User’s Manual EM11A017
DCM601A71 intelligent Touch Manager
272
[DIII chiller]
Items to be output by DIII chiller
The data is rounded to within the output effective range if it is outside the range.
No.
Item
Collection method
Unit
Valid output range
1
Operation time of heating
(Total)
Accumulated operating time (in minutes)
of the DIII chiller in heating mode
Minutes
0≤Value≤60
2
Operation time of cooling
(Total)
Accumulated operating time (in minutes)
of the DIII chiller in cooling mode
Minutes
0≤Value≤60
3
Start/Stop count
Number of times DIII chiller has been in
operation.
Times
0≤Value≤9999
4
Inlet Water Temp.
(Average)
Average 1-minute value
in 1-hour (data collection time)
˚C *
˚F *
–50.0≤Value≤120.0 *
–58≤Value≤248 *
5
Inlet Water Temp.
(Maximum)
Maximum 1-minute value
in 1-hour (data collection time)
˚C *
˚F *
–50.0≤Value≤120.0 *
–58≤Value≤248 *
6
Inlet Water Temp.
(Minimum)
Minimum 1-minute value
in 1-hour (data collection time)
˚C *
˚F *
–50.0≤Value≤120.0 *
–58≤Value≤248 *
7
Outlet Water Temp.
(Average)
Average 1-minute value
in 1-hour (data collection time)
˚C *
˚F *
–50.0≤Value≤120.0 *
–58≤Value≤248 *
8
Outlet Water Temp.
(Maximum)
Maximum 1-minute value
in 1-hour (data collection time)
˚C *
˚F *
–50.0≤Value≤120.0 *
–58≤Value≤248 *
9
Outlet Water Temp.
(Minimum)
Minimum 1-minute value
in 1-hour (data collection time)
˚C *
˚F *
–50.0≤Value≤120.0 *
–58≤Value≤248 *
*Room temperature is output in Celsius or Fahrenheit depending on the System Settings.
[Di/Dio]
Output Di/Dio data items
No.
Item
Collection method
Unit
Valid output range
1
Operation time (Total)
Accumulated Di/Dio operation
time, in minutes
Minutes
0≤Value≤60
2
Start/Stop count
Number of times Di/Dio has been in
operation.
Times
0≤Value≤9999
[Pi]
Output Pi data items
No.
Item
Collection method
Unit
Valid output range
1
Meter value (Total)
Hourly (data collection time) total
-
0≤Value≤999999.99
[Ai]
Output Ai data items
No.
Item
Collection method
Unit
Valid output range
1
Analog value (Average)
Average 1-minute value
in 1-hour (data collection time)
-
–100000.0≤Value
≤100000.0
Summary of Contents for Intelligent Touch Manager DCM601A71