background image

Installation and operation manual

28

125A8V1BF

VRV IV System indoor unit

4P405267-1C – 2021.04

11.3.2. Name and function of buttons and icons

ON/OFF BUTTON 

The ON/OFF button starts or stops the space cooling/heating.

Pressing the ON/OFF button consecutively too many times may

cause malfunction of the system (maximum 20 times per hour).

OPERATION LED 

The operation LED is lit during space heating/cooling operation.

The LED blinks if a malfunction occurs. When the LED is OFF,

space  heating/cooling  is  inactive  while  the  other  operation

modes can still be active.

OPERATION MODE ICONS  ,

These icons indicate the current operation mode(s): heating ( )

or cooling ( ).

EXTERNAL CONTROL ICON 

This icon indicates that the unit is working in a forced operation.

As long  as this icon is displayed,  the user interface cannot be

operated or has limited functionality.

DAY OF THE WEEK INDICATOR 

This indicator shows the current day of the week.

When reading or programming the schedule timer, the indicator

shows the set day.

CLOCK DISPLAY 

The clock display shows the current time.

When  reading  or  programming  the  schedule  timer,  the  clock

display shows the action time.

SCHEDULE TIMER ICON 

This icon indicates that the schedule timer is enabled.

ACTION ICONS 

These icons indicate the programming actions for each  day of

the schedule timer.

OFF ICON 

This  icon  indicates  that  the  OFF  action  is  selected  when

programming the schedule timer.

10 

INSPECTION REQUIRED   and 

These  icons  indicate  that  inspection  is  required  on  the

installation. Consult your dealer.

11 

TEMPERATURE DISPLAY 

The  display  shows  the  current  temperature  of  the  installation

either leaving water temperature or actual room temperature.

When changing the room temperature set point, the set point will

be  flashing  for  5  seconds  and  then  return  to  the  actual  room

temperature.

12 

SETTING 

This  icon  is  displayed  whenever  the  field  setting  mode  is

entered.

13 

NOT AVAILABLE 

This  icon  is  displayed  whenever  a  non-installed  option  is

addressed or a function is not available. A function not available

can mean insufficient permission level or can mean that a slave

user interface is used (see installation manual).

14 

DEFROST/START UP MODE ICON 

This icon indicates that the defrost/start up mode is active.

15 

COMPRESSOR ICON 

This icon indicates that the compressor in the outdoor unit of the

system is active.

16 

PUMP ICON 

This icon indicates that the circulation pump is active.

17 

OUTDOOR TEMPERATURE DISPLAY 

When this icon is flashing, the outdoor ambient temperature is

displayed.  Refer  to 

"11.3.7. Temperature  read-out  mode"  on

page 31

 for more information.

18 

WEATHER DEPENDENT SET POINT ICON 

This icon indicates that the controller will adapt the leaving water

temperature  set  point  automatically,  based  on  the  outdoor

ambient temperature (during heating operation).

19 

TEMPERATURE ICON 

This  icon  is  displayed  when  the  actual  room  temperature  or

room temperature set point is shown.

The icon is also displayed when the temperature set point is set

in  schedule  timer  programming  mode.  Refer  to

"11.3.7. Temperature  read-out  mode"  on  page 31

  for  more

information.

20 

TEST OPERATION ICON 

This icon indicates that the unit runs in test mode.

21 

FIELD SET CODE 

This code represents the code from the field set list. Refer to the

"8.3. Field settings" on page 17

.

22 

MALFUNCTION CODE 

This code refers to the malfunction  code list and is for service

purposes  only.  Refer  to  the  malfunction  code  list

"8.6.2. Malfunction codes list" on page 25

.

23 

BUTTON 

This button has no function.

24 

WEATHER DEPENDENT SET POINT BUTTON 

This button enables or disables the weather dependent set point

function which is available in space heating operation.

If  the  controller  is  set  to  permission  level 3  (refer  to  "Field

settings" in the installation manual), the weather dependent set

point button will not be operable.

25 

INSPECTION/TEST OPERATION BUTTON 

This button is used for installation purposes and changing field

settings. Refer to 

"8.3. Field settings" on page 17

.

26 

PROGRAMMING BUTTON 

This multi-purpose button is used to program the controller. The

function  of  the  button  depends  on  the  actual  status  of  the

controller or on previous actions carried out by the operator.

27 

SCHEDULE TIMER BUTTON  /

The  main  function  of  this  multi-purpose  button  is  to

enable/disable the schedule timer.

The  button  is  also  used  to  set  the  clock  and  to  program  the

controller.  The  function  of  the  button  depends  on  the  actual

status of the controller or on previous actions carried out by the

operator.

1

3

5

6 22

8

13

32

23

11

17

19

14

4

7
9

12

10
20

31

24

25

21

18

30
29
28

26

27

2

16

15

Master

Slave

Permission

level 2 level 3

Operation ON/OFF

Setting the leaving water temperature

Setting the room temperature

Weather dependent set point operation 

ON/OFF

Setting the clock

Programming the schedule timer

Schedule timer operation ON/OFF

Field settings

malfunction code display

Test operation

 = operable

Summary of Contents for HXY080A8V1BF

Page 1: ...INSTALLATION AND OPERATION MANUAL HXY080A8V1BF HXY125A8V1BF System indoor unit...

Page 2: ...rtificaat C 05 Nota como se establece en A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08...

Page 3: ...ion 16 7 4 1 To fix the user interface cover to the indoor unit 16 7 4 2 To close the indoor unit 16 8 Commissioning 17 8 2 Final air purging 17 8 3 Field settings 17 8 3 1 Procedure 17 8 3 2 Detailed...

Page 4: ...gerant of oil and of other parts must be done by an authorized installer and must comply with applicable legislation Units must be treated at a specialized treatment facility for reuse recycling and r...

Page 5: ...erant gas comes into contact with fire WARNING Always recover the refrigerants Do NOT release them directly into the environment Use a refrigerant reclaim unit to evacuate the installation NOTICE Make...

Page 6: ...and or codes that are relevant and applicable for a certain product or domain Service company Qualified company which can perform or coordinate the required service to the product Installation manual...

Page 7: ...h Control close to the indoor unit Room thermostat functionality in the principal space to be heated Room thermostat EKRTWA EKRTR1 You can connect an optional room thermostat to the indoor unit This t...

Page 8: ...valve field supply j User interface slave The under floor heating or heat pump connection is directly connected to the indoor unit The room temperature is controlled by the user interface which is us...

Page 9: ...al capacity in case of heat pump capacity shortage See 9 Installing the optional EKBUHAA 6V3 6W1 heater kit on page 26 for details 6 Preparation 6 1 Preparing installation site Do NOT install the unit...

Page 10: ...high humidity max RH 85 for example a bathroom In places where frost is possible Ambient temperature around the indoor unit should be 5 C The indoor unit is designed for indoor installation only and f...

Page 11: ...nt galvanic corrosion Never use Zn coated parts in the water circuit Because the unit s internal water circuit uses copper piping excessive corrosion may occur Only use appropriate tooling to handle b...

Page 12: ...uit is 100 l No actions or adjustments are required Example 2 The indoor unit is installed at the highest point in the water circuit The total water volume in the water circuit is 350 l Actions Becaus...

Page 13: ...ectrical connections to the fixed wiring All components procured on the site and all electrical construction must comply with the applicable legislation WARNING The indoor unit should have a dedicated...

Page 14: ...nnection 9 52 mm b Refrigerant gas connection 15 9 mm 1 Connect the liquid piping from the outdoor unit to the refrigerant liquid connection of the indoor unit 2 Connect the gas piping from the outdoo...

Page 15: ...duce capacity losses during heating and cooling operations If the temperature is higher than 30 C and the humidity is higher than RH 80 the thickness of the sealing materials should be at least 20 mm...

Page 16: ...able legislation Use only copper wires All field wiring must be carried out in accordance with the wiring diagram supplied with the unit and the instructions given below Never squeeze bundled cables a...

Page 17: ...e Fixation of the user interface to the indoor unit 1 Fix the wallplate of the user interface to the frontplate of the unit For installation of the frontplate see 7 4 1 To fix the user interface cover...

Page 18: ...tening the mounting screws INFORMATION If next to the standard remote controller the optional remote controller is installed as well Connect the electrical wires of both remote controllers in the same...

Page 19: ...valves Make sure that the shut off valves are correctly installed and fully open Once all checks are fulfilled the unit must be closed only then can the unit be powered on When the power supply to th...

Page 20: ...ng can be programmed in 2 different ways based on the temperature set point both leaving water temperature and room temperature and based on the ON OFF instruction In the following tables both methods...

Page 21: ...LED will stop working When pushing the button The schedule timer for space heating will stop when active at that moment and will start again at the next scheduled ON function The last programmed comma...

Page 22: ...is installed its operation must be enabled by field setting Default 6 01 0 which means no external room thermostat is installed Set 6 01 2 if the optional external room thermostat is installed The ext...

Page 23: ...ccount influence of high ambient temperatures in the measurement 9 02 Setting is not applicable 9 03 Leaving water temperature compensation value for cooling operation 9 04 Setting not applicable A Op...

Page 24: ...20 1 C 02 Set point at low ambient temperature Lo_Ti 40 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 25 25 80 1 C 4 Settings are not applicable 00 Not applicable Do not change the default...

Page 25: ...1 C 03 Set point cooling leaving water minimum temperature 10 5 18 1 C 04 Not applicable Do not change the default value 0 d Settings are not applicable 00 Not applicable Do not change the default va...

Page 26: ...and are blinking 3 Push the button again to leave this mode If no button is pressed the user interface leaves the display mode after 10 seconds Procedure for space heating cooling 1 Check the leaving...

Page 27: ...do not touch a conductive section Do not rinse the unit This may cause electric shocks or fire Play it safe Touch a metal part by hand such as piping sheet metal in order to eliminate static electric...

Page 28: ...heater Refer to 8 3 Field settings on page 17 how to make field settings for field settings related to the EKBUHAA heater kit Other field settings which are explained in the EKBUHAA manual are not app...

Page 29: ...e master VRV DX Indoor Unit Refer to outdoor unit manual for further information Push the or button Display 88 8 starts blinking Display Set desired room temperature e g 22 C The user interface room t...

Page 30: ...s active 16 PUMP ICON This icon indicates that the circulation pump is active 17 OUTDOOR TEMPERATURE DISPLAY When this icon is flashing the outdoor ambient temperature is displayed Refer to 11 3 7 Tem...

Page 31: ...ed by the room temperature set point The set point can be set manually or through the schedule timer Selecting space cooling operation 1 Use the button to switch ON OFF space cooling Icon appears on t...

Page 32: ...t point Activating this operation will result in a lower power consumption than use with a manually fixed leaving water set point During weather dependent operation the user has the possibility to shi...

Page 33: ...time at which setback is started 2 02 Stop time time at which setback is stopped 5 02 Leaving water setback temperature temperature drop A Normal leaving water temperature set point B Leaving water s...

Page 34: ...Time T Temperature set point Room temperature Leaving water temperature INFORMATION By default space cooling based on temperature set point method 1 is enabled so only temperature shifts are possible...

Page 35: ...st action and end with the highest number for the last action This is not a requirement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day a...

Page 36: ...time 8 Use the and buttons to set the leaving water temperature 9 Use the and buttons to set the room temperature 10 Use the button to select to switch cooling and the user interface off 11 Repeat st...

Page 37: ...e 10 Use the and buttons to set the room temperature 11 Use the button to select to switch heating and the user interface off to select automatic temperature calculation for leaving water temperature...

Page 38: ...e selected mode is blinking You can leave programming by pressing the button 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to copy to the n...

Page 39: ...nd value of altered field settings at variance with the default value 11 4 1 Procedure To change one or more field settings proceed as follows 1 Press the button for a minimum of 5 seconds to enter FI...

Page 40: ...bient temperature Hi_A 15 10 20 1 C 02 Set point at low ambient temperature Lo_Ti 40 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 25 25 80 1 C 4 Settings are not applicable 00 Not applicab...

Page 41: ...re not applicable 00 Not applicable Do not change the default value 10 01 Not applicable Do not change the default value 30 02 Not applicable Do not change the default value 15 03 Not applicable Do no...

Page 42: ...g the button In case this procedure for resetting the safety is not successful contact your local dealer For other malfunction codes which may be displayed during the system test run or operation see...

Page 43: ...te YLW Yellow Notes PC L N X2M C COM X1M H H20 R1H X1M X1M only for EKRTR only for EKRTETS only for EKRTW 1 C COM H 1 A6P A6P A7P X801M 4 5 1 2 3 A4P 1 A1P WHT YLW ORG BLU RED BRN BLU BRN RED BLK WHT...

Page 44: ...e on DX cooling cold draft and total efficiency Heating operation a Outdoor Ta CDB WB b Indoor LWC C c Warming up zone d Normal operation range 14 5 ESP curve ESP External Static Pressure Flow Waterfl...

Page 45: ...a 85 65 Power input W 110 135 Water side Heat exchanger Type Brazed plate Quantity 1 Minimal water flow rate d d Flow switch setting l min 15 Nominal water flow rate Cooling a l min 22 9 35 8 Heating...

Page 46: ......

Page 47: ......

Page 48: ...4P405267 1C 2021 04 Copyright 2021 Daikin 3...

Reviews: