User’s Manual EM11A017
DCM601A71 intelligent Touch Manager
178
•
Setup Items for Condition Setup Screen
The setting items and range of values you can set in each tab are as indicated in the table below.
Setting location
Item
Setting details
P
ossib
le r
ange [
: Visib
le
, ×:
In
visib
le
, Betw
een ( ) :
Numer
ical r
ange]
Condition to detect
On/Off
Equipment
error
Analog upper/
lo
w
er limit
error
Oper
ation
mode
Analog v
alue condition
Single
Condition Setup Screen
Star
t/Stop /
Error tab
Required condition f
or Star
t/Stop / Error
Star
t/Error
×
×
Stop/Nor
mal
×
×
Oper
ation Mode
tab
Oper
ation Mode
Cool, Dr
y, A
uto(Cool)
×
×
×
×
Heat, A
uto(Heat)
×
×
×
×
Fa
n
×
×
×
×
Analog V
alue
tab
Analog V
alue1
Example:
Outdoor T
emp1
×
×
×
×
Inequality Sign Selection
>
×
×
×
×
<
×
×
×
×
Analog
V
alue2
Const V
alue
Temper
ature
Celsius
Example:
0.0°C
×
×
×
×
(–512.0~512.0) *1*2*4 Step:
0.1
Fahrenheit
Example:
32°F
×
×
×
×
(–890~954) *1*2*4 Step:
1
Gener
ic
Example:
0.00
×
×
×
×
(–9999.99~9999.99) *1*4 Step:
0.01
Mgmt.
P
oint
Example:
Room T
emp1
×
×
×
×
*3
Offset
Temper
ature
Celsius
Example:
0.0
×
×
×
×
(–512.0~512.0) *1*2*3 Step:
0.1
Fahrenheit
Example:
0
×
×
×
×
(–922~922) *1*2*3 Step:
1
Gener
ic
Example:
0.00
×
×
×
×
(–9999.99~9999.99) *1*3 Step:
0.01
Hysteresis
Temper
ature
Celsius
Example:
1.0
×
×
×
×
(0.0~512.0) *1*2 Step:
0.1
Fahrenheit
Example:
1
×
×
×
×
(0~922) *1*2 Step:
1
Gener
ic
Example:
1.00
×
×
×
×
(0.00~9999.99) *1 Step:
0.01
*1 Displa
yed in accordance with the analog type of the selected management point.
*2 Displa
yed in °C or °F depending on the unit selected in the System Settings
.
*3 Gr
ay
ed out when Const
V
alue is selected.
*4 Gr
ay
ed out when Mgmt.
P
oint is selected.