3. Thereafter, when the room temperature becomes lower than the “Se Relative Setup
Setpoint” by the recovery temperature, the indoor unit is stopped. However to avoid continual
ON/OFF (hunting) of the indoor unit, it is not stopped until after 30 minutes.
Setpoint
Time
During absence
During presence
During absence
Indoor unit is operated
in Cool mode at Cool setpoint.
Room
temperature
Room
temperature
Setup setpoint
Cool setpoint during
presence
Cool recovery
temperature (2°F to 10°F range)
Indoor unit is turned
on to keep the setup setpoint.
When the target is operating in Heat, Auto(Heat), or Dependent (Heat) mode
1. While the room temperature is higher than “Setpoint – Relative Setback Setpoint”, the indoor
unit is stopped.
2. Room temperature is continuously monitored, and when it becomes lower than the “Setpoint –
Relative Setback Setpoint”, the indoor unit is started again.
3. Thereafter, when the room temperature exceeds the “Setpoint – Relative Setback Setpoint” by
the recovery temperature, the indoor unit is stopped. However to avoid continual ON/OFF
(hunting) of the indoor unit, it is not stopped until after 30 minutes.
Setpoint
Setback setpoint
Heat setpoint during
presence
Heat recovery temperature
(2°F to 10°F range)
Indoor unit is operated in Hreat mode
at Hreat setpoint.
Indoor unit is turned on to
keep the setup setpoint.
Time
During absence
During presence
During absence
Room
temperature
Room
temperature
When the target is operating in Fan or Dry mode
The indoor unit operates normally while people are present.
When no one is in, the indoor unit is put into Setback Inactive status and subsequent start/stop is
not performed.