

Page 17: ...arth wire may not contact sufficiently and the earthing effect of the wire may be lost Do not finish strand wire with solder 7 4 Procedure for wiring inside units Referring to the following figure sec...

Page 18: ...s no decrease in the pressure over a period of 24 hours If there is a decrease in the pressure check for and repair leaks Vacuum drying Operate the vacuum pump for more than three hours from the servi...

Page 19: ...7 2 Make sure insulation work is done See 8 2 Thermal insulation work on page 15 3 Make sure there is no faulty refrigerant piping See 6 REFRIGERANT PIPING on page 6 9 CHECKS AFTER WORK COMPLETION Mak...

Page 20: ...peration switch of the outdoor unit after the speci fied amount of refrigerant is replenished To prevent liquid compression e Caution Fully open the shutoff valves on the gas and liquid sides promptly...

Page 21: ...ion code items can be displayed on the condensing unit 1 Make sure that the LED H1P is off If the LED is on press the MODE button BS1 once 2 Press the MODE button BS1 once The LED H1P starts blinking...

Page 22: ...3 7 10 Calculate the amount of all refrigerant in this system 8 Table 1 Capacity and amount of refrigerant of the indoor unit Show case and Blower coil Note 1 Case of showcase the condition of capaci...

Page 23: ...4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Page 24: ...4PW74302 1D 2016 11 Copyright 2012 Daikin 4PW74302 1 D 0000000L 4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Reviews: