background image

Installation and operation manual

18

125A8V1BF

VRV IV System indoor unit

4P405267-1C – 2021.04

6

Repeat  step 

2

  through 

4

  to  change  other  field  settings  as

required.

7

When finished, press the   button to exit FIELD SET MODE.

8.3.2. Detailed description

For a summary of all field settings refer to 

"8.4. Field setting list for

Installation Manual" on page 22

.

[0] Remote control setup

[0

-

00]

 User permission level

The user interface can be programmed to make certain buttons

and functions unavailable for the user. There are 2 permission

levels defined. Both levels (level 2 and level 3) are basically the

same, the only difference is that for level 3 no water temperature

settings are possible (see table below).

By default  no  level is defined so  all  buttons  and  functions are

operable.

The  actual  permission  level  is  determined  by field  setting.  For

permission  level  2,  set  field  setting  [0

-

00]  to 2,  for  permission

level 3, set field setting [0

-

00] to 3.

Once the field setting is set, the chosen permission level is not

yet  active.  Enabling  the  selected  permission  level  is  done  by

simultaneously pressing buttons 

 and 

 immediately

followed by simultaneously pressing buttons 

 and 

, and

keeping all 4 buttons pressed for at least 5 seconds. Note that

no indication on the user interface is given. After the procedure

the blocked buttons will not be available anymore.

Deactivating the selected permission level is done in the same

way.

[0

-

01]

 Room temperature compensation value

If needed, it is possible to adjust some thermistor value of the

unit by a correction value. This can be used as countermeasure

for thermistor tolerances or capacity shortage.

The  compensated  temperature  (=  measured  temperature  plus

compensation value) is then used for controlling the system and

will  be  displayed  in  the  temperature  read-out  mode.  See  also

"[9] Automatic  temperature  compensation"  on  page 21

  for

compensation values for leaving water temperature.

[0

-

02] 

Setting not applicable

[0

-

03]

  Status:  defines whether  the  ON/OFF  instruction  can  be

used in the schedule timer for space heating.

Refer  to  the  operation  manual  for  details  how  to  program  the

schedule timer.

The  schedule  timer  for  space  heating  can  be  programmed  in

2 different  ways:  based  on  the  temperature  set  point  (both

leaving water temperature and room temperature) and based on

the ON/OFF instruction.

In the following tables both methods on how to interpret the schedule

timer are shown.

INFORMATION

Changes  made  to  a  specific  field  setting  are  only

stored when the 

 button is pressed. Navigating to

a new field setting code or pressing the   button will

discard the change made.

The field settings are grouped by their field setting first

code.

For example, field settings [0

-

00]; [0

-

01]; [0

-

02]; [0

-

03]

are defined as "Group 0".

When  different  values  are  changed  within  the  same

group, pressing the 

 button will save all the values

changed within this group.

Be aware of this when changing field settings within

the same group and pressing on the 

 button.

INFORMATION

Before  shipping,  the  set  values  have  been  set  as

shown  under 

"8.4. Field  setting  list  for  Installation

Manual" on page 22

.

When  exiting  FIELD  SET  MODE,  "

88

"  may  be

displayed  on  the  user  interface  LCD  while  the  unit

initializes itself.

NOTICE

When  running  through  the  field  settings  you  may  notice

that  there  are  some  more  field  settings  as  there  are

mentioned  in  the 

"8.4. Field  setting  list  for  Installation

Manual" on page 22

These field settings are not appli

-

cable and may not be changed!

Permission

level 2

level 3

Operation ON/OFF

Operable

Operable

Setting the leaving water temperature

Operable

Setting the room temperature

Operable

Operable

Weather dependent set point operation 

ON/OFF

Operable

Setting the clock

Programming the schedule timer

Schedule timer operation ON/OFF

Operable

Operable

Field settings

malfunction code display

Operable

Operable

Test operation

INFORMATION

By default space heating based on temperature set point

(method  1)  is  enabled,  so  only  temperature  shifts  are

possible (no ON/OFF instruction).

Method 1

Space heating based on temperature set point

(a)

(a) For leaving water temperature and/or room temperature

During operation During schedule timer operation the operation LED is lit 

continuously.

When pushing 

the 

 button

The schedule timer for space heating will stop and will 

not start again.

The controller will be switched off (operation LED will 

stop working).

When pushing 

the 

 button

The schedule timer for space heating will be stopped and 

will not start again.

The schedule timer icon will not be displayed anymore.

Summary of Contents for HXY080A8V1BF

Page 1: ...INSTALLATION AND OPERATION MANUAL HXY080A8V1BF HXY125A8V1BF System indoor unit...

Page 2: ...rtificaat C 05 Nota como se establece en A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08...

Page 3: ...ion 16 7 4 1 To fix the user interface cover to the indoor unit 16 7 4 2 To close the indoor unit 16 8 Commissioning 17 8 2 Final air purging 17 8 3 Field settings 17 8 3 1 Procedure 17 8 3 2 Detailed...

Page 4: ...gerant of oil and of other parts must be done by an authorized installer and must comply with applicable legislation Units must be treated at a specialized treatment facility for reuse recycling and r...

Page 5: ...erant gas comes into contact with fire WARNING Always recover the refrigerants Do NOT release them directly into the environment Use a refrigerant reclaim unit to evacuate the installation NOTICE Make...

Page 6: ...and or codes that are relevant and applicable for a certain product or domain Service company Qualified company which can perform or coordinate the required service to the product Installation manual...

Page 7: ...h Control close to the indoor unit Room thermostat functionality in the principal space to be heated Room thermostat EKRTWA EKRTR1 You can connect an optional room thermostat to the indoor unit This t...

Page 8: ...valve field supply j User interface slave The under floor heating or heat pump connection is directly connected to the indoor unit The room temperature is controlled by the user interface which is us...

Page 9: ...al capacity in case of heat pump capacity shortage See 9 Installing the optional EKBUHAA 6V3 6W1 heater kit on page 26 for details 6 Preparation 6 1 Preparing installation site Do NOT install the unit...

Page 10: ...high humidity max RH 85 for example a bathroom In places where frost is possible Ambient temperature around the indoor unit should be 5 C The indoor unit is designed for indoor installation only and f...

Page 11: ...nt galvanic corrosion Never use Zn coated parts in the water circuit Because the unit s internal water circuit uses copper piping excessive corrosion may occur Only use appropriate tooling to handle b...

Page 12: ...uit is 100 l No actions or adjustments are required Example 2 The indoor unit is installed at the highest point in the water circuit The total water volume in the water circuit is 350 l Actions Becaus...

Page 13: ...ectrical connections to the fixed wiring All components procured on the site and all electrical construction must comply with the applicable legislation WARNING The indoor unit should have a dedicated...

Page 14: ...nnection 9 52 mm b Refrigerant gas connection 15 9 mm 1 Connect the liquid piping from the outdoor unit to the refrigerant liquid connection of the indoor unit 2 Connect the gas piping from the outdoo...

Page 15: ...duce capacity losses during heating and cooling operations If the temperature is higher than 30 C and the humidity is higher than RH 80 the thickness of the sealing materials should be at least 20 mm...

Page 16: ...able legislation Use only copper wires All field wiring must be carried out in accordance with the wiring diagram supplied with the unit and the instructions given below Never squeeze bundled cables a...

Page 17: ...e Fixation of the user interface to the indoor unit 1 Fix the wallplate of the user interface to the frontplate of the unit For installation of the frontplate see 7 4 1 To fix the user interface cover...

Page 18: ...tening the mounting screws INFORMATION If next to the standard remote controller the optional remote controller is installed as well Connect the electrical wires of both remote controllers in the same...

Page 19: ...valves Make sure that the shut off valves are correctly installed and fully open Once all checks are fulfilled the unit must be closed only then can the unit be powered on When the power supply to th...

Page 20: ...ng can be programmed in 2 different ways based on the temperature set point both leaving water temperature and room temperature and based on the ON OFF instruction In the following tables both methods...

Page 21: ...LED will stop working When pushing the button The schedule timer for space heating will stop when active at that moment and will start again at the next scheduled ON function The last programmed comma...

Page 22: ...is installed its operation must be enabled by field setting Default 6 01 0 which means no external room thermostat is installed Set 6 01 2 if the optional external room thermostat is installed The ext...

Page 23: ...ccount influence of high ambient temperatures in the measurement 9 02 Setting is not applicable 9 03 Leaving water temperature compensation value for cooling operation 9 04 Setting not applicable A Op...

Page 24: ...20 1 C 02 Set point at low ambient temperature Lo_Ti 40 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 25 25 80 1 C 4 Settings are not applicable 00 Not applicable Do not change the default...

Page 25: ...1 C 03 Set point cooling leaving water minimum temperature 10 5 18 1 C 04 Not applicable Do not change the default value 0 d Settings are not applicable 00 Not applicable Do not change the default va...

Page 26: ...and are blinking 3 Push the button again to leave this mode If no button is pressed the user interface leaves the display mode after 10 seconds Procedure for space heating cooling 1 Check the leaving...

Page 27: ...do not touch a conductive section Do not rinse the unit This may cause electric shocks or fire Play it safe Touch a metal part by hand such as piping sheet metal in order to eliminate static electric...

Page 28: ...heater Refer to 8 3 Field settings on page 17 how to make field settings for field settings related to the EKBUHAA heater kit Other field settings which are explained in the EKBUHAA manual are not app...

Page 29: ...e master VRV DX Indoor Unit Refer to outdoor unit manual for further information Push the or button Display 88 8 starts blinking Display Set desired room temperature e g 22 C The user interface room t...

Page 30: ...s active 16 PUMP ICON This icon indicates that the circulation pump is active 17 OUTDOOR TEMPERATURE DISPLAY When this icon is flashing the outdoor ambient temperature is displayed Refer to 11 3 7 Tem...

Page 31: ...ed by the room temperature set point The set point can be set manually or through the schedule timer Selecting space cooling operation 1 Use the button to switch ON OFF space cooling Icon appears on t...

Page 32: ...t point Activating this operation will result in a lower power consumption than use with a manually fixed leaving water set point During weather dependent operation the user has the possibility to shi...

Page 33: ...time at which setback is started 2 02 Stop time time at which setback is stopped 5 02 Leaving water setback temperature temperature drop A Normal leaving water temperature set point B Leaving water s...

Page 34: ...Time T Temperature set point Room temperature Leaving water temperature INFORMATION By default space cooling based on temperature set point method 1 is enabled so only temperature shifts are possible...

Page 35: ...st action and end with the highest number for the last action This is not a requirement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day a...

Page 36: ...time 8 Use the and buttons to set the leaving water temperature 9 Use the and buttons to set the room temperature 10 Use the button to select to switch cooling and the user interface off 11 Repeat st...

Page 37: ...e 10 Use the and buttons to set the room temperature 11 Use the button to select to switch heating and the user interface off to select automatic temperature calculation for leaving water temperature...

Page 38: ...e selected mode is blinking You can leave programming by pressing the button 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to copy to the n...

Page 39: ...nd value of altered field settings at variance with the default value 11 4 1 Procedure To change one or more field settings proceed as follows 1 Press the button for a minimum of 5 seconds to enter FI...

Page 40: ...bient temperature Hi_A 15 10 20 1 C 02 Set point at low ambient temperature Lo_Ti 40 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 25 25 80 1 C 4 Settings are not applicable 00 Not applicab...

Page 41: ...re not applicable 00 Not applicable Do not change the default value 10 01 Not applicable Do not change the default value 30 02 Not applicable Do not change the default value 15 03 Not applicable Do no...

Page 42: ...g the button In case this procedure for resetting the safety is not successful contact your local dealer For other malfunction codes which may be displayed during the system test run or operation see...

Page 43: ...te YLW Yellow Notes PC L N X2M C COM X1M H H20 R1H X1M X1M only for EKRTR only for EKRTETS only for EKRTW 1 C COM H 1 A6P A6P A7P X801M 4 5 1 2 3 A4P 1 A1P WHT YLW ORG BLU RED BRN BLU BRN RED BLK WHT...

Page 44: ...e on DX cooling cold draft and total efficiency Heating operation a Outdoor Ta CDB WB b Indoor LWC C c Warming up zone d Normal operation range 14 5 ESP curve ESP External Static Pressure Flow Waterfl...

Page 45: ...a 85 65 Power input W 110 135 Water side Heat exchanger Type Brazed plate Quantity 1 Minimal water flow rate d d Flow switch setting l min 15 Nominal water flow rate Cooling a l min 22 9 35 8 Heating...

Page 46: ......

Page 47: ......

Page 48: ...4P405267 1C 2021 04 Copyright 2021 Daikin 3...

Reviews: