background image

125A8V1BF

VRV IV System indoor unit

4P405267-1C – 2021.04

Installation and operation manual

27

11. Operation of the unit

Please read chapter 1 and 2 first before consulting this chapter.

11.1. Introduction

11.1.1. General information

The unit is the indoor part of the air to water/air VRV IV heat pump.

The unit is designed for wall mounted indoor installation and used for

heating/cooling  applications.  The  unit  can  be  combined  with  (field

supply) floor heating/cooling loops or fan coil units.
A  user  interface  with  room  thermostat  functionality  is  standard

supplied with this unit to control your installation.
Refer to chapter 

"4. About the units and options" on page 5

.

11.2. Quick start-up of the unit

In this chapter the step-by-step procedure is explained for starting up

space cooling/heating.
The more detailed  information  of  how the unit must  be operated is

explained in the chapter 

"11.3. Operating the unit" on page 27

.

The quick start-up offers the user the possibility to start up the system

before reading the entire manual.

11.2.1. Space cooling/heating operation

11.3. Operating the unit

11.3.1. Operating the user interface

The  user  interface  offers  full  control  over  your  installation.  It  can

control  all  heating/cooling  applications  which  vary  in  capacity,

electrical  supply  and  installed  equipment  (options).  Operating  the

HXY080/125 unit comes down to operating the user interface.

WARNING

Before operating the unit, be sure the installation has been

carried out correctly by an installer.
If  you  feel  unsure  about  the  operation,  contact  your

installer for advice and information.

Confirm the operation mode 

(a)

 

heating   or cooling 

(a) The operation mode can not be selected on the hydrobox. The hydrobox follows 

the operation mode of the master VRV DX Indoor Unit. Refer to outdoor unit 

manual for further information

Push the 

 or 

 button

Display: 

88.8

 starts 

blinking

Display: "

"

Set desired room 

temperature (e.g. 22°C)

The user interface room 

thermostat function is 

not active

Push the 

 or 

 

button

You have "room 

temperature based" 

control of your system 

(user interface room 

thermostat is installed)

You have "leaving water 

temperature based" control of 

your system

(default)

Set desired leaving water 

temperature (e.g. 35°C for heating 

or 18°C cooling).

If the display is blank, automatic 

leaving water temperature is 

enabled in heating operation.

Push the 

 button

The   LED will light up and the unit 

will start.

For further details and advised s

ettings, see 

" Programming" on page 34

"11.3.4. Space cooling operation ( )" on page 29

 and 

"11.3.5. Space heating 

operation ( )" on page 29

CAUTION

Do not rinse the unit. This may cause electric shock or

fire.

Do not climb, sit or stand on top of the unit.

Do not place any objects or equipment on the unit top

plate.

INFORMATION

It is advised to use the user interface, which includes room

thermostat function, delivered with the unit.
This will prevent excessive space heating/cooling and will

stop  the  outdoor  and  indoor  unit  when  the  room

temperature  is above  the  thermostat  set  point.  Based  on

the request from the user there is an immediate feedback

to  the  compressor  control  which  optimizes  the

performance.
Refer  to  the  typical  application  examples  in  the  indoor

installation manual for more details.

WARNING

Never let the user interface get wet. This may cause

an electric shock or fire.

Never  press  the  buttons  of the user  interface with a

hard,  pointed  object.  This  may  damage  the  user

interface.

Never  inspect  or  service  the  user  interface  yourself,

ask a qualified service person to do this.

Do not rinse the indoor unit. This may cause electric

shock or fire.

Do not climb, sit or stand on top of the unit.

Do not place any objects or equipment on the unit top

plate.

Summary of Contents for HXY080A8V1BF

Page 1: ...INSTALLATION AND OPERATION MANUAL HXY080A8V1BF HXY125A8V1BF System indoor unit...

Page 2: ...rtificaat C 05 Nota como se establece en A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08...

Page 3: ...ion 16 7 4 1 To fix the user interface cover to the indoor unit 16 7 4 2 To close the indoor unit 16 8 Commissioning 17 8 2 Final air purging 17 8 3 Field settings 17 8 3 1 Procedure 17 8 3 2 Detailed...

Page 4: ...gerant of oil and of other parts must be done by an authorized installer and must comply with applicable legislation Units must be treated at a specialized treatment facility for reuse recycling and r...

Page 5: ...erant gas comes into contact with fire WARNING Always recover the refrigerants Do NOT release them directly into the environment Use a refrigerant reclaim unit to evacuate the installation NOTICE Make...

Page 6: ...and or codes that are relevant and applicable for a certain product or domain Service company Qualified company which can perform or coordinate the required service to the product Installation manual...

Page 7: ...h Control close to the indoor unit Room thermostat functionality in the principal space to be heated Room thermostat EKRTWA EKRTR1 You can connect an optional room thermostat to the indoor unit This t...

Page 8: ...valve field supply j User interface slave The under floor heating or heat pump connection is directly connected to the indoor unit The room temperature is controlled by the user interface which is us...

Page 9: ...al capacity in case of heat pump capacity shortage See 9 Installing the optional EKBUHAA 6V3 6W1 heater kit on page 26 for details 6 Preparation 6 1 Preparing installation site Do NOT install the unit...

Page 10: ...high humidity max RH 85 for example a bathroom In places where frost is possible Ambient temperature around the indoor unit should be 5 C The indoor unit is designed for indoor installation only and f...

Page 11: ...nt galvanic corrosion Never use Zn coated parts in the water circuit Because the unit s internal water circuit uses copper piping excessive corrosion may occur Only use appropriate tooling to handle b...

Page 12: ...uit is 100 l No actions or adjustments are required Example 2 The indoor unit is installed at the highest point in the water circuit The total water volume in the water circuit is 350 l Actions Becaus...

Page 13: ...ectrical connections to the fixed wiring All components procured on the site and all electrical construction must comply with the applicable legislation WARNING The indoor unit should have a dedicated...

Page 14: ...nnection 9 52 mm b Refrigerant gas connection 15 9 mm 1 Connect the liquid piping from the outdoor unit to the refrigerant liquid connection of the indoor unit 2 Connect the gas piping from the outdoo...

Page 15: ...duce capacity losses during heating and cooling operations If the temperature is higher than 30 C and the humidity is higher than RH 80 the thickness of the sealing materials should be at least 20 mm...

Page 16: ...able legislation Use only copper wires All field wiring must be carried out in accordance with the wiring diagram supplied with the unit and the instructions given below Never squeeze bundled cables a...

Page 17: ...e Fixation of the user interface to the indoor unit 1 Fix the wallplate of the user interface to the frontplate of the unit For installation of the frontplate see 7 4 1 To fix the user interface cover...

Page 18: ...tening the mounting screws INFORMATION If next to the standard remote controller the optional remote controller is installed as well Connect the electrical wires of both remote controllers in the same...

Page 19: ...valves Make sure that the shut off valves are correctly installed and fully open Once all checks are fulfilled the unit must be closed only then can the unit be powered on When the power supply to th...

Page 20: ...ng can be programmed in 2 different ways based on the temperature set point both leaving water temperature and room temperature and based on the ON OFF instruction In the following tables both methods...

Page 21: ...LED will stop working When pushing the button The schedule timer for space heating will stop when active at that moment and will start again at the next scheduled ON function The last programmed comma...

Page 22: ...is installed its operation must be enabled by field setting Default 6 01 0 which means no external room thermostat is installed Set 6 01 2 if the optional external room thermostat is installed The ext...

Page 23: ...ccount influence of high ambient temperatures in the measurement 9 02 Setting is not applicable 9 03 Leaving water temperature compensation value for cooling operation 9 04 Setting not applicable A Op...

Page 24: ...20 1 C 02 Set point at low ambient temperature Lo_Ti 40 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 25 25 80 1 C 4 Settings are not applicable 00 Not applicable Do not change the default...

Page 25: ...1 C 03 Set point cooling leaving water minimum temperature 10 5 18 1 C 04 Not applicable Do not change the default value 0 d Settings are not applicable 00 Not applicable Do not change the default va...

Page 26: ...and are blinking 3 Push the button again to leave this mode If no button is pressed the user interface leaves the display mode after 10 seconds Procedure for space heating cooling 1 Check the leaving...

Page 27: ...do not touch a conductive section Do not rinse the unit This may cause electric shocks or fire Play it safe Touch a metal part by hand such as piping sheet metal in order to eliminate static electric...

Page 28: ...heater Refer to 8 3 Field settings on page 17 how to make field settings for field settings related to the EKBUHAA heater kit Other field settings which are explained in the EKBUHAA manual are not app...

Page 29: ...e master VRV DX Indoor Unit Refer to outdoor unit manual for further information Push the or button Display 88 8 starts blinking Display Set desired room temperature e g 22 C The user interface room t...

Page 30: ...s active 16 PUMP ICON This icon indicates that the circulation pump is active 17 OUTDOOR TEMPERATURE DISPLAY When this icon is flashing the outdoor ambient temperature is displayed Refer to 11 3 7 Tem...

Page 31: ...ed by the room temperature set point The set point can be set manually or through the schedule timer Selecting space cooling operation 1 Use the button to switch ON OFF space cooling Icon appears on t...

Page 32: ...t point Activating this operation will result in a lower power consumption than use with a manually fixed leaving water set point During weather dependent operation the user has the possibility to shi...

Page 33: ...time at which setback is started 2 02 Stop time time at which setback is stopped 5 02 Leaving water setback temperature temperature drop A Normal leaving water temperature set point B Leaving water s...

Page 34: ...Time T Temperature set point Room temperature Leaving water temperature INFORMATION By default space cooling based on temperature set point method 1 is enabled so only temperature shifts are possible...

Page 35: ...st action and end with the highest number for the last action This is not a requirement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day a...

Page 36: ...time 8 Use the and buttons to set the leaving water temperature 9 Use the and buttons to set the room temperature 10 Use the button to select to switch cooling and the user interface off 11 Repeat st...

Page 37: ...e 10 Use the and buttons to set the room temperature 11 Use the button to select to switch heating and the user interface off to select automatic temperature calculation for leaving water temperature...

Page 38: ...e selected mode is blinking You can leave programming by pressing the button 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to copy to the n...

Page 39: ...nd value of altered field settings at variance with the default value 11 4 1 Procedure To change one or more field settings proceed as follows 1 Press the button for a minimum of 5 seconds to enter FI...

Page 40: ...bient temperature Hi_A 15 10 20 1 C 02 Set point at low ambient temperature Lo_Ti 40 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 25 25 80 1 C 4 Settings are not applicable 00 Not applicab...

Page 41: ...re not applicable 00 Not applicable Do not change the default value 10 01 Not applicable Do not change the default value 30 02 Not applicable Do not change the default value 15 03 Not applicable Do no...

Page 42: ...g the button In case this procedure for resetting the safety is not successful contact your local dealer For other malfunction codes which may be displayed during the system test run or operation see...

Page 43: ...te YLW Yellow Notes PC L N X2M C COM X1M H H20 R1H X1M X1M only for EKRTR only for EKRTETS only for EKRTW 1 C COM H 1 A6P A6P A7P X801M 4 5 1 2 3 A4P 1 A1P WHT YLW ORG BLU RED BRN BLU BRN RED BLK WHT...

Page 44: ...e on DX cooling cold draft and total efficiency Heating operation a Outdoor Ta CDB WB b Indoor LWC C c Warming up zone d Normal operation range 14 5 ESP curve ESP External Static Pressure Flow Waterfl...

Page 45: ...a 85 65 Power input W 110 135 Water side Heat exchanger Type Brazed plate Quantity 1 Minimal water flow rate d d Flow switch setting l min 15 Nominal water flow rate Cooling a l min 22 9 35 8 Heating...

Page 46: ......

Page 47: ......

Page 48: ...4P405267 1C 2021 04 Copyright 2021 Daikin 3...

Reviews: