background image

125A8V1BF

VRV IV System indoor unit

4P405267-1C – 2021.04

Installation and operation manual

25

8.6.

Service and maintenance

In order to ensure optimal operation of the unit, a number of checks

and inspections on the unit and the field wiring have to be carried out

at regular intervals.
This maintenance should be carried out by your local installer.
To  execute  maintenance  first  remove  the  panels  as  shown  in

"7.4.2. To close the indoor unit" on page 16

.

8.6.1. Maintenance activities

Checks

The  described  checks  must  be  executed  at  least 

once  a  year

  by

qualified personnel.

1

Pressure relief valve hose (if present)
Check  that  the  pressure  relief  valve  hose  is  positioned

appropriately to drain the water.

2

Water pressure relief valve
Check  for  correct  operation  of  the  pressure  relief  valve  by

turning the red knob on the valve counter-clockwise:

If you do not hear a clacking sound, contact your local dealer.

In  case the  water keeps  running out of  the unit, close both

the water inlet and outlet shut-off valves first and then contact

your local dealer.

3

Switch box
Carry out a thorough visual inspection of the switch box and look

for  obvious  defects  such  as  loose  connections  or  defective

wiring.

4

Water pressure
Check if the water pressure is above 1 bar.

If necessary add water.

5

Water filter
Clean the water filter.

8.6.2. Malfunction codes list

A more detailed malfunction code list can be found in the installation

manual of the outdoor unit. 

8.6.3. Important information regarding the refrigerant used

This  product  contains  fluorinated  greenhouse  gases.  Do  not  vent

gases into the atmosphere.
Refrigerant type: R410A

GWP

(1)

 value: 2087,5

(1)

 GWP = global warming potential

DANGER: ELECTRICAL SHOCK

See 

"7.3.1. Precautions  on  electrical  wiring  work"  on

page 14

.

WARNING: ELECTRIC SHOCK 

Before carrying out any maintenance or repair activity,

always  switch  off  the  circuit  breaker  on  the  supply

panel,  remove  the  fuses  or  open  the  protection

devices of the unit.

Do not touch live parts for 10 minutes after the power

supply is turned off because of high voltage risk.

Please  note  that  some  sections  of  the  electric

component box are hot.

Make sure you do not touch a conductive section.

Do not rinse the unit. This may cause electric shocks

or fire.

Play it safe!

Touch a metal part by hand (such as piping sheet metal) in

order to eliminate static electricity and to protect the PCB

before performing service.

Malfunction 

code

Failure cause

Corrective action

A1

Failure of writing memory 

(EEPROM malfunction)

Contact your local dealer.

A6

Malfunction water circuit

• Make sure waterflow is 

possible (open all valves in 

the circuit).

• Force clean water through 

the unit.

• Malfunction of pump.

• Malfunction of flowswitch.

A9

R410A expansion valve 

malfunction.

• Check wiring connections.

• Contact your local dealer.

AA

Heater kit malfunction

• Make sure water flow is 

possible.

• Contact your local dealer.

AJ

Capacity malfunction.

Contact your local dealer.

C1

Bad ACS communication.

Contact your local dealer.

C4

R410A liquid thermistor 

malfunction.

• Check wiring connections.

• Contact your local dealer.

C9

Returning water thermistor 

malfunction.

• Check wiring connections.

• Contact your local dealer.

CA

Heating/cooling leaving 

water thermistor malfunction.

• Check wiring connections.

• Contact your local dealer.

CJ

User interface thermostat 

thermistor malfunction.

Contact your local dealer.

E3

High pressure malfunction.

This malfunction is outdoor 

unit related. Refer to outdoor 

unit manual.

• Make sure the circuit is 

filled with water (no air 

inside, e.g. is the air purge 

open?)

• Make sure water flow is 

possible (open all valves in 

the circuit).

• Make sure the water filter is 

not blocked.

• Make sure all refrigerant 

stop valves are open.

• Contact your local dealer.

E4

Low pressure malfunction.

This malfunction is outdoor 

unit related. Refer to outdoor 

unit manual.

Contact your local dealer.

J7

R410A gas thermistor 

malfunction.

• Check wiring connections.

• Contact your local dealer.

U1

The phases of the power to 

the unit is reversed.

This malfunction is outdoor 

unit related. Refer to outdoor 

unit manual.

Exchange two of the three 

phases (L1, L2, L3) to make a 

positive phase connection.

U2

Power supply malfunction.

This malfunction is outdoor 

unit related. Refer to outdoor 

unit manual.

• Check wiring connections.

• Contact your local dealer.

UA

Type connection problem.

• Wait till initialisation 

between outdoor module 

and hydro module finished 

(after power ON, wait at 

least 12 minutes).

• Contact your local dealer.

UH

Address malfunction.

Contact your local dealer.

Summary of Contents for HXY080A8V1BF

Page 1: ...INSTALLATION AND OPERATION MANUAL HXY080A8V1BF HXY125A8V1BF System indoor unit...

Page 2: ...rtificaat C 05 Nota como se establece en A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08...

Page 3: ...ion 16 7 4 1 To fix the user interface cover to the indoor unit 16 7 4 2 To close the indoor unit 16 8 Commissioning 17 8 2 Final air purging 17 8 3 Field settings 17 8 3 1 Procedure 17 8 3 2 Detailed...

Page 4: ...gerant of oil and of other parts must be done by an authorized installer and must comply with applicable legislation Units must be treated at a specialized treatment facility for reuse recycling and r...

Page 5: ...erant gas comes into contact with fire WARNING Always recover the refrigerants Do NOT release them directly into the environment Use a refrigerant reclaim unit to evacuate the installation NOTICE Make...

Page 6: ...and or codes that are relevant and applicable for a certain product or domain Service company Qualified company which can perform or coordinate the required service to the product Installation manual...

Page 7: ...h Control close to the indoor unit Room thermostat functionality in the principal space to be heated Room thermostat EKRTWA EKRTR1 You can connect an optional room thermostat to the indoor unit This t...

Page 8: ...valve field supply j User interface slave The under floor heating or heat pump connection is directly connected to the indoor unit The room temperature is controlled by the user interface which is us...

Page 9: ...al capacity in case of heat pump capacity shortage See 9 Installing the optional EKBUHAA 6V3 6W1 heater kit on page 26 for details 6 Preparation 6 1 Preparing installation site Do NOT install the unit...

Page 10: ...high humidity max RH 85 for example a bathroom In places where frost is possible Ambient temperature around the indoor unit should be 5 C The indoor unit is designed for indoor installation only and f...

Page 11: ...nt galvanic corrosion Never use Zn coated parts in the water circuit Because the unit s internal water circuit uses copper piping excessive corrosion may occur Only use appropriate tooling to handle b...

Page 12: ...uit is 100 l No actions or adjustments are required Example 2 The indoor unit is installed at the highest point in the water circuit The total water volume in the water circuit is 350 l Actions Becaus...

Page 13: ...ectrical connections to the fixed wiring All components procured on the site and all electrical construction must comply with the applicable legislation WARNING The indoor unit should have a dedicated...

Page 14: ...nnection 9 52 mm b Refrigerant gas connection 15 9 mm 1 Connect the liquid piping from the outdoor unit to the refrigerant liquid connection of the indoor unit 2 Connect the gas piping from the outdoo...

Page 15: ...duce capacity losses during heating and cooling operations If the temperature is higher than 30 C and the humidity is higher than RH 80 the thickness of the sealing materials should be at least 20 mm...

Page 16: ...able legislation Use only copper wires All field wiring must be carried out in accordance with the wiring diagram supplied with the unit and the instructions given below Never squeeze bundled cables a...

Page 17: ...e Fixation of the user interface to the indoor unit 1 Fix the wallplate of the user interface to the frontplate of the unit For installation of the frontplate see 7 4 1 To fix the user interface cover...

Page 18: ...tening the mounting screws INFORMATION If next to the standard remote controller the optional remote controller is installed as well Connect the electrical wires of both remote controllers in the same...

Page 19: ...valves Make sure that the shut off valves are correctly installed and fully open Once all checks are fulfilled the unit must be closed only then can the unit be powered on When the power supply to th...

Page 20: ...ng can be programmed in 2 different ways based on the temperature set point both leaving water temperature and room temperature and based on the ON OFF instruction In the following tables both methods...

Page 21: ...LED will stop working When pushing the button The schedule timer for space heating will stop when active at that moment and will start again at the next scheduled ON function The last programmed comma...

Page 22: ...is installed its operation must be enabled by field setting Default 6 01 0 which means no external room thermostat is installed Set 6 01 2 if the optional external room thermostat is installed The ext...

Page 23: ...ccount influence of high ambient temperatures in the measurement 9 02 Setting is not applicable 9 03 Leaving water temperature compensation value for cooling operation 9 04 Setting not applicable A Op...

Page 24: ...20 1 C 02 Set point at low ambient temperature Lo_Ti 40 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 25 25 80 1 C 4 Settings are not applicable 00 Not applicable Do not change the default...

Page 25: ...1 C 03 Set point cooling leaving water minimum temperature 10 5 18 1 C 04 Not applicable Do not change the default value 0 d Settings are not applicable 00 Not applicable Do not change the default va...

Page 26: ...and are blinking 3 Push the button again to leave this mode If no button is pressed the user interface leaves the display mode after 10 seconds Procedure for space heating cooling 1 Check the leaving...

Page 27: ...do not touch a conductive section Do not rinse the unit This may cause electric shocks or fire Play it safe Touch a metal part by hand such as piping sheet metal in order to eliminate static electric...

Page 28: ...heater Refer to 8 3 Field settings on page 17 how to make field settings for field settings related to the EKBUHAA heater kit Other field settings which are explained in the EKBUHAA manual are not app...

Page 29: ...e master VRV DX Indoor Unit Refer to outdoor unit manual for further information Push the or button Display 88 8 starts blinking Display Set desired room temperature e g 22 C The user interface room t...

Page 30: ...s active 16 PUMP ICON This icon indicates that the circulation pump is active 17 OUTDOOR TEMPERATURE DISPLAY When this icon is flashing the outdoor ambient temperature is displayed Refer to 11 3 7 Tem...

Page 31: ...ed by the room temperature set point The set point can be set manually or through the schedule timer Selecting space cooling operation 1 Use the button to switch ON OFF space cooling Icon appears on t...

Page 32: ...t point Activating this operation will result in a lower power consumption than use with a manually fixed leaving water set point During weather dependent operation the user has the possibility to shi...

Page 33: ...time at which setback is started 2 02 Stop time time at which setback is stopped 5 02 Leaving water setback temperature temperature drop A Normal leaving water temperature set point B Leaving water s...

Page 34: ...Time T Temperature set point Room temperature Leaving water temperature INFORMATION By default space cooling based on temperature set point method 1 is enabled so only temperature shifts are possible...

Page 35: ...st action and end with the highest number for the last action This is not a requirement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day a...

Page 36: ...time 8 Use the and buttons to set the leaving water temperature 9 Use the and buttons to set the room temperature 10 Use the button to select to switch cooling and the user interface off 11 Repeat st...

Page 37: ...e 10 Use the and buttons to set the room temperature 11 Use the button to select to switch heating and the user interface off to select automatic temperature calculation for leaving water temperature...

Page 38: ...e selected mode is blinking You can leave programming by pressing the button 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to copy to the n...

Page 39: ...nd value of altered field settings at variance with the default value 11 4 1 Procedure To change one or more field settings proceed as follows 1 Press the button for a minimum of 5 seconds to enter FI...

Page 40: ...bient temperature Hi_A 15 10 20 1 C 02 Set point at low ambient temperature Lo_Ti 40 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 25 25 80 1 C 4 Settings are not applicable 00 Not applicab...

Page 41: ...re not applicable 00 Not applicable Do not change the default value 10 01 Not applicable Do not change the default value 30 02 Not applicable Do not change the default value 15 03 Not applicable Do no...

Page 42: ...g the button In case this procedure for resetting the safety is not successful contact your local dealer For other malfunction codes which may be displayed during the system test run or operation see...

Page 43: ...te YLW Yellow Notes PC L N X2M C COM X1M H H20 R1H X1M X1M only for EKRTR only for EKRTETS only for EKRTW 1 C COM H 1 A6P A6P A7P X801M 4 5 1 2 3 A4P 1 A1P WHT YLW ORG BLU RED BRN BLU BRN RED BLK WHT...

Page 44: ...e on DX cooling cold draft and total efficiency Heating operation a Outdoor Ta CDB WB b Indoor LWC C c Warming up zone d Normal operation range 14 5 ESP curve ESP External Static Pressure Flow Waterfl...

Page 45: ...a 85 65 Power input W 110 135 Water side Heat exchanger Type Brazed plate Quantity 1 Minimal water flow rate d d Flow switch setting l min 15 Nominal water flow rate Cooling a l min 22 9 35 8 Heating...

Page 46: ......

Page 47: ......

Page 48: ...4P405267 1C 2021 04 Copyright 2021 Daikin 3...

Reviews: