Installation and operation manual

14

125A8V1BF

VRV IV System indoor unit

4P405267-1C – 2021.04

7.3.

Connecting the electrical wiring

7.3.1. Precautions on electrical wiring work

7.3.2. System overview of field wiring

Field  wiring  consists  out  of  power  supply,  indoor-outdoor

communication  (=  transmission  F1F2)  wiring,  wiring  of  the  user

interface (=P1P2),  wiring for connection  of options  and  field supply

accessories.

7.3.3. Requirements

A power supply (refer to the table mentioned in 

"6.3.2. Overview of

electrical  connections  on  the  indoor  unit"  on  page 11

)  must  be

provided  for  connection  of  the  unit.  The  power  supply  must  be

protected with the required safety devices, i.e. a main switch, a slow

blow  fuse  on  each  phase  and  an  earth  leakage  protector  in

accordance with applicable legislation.
Selection and sizing of the wiring should be done in accordance with

the applicable legislation based on the information mentioned in the

table 

"6.3.2. Overview of electrical connections on the indoor unit" on

page 11

.

7.3.4. To open the switch box cover

7.3.5. To connect the electrical wiring on the indoor unit

Wiring should enter the unit from the bottom.

Routing of the wiring inside the unit and switchbox should be as

follows:

WARNING: Electrical Installation

All  field  wiring  and  components  must  be  installed  by  an

installer and must comply with the applicable legislation.

NOTICE

Electrical wiring work recommendations.
To persons in charge of electrical wiring work.
Do  not  operate  the  unit  until  the  refrigerant  piping  is

complete. Running the unit before the piping is ready will

break the compressor.

WARNING

A  main  switch  or  other  means  for  disconnection,

having  a  contact  separation  in  all  poles,  must  be

incorporated in the fixed wiring in accordance with the

applicable legislation. 

Use only copper wires.

All field wiring must be carried out in accordance with

the  wiring  diagram  supplied  with  the  unit  and  the

instructions given below.

Never  squeeze  bundled  cables  and  be  sure  that  it

does  not  come  in  contact  with  the  non-insulated

piping and sharp edges. Be sure no external pressure

is applied to the terminal connections.

Power supply wires must be attached securely.

Be sure to establish an earth. Do not earth the unit to

a  utility  pipe,  surge  absorber,  or  telephone  earth.

Incomplete earth may cause electrical shock.

Be  sure  to  install  an  earth  leakage  protector  in

accordance with the applicable legislation. Failure to

do so may cause electric shock or fire. 

Be sure to use a dedicated power circuit, never use a

power supply shared by another appliance.

Be  sure  to  install  the  required  fuses  or  circuit

breakers.

NOTICE

The  equipment  described  in  this  manual  may  cause

electronic  noise  generated  from  radio-frequency  energy.

The  equipment  complies  to  specifications  that  are

designed  to  provide  reasonable  protection  against  such

interference.  However,  there  is  no  guarantee  that

interference will not occur in a particular installation.
It is therefore  recommended to  install the equipment and

electric wires keeping proper distances away from stereo

equipment, personal computers, etc....
In extreme circumstances you shall keep distances of 3m

or more and use conduit tubes for power and transmission

lines.

INFORMATION

More information about the legend and the location of the

wiring  diagram  of  the  unit  can  be  found  in 

"14.2. Wiring

diagram" on page 41

.

The Wiring diagram on the indoor unit is only for the indoor

unit.
For  the  outdoor  unit  refer  to  the  wiring  diagram  of  the

outdoor unit.

NOTICE

Check  the  table  in 

"6.3.2. Overview  of  electrical

connections on the indoor unit" on page 11

 to know which

wiring should  be  routed  in  the  high  voltage  cable  bundle

and which wiring should be routed in the low voltage cable

bundle.

4x

a

b

Summary of Contents for HXY080A8V1BF

Page 1: ...INSTALLATION AND OPERATION MANUAL HXY080A8V1BF HXY125A8V1BF System indoor unit...

Page 2: ...rtificaat C 05 Nota como se establece en A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08...

Page 3: ...ion 16 7 4 1 To fix the user interface cover to the indoor unit 16 7 4 2 To close the indoor unit 16 8 Commissioning 17 8 2 Final air purging 17 8 3 Field settings 17 8 3 1 Procedure 17 8 3 2 Detailed...

Page 4: ...gerant of oil and of other parts must be done by an authorized installer and must comply with applicable legislation Units must be treated at a specialized treatment facility for reuse recycling and r...

Page 5: ...erant gas comes into contact with fire WARNING Always recover the refrigerants Do NOT release them directly into the environment Use a refrigerant reclaim unit to evacuate the installation NOTICE Make...

Page 6: ...and or codes that are relevant and applicable for a certain product or domain Service company Qualified company which can perform or coordinate the required service to the product Installation manual...

Page 7: ...h Control close to the indoor unit Room thermostat functionality in the principal space to be heated Room thermostat EKRTWA EKRTR1 You can connect an optional room thermostat to the indoor unit This t...

Page 8: ...valve field supply j User interface slave The under floor heating or heat pump connection is directly connected to the indoor unit The room temperature is controlled by the user interface which is us...

Page 9: ...al capacity in case of heat pump capacity shortage See 9 Installing the optional EKBUHAA 6V3 6W1 heater kit on page 26 for details 6 Preparation 6 1 Preparing installation site Do NOT install the unit...

Page 10: ...high humidity max RH 85 for example a bathroom In places where frost is possible Ambient temperature around the indoor unit should be 5 C The indoor unit is designed for indoor installation only and f...

Page 11: ...nt galvanic corrosion Never use Zn coated parts in the water circuit Because the unit s internal water circuit uses copper piping excessive corrosion may occur Only use appropriate tooling to handle b...

Page 12: ...uit is 100 l No actions or adjustments are required Example 2 The indoor unit is installed at the highest point in the water circuit The total water volume in the water circuit is 350 l Actions Becaus...

Page 13: ...ectrical connections to the fixed wiring All components procured on the site and all electrical construction must comply with the applicable legislation WARNING The indoor unit should have a dedicated...

Page 14: ...nnection 9 52 mm b Refrigerant gas connection 15 9 mm 1 Connect the liquid piping from the outdoor unit to the refrigerant liquid connection of the indoor unit 2 Connect the gas piping from the outdoo...

Page 15: ...duce capacity losses during heating and cooling operations If the temperature is higher than 30 C and the humidity is higher than RH 80 the thickness of the sealing materials should be at least 20 mm...

Page 16: ...able legislation Use only copper wires All field wiring must be carried out in accordance with the wiring diagram supplied with the unit and the instructions given below Never squeeze bundled cables a...

Page 17: ...e Fixation of the user interface to the indoor unit 1 Fix the wallplate of the user interface to the frontplate of the unit For installation of the frontplate see 7 4 1 To fix the user interface cover...

Page 18: ...tening the mounting screws INFORMATION If next to the standard remote controller the optional remote controller is installed as well Connect the electrical wires of both remote controllers in the same...

Page 19: ...valves Make sure that the shut off valves are correctly installed and fully open Once all checks are fulfilled the unit must be closed only then can the unit be powered on When the power supply to th...

Page 20: ...ng can be programmed in 2 different ways based on the temperature set point both leaving water temperature and room temperature and based on the ON OFF instruction In the following tables both methods...

Page 21: ...LED will stop working When pushing the button The schedule timer for space heating will stop when active at that moment and will start again at the next scheduled ON function The last programmed comma...

Page 22: ...is installed its operation must be enabled by field setting Default 6 01 0 which means no external room thermostat is installed Set 6 01 2 if the optional external room thermostat is installed The ext...

Page 23: ...ccount influence of high ambient temperatures in the measurement 9 02 Setting is not applicable 9 03 Leaving water temperature compensation value for cooling operation 9 04 Setting not applicable A Op...

Page 24: ...20 1 C 02 Set point at low ambient temperature Lo_Ti 40 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 25 25 80 1 C 4 Settings are not applicable 00 Not applicable Do not change the default...

Page 25: ...1 C 03 Set point cooling leaving water minimum temperature 10 5 18 1 C 04 Not applicable Do not change the default value 0 d Settings are not applicable 00 Not applicable Do not change the default va...

Page 26: ...and are blinking 3 Push the button again to leave this mode If no button is pressed the user interface leaves the display mode after 10 seconds Procedure for space heating cooling 1 Check the leaving...

Page 27: ...do not touch a conductive section Do not rinse the unit This may cause electric shocks or fire Play it safe Touch a metal part by hand such as piping sheet metal in order to eliminate static electric...

Page 28: ...heater Refer to 8 3 Field settings on page 17 how to make field settings for field settings related to the EKBUHAA heater kit Other field settings which are explained in the EKBUHAA manual are not app...

Page 29: ...e master VRV DX Indoor Unit Refer to outdoor unit manual for further information Push the or button Display 88 8 starts blinking Display Set desired room temperature e g 22 C The user interface room t...

Page 30: ...s active 16 PUMP ICON This icon indicates that the circulation pump is active 17 OUTDOOR TEMPERATURE DISPLAY When this icon is flashing the outdoor ambient temperature is displayed Refer to 11 3 7 Tem...

Page 31: ...ed by the room temperature set point The set point can be set manually or through the schedule timer Selecting space cooling operation 1 Use the button to switch ON OFF space cooling Icon appears on t...

Page 32: ...t point Activating this operation will result in a lower power consumption than use with a manually fixed leaving water set point During weather dependent operation the user has the possibility to shi...

Page 33: ...time at which setback is started 2 02 Stop time time at which setback is stopped 5 02 Leaving water setback temperature temperature drop A Normal leaving water temperature set point B Leaving water s...

Page 34: ...Time T Temperature set point Room temperature Leaving water temperature INFORMATION By default space cooling based on temperature set point method 1 is enabled so only temperature shifts are possible...

Page 35: ...st action and end with the highest number for the last action This is not a requirement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day a...

Page 36: ...time 8 Use the and buttons to set the leaving water temperature 9 Use the and buttons to set the room temperature 10 Use the button to select to switch cooling and the user interface off 11 Repeat st...

Page 37: ...e 10 Use the and buttons to set the room temperature 11 Use the button to select to switch heating and the user interface off to select automatic temperature calculation for leaving water temperature...

Page 38: ...e selected mode is blinking You can leave programming by pressing the button 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to copy to the n...

Page 39: ...nd value of altered field settings at variance with the default value 11 4 1 Procedure To change one or more field settings proceed as follows 1 Press the button for a minimum of 5 seconds to enter FI...

Page 40: ...bient temperature Hi_A 15 10 20 1 C 02 Set point at low ambient temperature Lo_Ti 40 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 25 25 80 1 C 4 Settings are not applicable 00 Not applicab...

Page 41: ...re not applicable 00 Not applicable Do not change the default value 10 01 Not applicable Do not change the default value 30 02 Not applicable Do not change the default value 15 03 Not applicable Do no...

Page 42: ...g the button In case this procedure for resetting the safety is not successful contact your local dealer For other malfunction codes which may be displayed during the system test run or operation see...

Page 43: ...te YLW Yellow Notes PC L N X2M C COM X1M H H20 R1H X1M X1M only for EKRTR only for EKRTETS only for EKRTW 1 C COM H 1 A6P A6P A7P X801M 4 5 1 2 3 A4P 1 A1P WHT YLW ORG BLU RED BRN BLU BRN RED BLK WHT...