Installation manual

11

LREQ5~20B7Y1

Air cooled refrigeration condensing unit

4PW74302-1D – 2016.11

When connected at lateral side (bottom)

Remove the knock hole on the bottom frame and route the piping 
under the bottom frame.

CAUTION

• Check that the on-site piping does not come in contact with other 

piping, the bottom frame, or side plate of the product.

Precautions for Piping

Perform piping branching with the following conditions kept in mind.

• At the time of branching the liquid piping, use a T-joint or Y-joint 

and branch it horizontally. This will prevent an uneven flow of 
refrigerant.

• At the time of branching gas piping, use a T-joint and branch it so 

that the branched piping will be located above the main piping (see 
the illustration below). This will prevent the stay of refrigerant oil in 
the indoor unit not in operation.

• Use a Y-joint for the liquid refrigerant branch and have the piping 

branch horizontally.

• Use a T-joint for the gas refrigerant branch and connect from the 

top of the main piping.

• Make sure that the horizontal portion of the gas piping slants 

downward to the outdoor unit (see the illustration above).

• If the outdoor unit is located above, make a trap on the gas pipe at 

5 m intervals from outdoor unit. This will ensure the smooth 
returning of oil in the piping slanting upward.

7. FIELD WIRING

To electric engineering contractors

• Be sure to install an earth leakage breaker. The product 

incorporates inverter equipment. In order to prevent the 
malfunctioning of the earth leakage breaker, make sure that the 
earth leakage breaker withstands harmonic interference.

• Do not operate the condensing unit until refrigerant piping work is 

completed, or otherwise the compressor will malfunction.

• Do not remove any electrical components such as thermistors or 

sensors when connecting power supply wires or transmission 
wires. The compressor may malfunction if the condensing unit is 
operated with such electrical components removed. 

CAUTION

• All field wiring and components must be installed by a licensed 

electrician and must comply with relevant local and national 
regulations.

• Be sure to use a dedicated power circuit. Never use a power supply 

shared by another appliance.

• Never install a phase advancing capacitor. As this unit is equipped 

with an inverter, installing a phase advancing capacitor will not only 
deteriorate power factor improvement effect, but also may cause 
capacitor abnormal heating accident due to high-frequency waves.

• Only proceed with wiring work after blocking off all power.
• Always ground wires in accordance with relevant local and national 

regulations.

• This machine includes an inverter device. Connect earth and leave 

charge to eliminate the impact on other devices by reducing noise 
generated from the inverter device and to prevent leaked current 
from being charged in the outer hull of the product.

• Do not connect the ground wire to gas pipes, sewage pipes, 

lightning rods, or telephone ground wires.

 

Gas pipes:

 can explode or catch fire if there is a gas leak.

 

Sewage pipes:

 no grounding effect is possible if hard plastic 

piping is used.

 

Telephone ground wires and lightning rods:

 dangerous when 

struck by lightning due to abnormal rise in electrical potential in the 
grounding.

• Be sure to install an earth leakage circuit breaker.

 

This unit uses an inverter, so install the earth leakage circuit 
breaker that be capable of handling high harmonics in order to 
prevent malfunctioning of the earth leakage circuit breaker itself.

• Earth leakage circuit breaker which are especially for protecting 

ground-faults should be used in conjunction with main switch or 
fuse for use with wiring.

• Disconnect the power supply for more than 1 minute, and measure 

the voltage at the terminals of main circuit capacitors or electrical 
components before servicing. The voltage must be less than 
50 V DC before you can touch electrical components. For the 
location of the terminals, see the wiring diagram.

• Do not touch electrical components with wet hands.
• Do not leave the unit unattended when the service cover is 

removed.

Liquid side shutoff valve

Gas side shutoff valve

Gas side 
accessory pipe (1)

Gas side 
accessory pipe (2)

Brazing

Brazing

Liquid side 
(field supply)

Gas side 
(field supply)

Liquid side 
accessory pipe (1)

Liquid side 
accessory pipe (2)

Knockout hole

Brazing

Brazing

Punch the knock hole.

LREQ5~12

Liquid side 
shutoff valve

Gas side 
shutoff valve

Gas side 
accessory pipe (2)

Gas side 
accessory pipe (1)

Brazing

Brazing

Liquid side 
(field supply)

Gas side 
(field supply)

Liquid side 
accessory pipe (2)

Liquid side 
accessory pipe (1)

Knockout hole

Punch the knock hole.

Brazing

Brazing

LREQ15, LREQ20

Horizontal 
surface

±30° or less

A-arrow view

A

Y-joint

T-joint

Main piping

Indoor unit side

Outdoor unit side

Branch piping

Make the piping 
slant downward

Branch piping

Make the piping 
slant downward

Main piping
Make the piping 
slant downward

T-joint

4PWEN74302-1D.book  Page 11  Thursday, April 27, 2017  9:01 PM

Summary of Contents for LREQ-BY1

Page 1: ...INSTALLATION MANUAL LREQ5B7Y1 LREQ6B7Y1 LREQ8B7Y1 LREQ10B7Y1 LREQ12B7Y1 LREQ15B7Y1 LREQ20B7Y1 Air cooled refrigeration condensing unit 4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Page 2: ...det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bed mmelse av E Anvendt modul F G Risikokategori H Se ogs neste side 13 jotka on esitetty asiakirjassa A ja jotka B on hyv ksynyt...

Page 3: ...peratuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimalus leistinas sl gis PS K...

Page 4: ...lectric shocks or fire When installing the unit in a small room take measures so that the refrigerant may not exceed the limiting concentration in the event of refrigerant leakage Contact your dealer...

Page 5: ...connected indoor unit to know the climate class EN60335 2 89 EMC CHARACTERISTICS This system is a class A product In a domestic environment this product may cause radio interference in which case the...

Page 6: ...d on the size specified by the solenoid valve and mechanical thermostatic expansion valve being used Route the path to the indoor unit heat exchanger so that the flow of refrigerant is from top to bot...

Page 7: ...l height on the suction side no higher than 500 mm Wall height for sides no limit If the height is exceeded the above calculate h1 and h2 shown in the figure below and add h1 2 to the service space of...

Page 8: ...be attached attach it to the whole face of the base The height of the base should be at least 150 mm from the floor Secure the unit to its base using foundation bolts Use four commercially available M...

Page 9: ...adverse influence of residual substances such as the oxidation of refrigerant oil and the generation of scale is considered If the indoor unit or outdoor unit is disconnected from the piping for a lo...

Page 10: ...is required at 5 m intervals from outdoor unit d1 e B d2 C c D1 F E f D2 A b a Outdoor unit Showcase Unit cooler Gas piping Liquid piping H Refrigerant piping size Unit mm Outdoor unit side Piping siz...

Page 11: ...yer 6 5 Connecting the refrigerant piping CAUTION In addition to gas and liquid shutoff valves this unit has a maintenance shutoff valve see diagram below Do not operate the maintenance shutoff valve...

Page 12: ...proceed with connection of the field piping 1 Service port 2 Stop valve 3 Point of pipe cutting just above brazing point or above marking A Pinched piping B Pinched piping CAUTION Precautions when con...

Page 13: ...the screw thread Do not apply a screw lock agent for flare nut use to the sealing part Be sure to tighten the cap securely after the work Refer to Operation Method of Shutoff Valves on page 9 for the...

Page 14: ...effect but also may cause capacitor abnormal heating accident due to high frequency waves Only proceed with wiring work after blocking off all power Always ground wires in accordance with relevant lo...

Page 15: ...aker 14 Earth leakage circuit breaker 15 Panel 16 Run input 17 Earth 18 OFF Normal mode ON Low noise mode Note Use conduit for power supply wiring Make sure the weak electric wiring i e for the remote...

Page 16: ...provided that the system impedance Zsys is less than or equal to Zmax and EN IEC61000 3 12 2 provided that the short circuit power Ssc is greater than or equal to the minimum Ssc value at the interfac...

Page 17: ...arth wire may not contact sufficiently and the earthing effect of the wire may be lost Do not finish strand wire with solder 7 4 Procedure for wiring inside units Referring to the following figure sec...

Page 18: ...s no decrease in the pressure over a period of 24 hours If there is a decrease in the pressure check for and repair leaks Vacuum drying Operate the vacuum pump for more than three hours from the servi...

Page 19: ...7 2 Make sure insulation work is done See 8 2 Thermal insulation work on page 15 3 Make sure there is no faulty refrigerant piping See 6 REFRIGERANT PIPING on page 6 9 CHECKS AFTER WORK COMPLETION Mak...

Page 20: ...peration switch of the outdoor unit after the speci fied amount of refrigerant is replenished To prevent liquid compression e Caution Fully open the shutoff valves on the gas and liquid sides promptly...

Page 21: ...ion code items can be displayed on the condensing unit 1 Make sure that the LED H1P is off If the LED is on press the MODE button BS1 once 2 Press the MODE button BS1 once The LED H1P starts blinking...

Page 22: ...3 7 10 Calculate the amount of all refrigerant in this system 8 Table 1 Capacity and amount of refrigerant of the indoor unit Show case and Blower coil Note 1 Case of showcase the condition of capaci...

Page 23: ...4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Page 24: ...4PW74302 1D 2016 11 Copyright 2012 Daikin 4PW74302 1 D 0000000L 4PWEN74302 1D book Page 1 Thursday April 27 2017 9 01 PM...

Reviews: