background image

Installation and operation manual

24

125A8V1BF

VRV IV System indoor unit

4P405267-1C – 2021.04

8.5.

Final check and test run

8.5.1. Final check

Before switching on the unit, read the following:

When the complete installation and all necessary settings have

been carried out, be sure that all panels of the unit are closed. If

this is not the case, inserting your hand through the remaining

openings can cause serious injury due to electrical and hot parts

inside the unit.

The service panel of the switch box may only be opened by a

licensed electrician for maintenance purposes.

In order to purge most of the air out of the system perform a pump

operation as described below:

1

Change field setting [E

-

04]

The default value is 0. 

When changing the setting to 1, the pump will operate at low

speed (pump only, the unit will not operate).

When changing the field setting to 2, the pump will operate at

high speed.

2

When air purging is finished, change the field setting back to 0.

It  is  the  responsibility  of  the  installer  to  make  sure  that  the  air  is

purged out of the unit and system.

Be  sure  that  all  stop  valves  are  open.  (Refer  to  vacuuming

procedure of the outdoor unit)

Be sure that all water valves are open.

8.5.2. System test run

Before you can check test operation of each indoor unit separately,

you have to do the system test run. System test run is explained in

the installation manual of the outdoor unit. This is an automatic test

run which can take some time.
When the system test run is finished, it is possible to do an individual

test  run  as  described  in 

"8.5.3. Indoor  unit  individual  test  run"  on

page 24

.  During  this  test  run,  the  installer  should  check  indicated

items.

8.5.3. Indoor unit individual test run

The installer is obliged to verify correct operation of the indoor and

outdoor unit after installation. Therefor a test run must be performed

according  to  the  procedures  described  below.  At  any  time  it  is

possible to check correct operation of space heating/cooling.

Temperature read-out mode

On the user interface, the actual temperatures can be displayed.

1

Push and hold the 

 button for 5 seconds.

The leaving water temperature is displayed (icons 

 and 

and   are blinking).

2

Use the 

 and 

 buttons to display:

The  entering  water  temperature  (icons 

  and 

  are

blinking and the   icon is flashing slowly).

The indoor temperature (icons   and 

 are blinking).

The outdoor temperature (icons   and   are blinking).

3

Push the 

 button again to leave  this  mode.  If  no button  is

pressed,  the  user  interface  leaves  the  display  mode  after  10

seconds.

Procedure for space heating/cooling

1

Check the leaving water and entering water temperature through

the user interface read-out mode and write down the displayed

values. See 

"Temperature read-out mode" on page 24

.

2

Push the   button 4 times so the 

 icon will be displayed.

3

Perform  the  test  as  follows  (when  no  action  is  performed,  the

user interface will return to normal mode after 10 seconds or by

pressing the   button once):
To test the space heating/cooling operation push the 

 button

to start the test run operation.

4

The test run operation will end automatically after 30 minutes or

when reaching the set temperature. The test run operation can

be stopped manually by pressing the   button once. If there are

misconnections  or  malfunctions,  an  malfunction  code  will  be

displayed  on  the  user  interface.  Otherwise,  the  user  interface

will return to normal operation.

5

To resolve the malfunction codes, see 

"8.6.2. Malfunction codes

list" on page 25

.

6

Check the leaving water and entering water temperature through

the  user  interface  read-out  mode  and  compare  them  with  the

values  noted  with  step  1.  After  20  minutes  of  operation  an

increase/decrease  of  the  values  should  confirm  the  space

heating/cooling operation.

NOTICE

When  using  thermostatic  radiator  valves,  make  sure  to

open all valves during air purging operation.

INFORMATION

When the indoor units and outdoor unit are powered on for

the  first  time,  an  initialisation  takes  place.  This  will  take

maximum 12 minutes.
When using the user interface during the initialisation, an

malfunction code (

UH

) can be displayed.

INFORMATION

During the first start up of the unit (the first 50 hours of

compressor  running), it  might  happen  that  the  noise

level  of  the  unit  is  higher  than  mentioned  in  the

technical  specifications.  This  is  not  an  abnormal

event.

Start  up  of  the  unit  in  space  heating  mode  is  only

possible  when  the  outdoor  ambient  temperature  is

lower than 20°C.

INFORMATION

The operation mode can not be selected on the hydrobox.

The  hydrobox  follows  the  operation  mode  of  the  master

VRV  DX  Indoor  Unit.  Refer  to  outdoor  unit  manual  for

further information.

INFORMATION

To display the last resolved malfunction code, push the 

button 1 time. Push the   button again 4 times to return to

normal mode.

INFORMATION

It is not possible to perform a test run if a forced operation

from  the  outdoor  unit  is  in  progress.  Should  forced

operation be started during a test run, the test run will be

aborted.

Summary of Contents for HXY080A8V1BF

Page 1: ...INSTALLATION AND OPERATION MANUAL HXY080A8V1BF HXY125A8V1BF System indoor unit...

Page 2: ...rtificaat C 05 Nota como se establece en A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08...

Page 3: ...ion 16 7 4 1 To fix the user interface cover to the indoor unit 16 7 4 2 To close the indoor unit 16 8 Commissioning 17 8 2 Final air purging 17 8 3 Field settings 17 8 3 1 Procedure 17 8 3 2 Detailed...

Page 4: ...gerant of oil and of other parts must be done by an authorized installer and must comply with applicable legislation Units must be treated at a specialized treatment facility for reuse recycling and r...

Page 5: ...erant gas comes into contact with fire WARNING Always recover the refrigerants Do NOT release them directly into the environment Use a refrigerant reclaim unit to evacuate the installation NOTICE Make...

Page 6: ...and or codes that are relevant and applicable for a certain product or domain Service company Qualified company which can perform or coordinate the required service to the product Installation manual...

Page 7: ...h Control close to the indoor unit Room thermostat functionality in the principal space to be heated Room thermostat EKRTWA EKRTR1 You can connect an optional room thermostat to the indoor unit This t...

Page 8: ...valve field supply j User interface slave The under floor heating or heat pump connection is directly connected to the indoor unit The room temperature is controlled by the user interface which is us...

Page 9: ...al capacity in case of heat pump capacity shortage See 9 Installing the optional EKBUHAA 6V3 6W1 heater kit on page 26 for details 6 Preparation 6 1 Preparing installation site Do NOT install the unit...

Page 10: ...high humidity max RH 85 for example a bathroom In places where frost is possible Ambient temperature around the indoor unit should be 5 C The indoor unit is designed for indoor installation only and f...

Page 11: ...nt galvanic corrosion Never use Zn coated parts in the water circuit Because the unit s internal water circuit uses copper piping excessive corrosion may occur Only use appropriate tooling to handle b...

Page 12: ...uit is 100 l No actions or adjustments are required Example 2 The indoor unit is installed at the highest point in the water circuit The total water volume in the water circuit is 350 l Actions Becaus...

Page 13: ...ectrical connections to the fixed wiring All components procured on the site and all electrical construction must comply with the applicable legislation WARNING The indoor unit should have a dedicated...

Page 14: ...nnection 9 52 mm b Refrigerant gas connection 15 9 mm 1 Connect the liquid piping from the outdoor unit to the refrigerant liquid connection of the indoor unit 2 Connect the gas piping from the outdoo...

Page 15: ...duce capacity losses during heating and cooling operations If the temperature is higher than 30 C and the humidity is higher than RH 80 the thickness of the sealing materials should be at least 20 mm...

Page 16: ...able legislation Use only copper wires All field wiring must be carried out in accordance with the wiring diagram supplied with the unit and the instructions given below Never squeeze bundled cables a...

Page 17: ...e Fixation of the user interface to the indoor unit 1 Fix the wallplate of the user interface to the frontplate of the unit For installation of the frontplate see 7 4 1 To fix the user interface cover...

Page 18: ...tening the mounting screws INFORMATION If next to the standard remote controller the optional remote controller is installed as well Connect the electrical wires of both remote controllers in the same...

Page 19: ...valves Make sure that the shut off valves are correctly installed and fully open Once all checks are fulfilled the unit must be closed only then can the unit be powered on When the power supply to th...

Page 20: ...ng can be programmed in 2 different ways based on the temperature set point both leaving water temperature and room temperature and based on the ON OFF instruction In the following tables both methods...

Page 21: ...LED will stop working When pushing the button The schedule timer for space heating will stop when active at that moment and will start again at the next scheduled ON function The last programmed comma...

Page 22: ...is installed its operation must be enabled by field setting Default 6 01 0 which means no external room thermostat is installed Set 6 01 2 if the optional external room thermostat is installed The ext...

Page 23: ...ccount influence of high ambient temperatures in the measurement 9 02 Setting is not applicable 9 03 Leaving water temperature compensation value for cooling operation 9 04 Setting not applicable A Op...

Page 24: ...20 1 C 02 Set point at low ambient temperature Lo_Ti 40 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 25 25 80 1 C 4 Settings are not applicable 00 Not applicable Do not change the default...

Page 25: ...1 C 03 Set point cooling leaving water minimum temperature 10 5 18 1 C 04 Not applicable Do not change the default value 0 d Settings are not applicable 00 Not applicable Do not change the default va...

Page 26: ...and are blinking 3 Push the button again to leave this mode If no button is pressed the user interface leaves the display mode after 10 seconds Procedure for space heating cooling 1 Check the leaving...

Page 27: ...do not touch a conductive section Do not rinse the unit This may cause electric shocks or fire Play it safe Touch a metal part by hand such as piping sheet metal in order to eliminate static electric...

Page 28: ...heater Refer to 8 3 Field settings on page 17 how to make field settings for field settings related to the EKBUHAA heater kit Other field settings which are explained in the EKBUHAA manual are not app...

Page 29: ...e master VRV DX Indoor Unit Refer to outdoor unit manual for further information Push the or button Display 88 8 starts blinking Display Set desired room temperature e g 22 C The user interface room t...

Page 30: ...s active 16 PUMP ICON This icon indicates that the circulation pump is active 17 OUTDOOR TEMPERATURE DISPLAY When this icon is flashing the outdoor ambient temperature is displayed Refer to 11 3 7 Tem...

Page 31: ...ed by the room temperature set point The set point can be set manually or through the schedule timer Selecting space cooling operation 1 Use the button to switch ON OFF space cooling Icon appears on t...

Page 32: ...t point Activating this operation will result in a lower power consumption than use with a manually fixed leaving water set point During weather dependent operation the user has the possibility to shi...

Page 33: ...time at which setback is started 2 02 Stop time time at which setback is stopped 5 02 Leaving water setback temperature temperature drop A Normal leaving water temperature set point B Leaving water s...

Page 34: ...Time T Temperature set point Room temperature Leaving water temperature INFORMATION By default space cooling based on temperature set point method 1 is enabled so only temperature shifts are possible...

Page 35: ...st action and end with the highest number for the last action This is not a requirement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day a...

Page 36: ...time 8 Use the and buttons to set the leaving water temperature 9 Use the and buttons to set the room temperature 10 Use the button to select to switch cooling and the user interface off 11 Repeat st...

Page 37: ...e 10 Use the and buttons to set the room temperature 11 Use the button to select to switch heating and the user interface off to select automatic temperature calculation for leaving water temperature...

Page 38: ...e selected mode is blinking You can leave programming by pressing the button 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to copy to the n...

Page 39: ...nd value of altered field settings at variance with the default value 11 4 1 Procedure To change one or more field settings proceed as follows 1 Press the button for a minimum of 5 seconds to enter FI...

Page 40: ...bient temperature Hi_A 15 10 20 1 C 02 Set point at low ambient temperature Lo_Ti 40 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 25 25 80 1 C 4 Settings are not applicable 00 Not applicab...

Page 41: ...re not applicable 00 Not applicable Do not change the default value 10 01 Not applicable Do not change the default value 30 02 Not applicable Do not change the default value 15 03 Not applicable Do no...

Page 42: ...g the button In case this procedure for resetting the safety is not successful contact your local dealer For other malfunction codes which may be displayed during the system test run or operation see...

Page 43: ...te YLW Yellow Notes PC L N X2M C COM X1M H H20 R1H X1M X1M only for EKRTR only for EKRTETS only for EKRTW 1 C COM H 1 A6P A6P A7P X801M 4 5 1 2 3 A4P 1 A1P WHT YLW ORG BLU RED BRN BLU BRN RED BLK WHT...

Page 44: ...e on DX cooling cold draft and total efficiency Heating operation a Outdoor Ta CDB WB b Indoor LWC C c Warming up zone d Normal operation range 14 5 ESP curve ESP External Static Pressure Flow Waterfl...

Page 45: ...a 85 65 Power input W 110 135 Water side Heat exchanger Type Brazed plate Quantity 1 Minimal water flow rate d d Flow switch setting l min 15 Nominal water flow rate Cooling a l min 22 9 35 8 Heating...

Page 46: ......

Page 47: ......

Page 48: ...4P405267 1C 2021 04 Copyright 2021 Daikin 3...

Reviews: