5-2 Setting up the Timer Extension Function
Using this function, you can prevent failure to turn off the indoor unit by automatically stopping the
indoor unit after a certain period of time from the operation start.
If this function is enabled, the indoor units are stopped when Duration elapses from the time they
were started.
The following describes how to set this function up.
•
Once the iTM unit is turned off, all the Timer Extension Function setup will be OFF.
•
When the indoor unit encounters the communication error or maintenance has been started,
the counted Duration will be cleared.
NOTE
1. Touch the Timer Extension button on the Automatic Ctrl. tab of the Menu List screen and display
the Timer Extension screen (see page 52).
(1)
2. Select the time to wait to stop from the
Duration
combo box
(1)
. You can select a value between
30 to 180 minutes, in increments of 30 minutes.
3.
When finished, touch the OK button to save and close the screen.
4. The Timer Extension function can be enabled/disabled from the A/C tab displayed in the
Detailed Setup screen of the Standard screen, the Events screen of Schedule screen, and
Action Setup screen of the Interlocking Control screen.
For details, see the relevant page.