When
Representative suction temperature – Representative setpoint (Heat) > Thermal diff 1,
operation mode is changed from Heat to Cool
•
When
Representative setpoint (Cool) – Representative suction temperature > Thermal diff 1,
operation mode is changed from Cool to Heat
°F
Representative setpoint (Cool)
6°F
Representative setpoint (Heat)
<When the thermal difference is 3, 4°F>
4°F
1°F
1°F
Representative setpoint (Heat) +
Thermal difference in (4°F) + 1
Representative setpoint (Cool) –
Thermal difference in (4°F) – 1
When the thermal difference is 3, 4°F
Cooling mode Heating mode
Heating mode Cooling mode
Heating mode
Heating mode
Cooling mode
Representative
suction temperature
• When
Representative suction temperature – Representative setpoint (Heat) > Thermal diff 2,
operation mode is changed from Heat to Cool
• When
Representative setpoint (Cool) – Representative suction temperature > Thermal diff 2,
operation mode is changed from Cool to Heat
°F
Representative setpoint (Cool)
Representative setpoint (Heat) –
Thermal difference in (2°F) + 2
6°F
Representative setpoint (Heat)
<When the thermal difference is 1, 2°F>
2°F
2°F
2°F
Representative setpoint (Cool) –
Thermal difference in (2°F) – 2
When the thermal difference is 1, 2°F
Representative
suction
temperature
Heating mode Cooling mode
Cooling mode Heating mode
Heating mode
Heating mode
Cooling mode