Installation and operation manual

6

125A8V1BF

VRV IV System indoor unit

4P405267-1C – 2021.04

Drain pan kit (EKHBDPCA2)

The  drain  pan  is  required  to  drain  accumulated  condensation  from

the  indoor  unit.  It  is  required  during  low  temperature  cooling

operation of the indoor unit and when the leaving water temperature

is <18°C.
For  installation  of  this  option  into  the  indoor  unit,  refer  to  the

installation manual delivered with this option kit.

Heater kit (EKBUH)

The heater kit option can be installed to assist the heat pump during

heating  operation  or  to  provide  primary  heating  during  emergency

situations 

(1)

.

4.2.2. Possible combinations of indoor unit and outdoor unit

5. Application guidelines

5.1.

Overview: Application guidelines

The purpose of the application guidelines is to give a glance of the

possibilities of the Daikin heat pump system.

This chapter contains applications guidelines for:

Setting up the space heating/cooling system

Setting up an auxiliary heat source for space heating

5.2.

Setting up the space heating/cooling system

The Daikin heat pump system supplies leaving water to heat emitters

in one or more rooms. 
Because the system offers a wide flexibility to control the temperature

in each room, you need to answer the following questions first:

How  many  rooms  are  heated  (or  cooled)  by  the  Daikin

heat pump system?

Which  heat  emitter  types  are  used  in  each  room  and  what  is

their design leaving water temperature? 

Once  the  space  heating/cooling  requirements  are  clear,  Daikin

recommends to follow the setup guidelines below.

5.2.1. Single room
Under floor  heating  or  heat  pump  convector  –  Wired  room

thermostat
Setup

A

Main leaving water temperature zone

B

One single room

C

One single room

a

Outdoor VRV IV heat pump

b

VRV Direct Expansion (DX) Indoor unit cassette

c

HXY(080/125)

d

Optional EKRUAHT user interface (master)

e

Refrigerant piping

f

Water piping

g

Floor heating loop

h

Fan coil unit

i

Bypass valve (field supply)

j

User interface (slave)

The  under floor  heating  or  heat  pump  connection  is  directly

connected to the indoor unit.

The room temperature is controlled by the user interface, which

is used as room thermostat. Possible installations:

User interface (standard equipment) installed in the room and

used as room thermostat

User  interface  (standard  equipment)  installed  at  the  indoor

unit  and  used  for  control  close  to  the  indoor  unit  +  user

interface  (optional  equipment  EKRUAHT)  installed  in  the

room and used as room thermostat

Benefits

Cost effective

You do NOT need an additional external room

thermostat.

Highest  comfort and efficiency

.  The  smart  room  thermostat

functionality can decrease or increase the desired leaving water

temperature  based  on  the  actual  room  temperature

(modulation). This results in:

Stable room temperature matching the desired temperature

(higher comfort)

Less ON/OFF cycles (more quiet, higher comfort and higher

efficiency)

Lowest possible leaving water temperature (higher efficiency)

Easy

. You can easily set the desired room temperature via the

user interface:

For  your  daily  needs,  you  can  use  preset  values  and

schedules. 

To  deviate  from  your  daily  needs,  you  can  temporarily

overrule the preset values and schedules.

(1) More information can be found in the manual of the heater kit and on page 

"9. Installing the optional EKBUHAA(6V3/6W1) heater kit" on page 26

 of 

this manual.

Outdoor unit

Indoor unit

RYYQ8~20

RYYQ22~54

RXYQ8~20

RXYQ22~54

HXY080A8V1B

O

X

O

X

HXY125A8V1B

O

X

O

X

O =  allowed

X =  not allowed

INFORMATION

For  detailed  information,  refer  to  the  VRV IV  heat  pump

combination  table  in  Technical  Data.  Combinations  are

explained depending on the  system layout of the VRV IV

heat pump series.

NOTICE

The  illustrations  in  the  application  guidelines  are

meant for reference only, and are NOT to be used as

detailed  hydraulic  diagrams.  The  detailed  hydraulic

dimensioning and balancing are NOT shown, and are

the responsibility of the installer.

For more information about the configuration settings

to  optimize  heat pump  operation,  see  the

configuration chapter.

C

B

A

d

B

A

d

b

e

c

f

f

i

i

j

a

g

h

Summary of Contents for HXY080A8V1BF

Page 1: ...INSTALLATION AND OPERATION MANUAL HXY080A8V1BF HXY125A8V1BF System indoor unit...

Page 2: ...rtificaat C 05 Nota como se establece en A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08...

Page 3: ...ion 16 7 4 1 To fix the user interface cover to the indoor unit 16 7 4 2 To close the indoor unit 16 8 Commissioning 17 8 2 Final air purging 17 8 3 Field settings 17 8 3 1 Procedure 17 8 3 2 Detailed...

Page 4: ...gerant of oil and of other parts must be done by an authorized installer and must comply with applicable legislation Units must be treated at a specialized treatment facility for reuse recycling and r...

Page 5: ...erant gas comes into contact with fire WARNING Always recover the refrigerants Do NOT release them directly into the environment Use a refrigerant reclaim unit to evacuate the installation NOTICE Make...

Page 6: ...and or codes that are relevant and applicable for a certain product or domain Service company Qualified company which can perform or coordinate the required service to the product Installation manual...

Page 7: ...h Control close to the indoor unit Room thermostat functionality in the principal space to be heated Room thermostat EKRTWA EKRTR1 You can connect an optional room thermostat to the indoor unit This t...

Page 8: ...valve field supply j User interface slave The under floor heating or heat pump connection is directly connected to the indoor unit The room temperature is controlled by the user interface which is us...

Page 9: ...al capacity in case of heat pump capacity shortage See 9 Installing the optional EKBUHAA 6V3 6W1 heater kit on page 26 for details 6 Preparation 6 1 Preparing installation site Do NOT install the unit...

Page 10: ...high humidity max RH 85 for example a bathroom In places where frost is possible Ambient temperature around the indoor unit should be 5 C The indoor unit is designed for indoor installation only and f...

Page 11: ...nt galvanic corrosion Never use Zn coated parts in the water circuit Because the unit s internal water circuit uses copper piping excessive corrosion may occur Only use appropriate tooling to handle b...

Page 12: ...uit is 100 l No actions or adjustments are required Example 2 The indoor unit is installed at the highest point in the water circuit The total water volume in the water circuit is 350 l Actions Becaus...

Page 13: ...ectrical connections to the fixed wiring All components procured on the site and all electrical construction must comply with the applicable legislation WARNING The indoor unit should have a dedicated...

Page 14: ...nnection 9 52 mm b Refrigerant gas connection 15 9 mm 1 Connect the liquid piping from the outdoor unit to the refrigerant liquid connection of the indoor unit 2 Connect the gas piping from the outdoo...

Page 15: ...duce capacity losses during heating and cooling operations If the temperature is higher than 30 C and the humidity is higher than RH 80 the thickness of the sealing materials should be at least 20 mm...

Page 16: ...able legislation Use only copper wires All field wiring must be carried out in accordance with the wiring diagram supplied with the unit and the instructions given below Never squeeze bundled cables a...

Page 17: ...e Fixation of the user interface to the indoor unit 1 Fix the wallplate of the user interface to the frontplate of the unit For installation of the frontplate see 7 4 1 To fix the user interface cover...

Page 18: ...tening the mounting screws INFORMATION If next to the standard remote controller the optional remote controller is installed as well Connect the electrical wires of both remote controllers in the same...

Page 19: ...valves Make sure that the shut off valves are correctly installed and fully open Once all checks are fulfilled the unit must be closed only then can the unit be powered on When the power supply to th...

Page 20: ...ng can be programmed in 2 different ways based on the temperature set point both leaving water temperature and room temperature and based on the ON OFF instruction In the following tables both methods...

Page 21: ...LED will stop working When pushing the button The schedule timer for space heating will stop when active at that moment and will start again at the next scheduled ON function The last programmed comma...

Page 22: ...is installed its operation must be enabled by field setting Default 6 01 0 which means no external room thermostat is installed Set 6 01 2 if the optional external room thermostat is installed The ext...

Page 23: ...ccount influence of high ambient temperatures in the measurement 9 02 Setting is not applicable 9 03 Leaving water temperature compensation value for cooling operation 9 04 Setting not applicable A Op...

Page 24: ...20 1 C 02 Set point at low ambient temperature Lo_Ti 40 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 25 25 80 1 C 4 Settings are not applicable 00 Not applicable Do not change the default...

Page 25: ...1 C 03 Set point cooling leaving water minimum temperature 10 5 18 1 C 04 Not applicable Do not change the default value 0 d Settings are not applicable 00 Not applicable Do not change the default va...

Page 26: ...and are blinking 3 Push the button again to leave this mode If no button is pressed the user interface leaves the display mode after 10 seconds Procedure for space heating cooling 1 Check the leaving...

Page 27: ...do not touch a conductive section Do not rinse the unit This may cause electric shocks or fire Play it safe Touch a metal part by hand such as piping sheet metal in order to eliminate static electric...

Page 28: ...heater Refer to 8 3 Field settings on page 17 how to make field settings for field settings related to the EKBUHAA heater kit Other field settings which are explained in the EKBUHAA manual are not app...

Page 29: ...e master VRV DX Indoor Unit Refer to outdoor unit manual for further information Push the or button Display 88 8 starts blinking Display Set desired room temperature e g 22 C The user interface room t...

Page 30: ...s active 16 PUMP ICON This icon indicates that the circulation pump is active 17 OUTDOOR TEMPERATURE DISPLAY When this icon is flashing the outdoor ambient temperature is displayed Refer to 11 3 7 Tem...

Page 31: ...ed by the room temperature set point The set point can be set manually or through the schedule timer Selecting space cooling operation 1 Use the button to switch ON OFF space cooling Icon appears on t...

Page 32: ...t point Activating this operation will result in a lower power consumption than use with a manually fixed leaving water set point During weather dependent operation the user has the possibility to shi...

Page 33: ...time at which setback is started 2 02 Stop time time at which setback is stopped 5 02 Leaving water setback temperature temperature drop A Normal leaving water temperature set point B Leaving water s...

Page 34: ...Time T Temperature set point Room temperature Leaving water temperature INFORMATION By default space cooling based on temperature set point method 1 is enabled so only temperature shifts are possible...

Page 35: ...st action and end with the highest number for the last action This is not a requirement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day a...

Page 36: ...time 8 Use the and buttons to set the leaving water temperature 9 Use the and buttons to set the room temperature 10 Use the button to select to switch cooling and the user interface off 11 Repeat st...

Page 37: ...e 10 Use the and buttons to set the room temperature 11 Use the button to select to switch heating and the user interface off to select automatic temperature calculation for leaving water temperature...

Page 38: ...e selected mode is blinking You can leave programming by pressing the button 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to copy to the n...

Page 39: ...nd value of altered field settings at variance with the default value 11 4 1 Procedure To change one or more field settings proceed as follows 1 Press the button for a minimum of 5 seconds to enter FI...

Page 40: ...bient temperature Hi_A 15 10 20 1 C 02 Set point at low ambient temperature Lo_Ti 40 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 25 25 80 1 C 4 Settings are not applicable 00 Not applicab...

Page 41: ...re not applicable 00 Not applicable Do not change the default value 10 01 Not applicable Do not change the default value 30 02 Not applicable Do not change the default value 15 03 Not applicable Do no...

Page 42: ...g the button In case this procedure for resetting the safety is not successful contact your local dealer For other malfunction codes which may be displayed during the system test run or operation see...

Page 43: ...te YLW Yellow Notes PC L N X2M C COM X1M H H20 R1H X1M X1M only for EKRTR only for EKRTETS only for EKRTW 1 C COM H 1 A6P A6P A7P X801M 4 5 1 2 3 A4P 1 A1P WHT YLW ORG BLU RED BRN BLU BRN RED BLK WHT...

Page 44: ...e on DX cooling cold draft and total efficiency Heating operation a Outdoor Ta CDB WB b Indoor LWC C c Warming up zone d Normal operation range 14 5 ESP curve ESP External Static Pressure Flow Waterfl...

Page 45: ...a 85 65 Power input W 110 135 Water side Heat exchanger Type Brazed plate Quantity 1 Minimal water flow rate d d Flow switch setting l min 15 Nominal water flow rate Cooling a l min 22 9 35 8 Heating...

Page 46: ......

Page 47: ......

Page 48: ...4P405267 1C 2021 04 Copyright 2021 Daikin 3...

Reviews: