125A8V1BF
VRV IV System indoor unit
4P405267-1C – 2021.04
Installation and operation manual
11
6.3.
Preparing electrical wiring
6.3.1. About preparing electrical wiring
6.3.2. Overview of electrical connections on the indoor unit
The following illustration shows the required field wiring.
a Dedicated power supply for the indoor unit
b HXY(080/125)
c User interface
d Optional user interface
e Optional heater kit
f Dedicated power supply for the external backup heater kit
g Optional room thermostat
h 230 V AC power supply
WARNING
Establish proper earthing. Do NOT earth the unit to a
utility pipe, surge absorber, or telephone earth.
Incomplete earthing may cause electrical shock.
Install the required fuses or circuit breakers.
Secure the electrical wiring with cable ties so that the
cables do NOT come in contact with the piping or
sharp edges, particularly on the high-pressure side
Do NOT use taped wires, stranded conductor wires,
extension cords, or connections from a star system.
They can cause overheating, electrical shock or fire.
All wiring must be performed by an authorized
electrician and must comply with the applicable
legislation.
Make electrical connections to the fixed wiring.
All components procured on the site and all electrical
construction must comply with the applicable
legislation.
WARNING
The indoor unit should have a dedicated power
supply.
The optional heater kit (EKBUH) should have a
dedicated power supply.
580
1 50
0
0
a
b
1
a Normal power supply
b Fuse
1 Power supply for indoor unit
INFORMATION
The following illustration is an example and may NOT
match your system layout.
"14.2. Wiring diagram" on page 41
Item Description
Wiring
Maximum
running
current
High voltage wiring (High voltage bundle)
1
Indoor unit power supply
2+GND
(a)
(a) Refer to name plate on the indoor unit.
2
malfunction output
2
0.3 A
(b)
(b) Minimum cable section 0.75 mm².
3
Operation ON/OFF output
2
0.3 A
4
Cooling/heating output
2
0.3 A
5
Heater kit step 1/2 output
3
6
External heater kit power supply
For details refer to the
installation manual provided
with the option kit.
Low voltage wiring (Low voltage bundle)
7
Indoor/outdoor transmission
2
(c)
(c) Cable section between 0.75 mm² and 1.25 mm².
8
User interface transmission
2
9
External heater kit safety
2
10
Thermostat input 1
2
11
Thermostat input 2
2
12
Operation ON signal
2
13
Operation OFF signal
2
14
230 V AC power supply (only for
wireless room thermostat EKRTR1)
2
<1 A
6
b
a
e
f
d
c
10
11
8
2
3
4
5
9
1
7
g
h
14
12
13
Summary of Contents for HXY080A8V1BF