VRV IV System indoor unit

4P405267-1C – 2021.04

Installation and operation manual

29

28 

TIME ADJUST BUTTONS 

 and 

These  multi-purpose  buttons  are  used  to  adjust  the  clock,  to

toggle between  temperatures (water inlet/outlet temperature of

the unit, outdoor ambient temperature, actual room temperature)

and in schedule timer programming mode.

29 

LEAVING  WATER  TEMPERATURE  ADJUST  BUTTONS

 and 

These buttons are used to adjust the leaving water temperature

set  point  in  normal  operation  mode  or  in  schedule  timer

programming mode.

If  the  controller  is  set  to  permission  level 3  (refer  to  "Field

settings"  in  the  installation  manual),  the  leaving  water

temperature adjust button will not be operable.

In case the weather dependent set point operation is selected,

the unit has a floating set point. In this case, the   icon as well

as the shift value (in case not zero) will display.

30 

ROOM TEMPERATURE ADJUST BUTTONS 

 and 

These multi-purpose buttons are used to adjust the current room

temperature set point in normal operation mode or in schedule

timer programming mode.

When  changing  the  room  temperature  set  point,  the  set  point

value on the display will be flashing. After 5 seconds the display

will show to the actual room temperature.

31 

BUTTON 

This button has no function.

11.3.3. Setting up the controller

After  initial  installation,  the  user  can  set  the  clock  and  day  of  the

week.
The controller is equipped with a schedule timer that enables the user

to  schedule  operations.  Setting  the  clock  and  day  of  the  week  is

required to be able to use the schedule timer.

Setting the clock
1

Hold down the 

 button for 5 seconds.

The clock read-out and the day of week indicator start flashing.

2

Use the 

 and 

 buttons to adjust the clock.

Each  time the 

  or 

 button is  pressed, the time  will

increase/decrease  by  1 minute.  Keeping  the 

  or 

button pressed will increase/decrease the time by 10 minutes.

3

Use the 

 or 

 button to adjust the day of the week.

Each time the 

 or 

 button is pressed the next or

previous day is displayed.

4

Press the   button to confirm the current set time and day of the

week.
To leave this procedure without saving, press the 

 button.

If  no button  is  pressed  for 5 minutes  the  clock and  day of  the

week will return to their previous setting.

Setting the schedule timer

To  set  the  schedule  timer,  refer  to  chapter 

"11.3.10. Programming

and consulting the schedule timer" on page 33

.

11.3.4. Space cooling operation ( )

Space cooling operation can be controlled in two different ways:

based on room temperature,

based on leaving water temperature (default).

The purpose of each operation and how the configuration is done, is

explained below.

Room temperature control

In  this  mode,  cooling  will  be  activated  as  required  by  the  room

temperature set point. The set point can be set manually or through

the schedule timer.

Selecting space cooling operation

1

Use the 

 button to switch ON/OFF space cooling ( ).

Icon    appears  on  the  display  as  well  as  the  corresponding

actual room temperature.

The operation LED   lights up.

2

Use  the 

  and 

  buttons  to  set  the  desired  room

temperature.
Temperature range for cooling: 16°C~32°C (room temperature)

Refer  to 

"11.3.10. Programming  and  consulting  the  schedule

timer" on page 33

 for setup of the schedule timer function.

3

Use  the 

  and 

  buttons  to  select  the  leaving

water temperature which you want to be used to cool down your

system.

Leaving water temperature control (default)

In  this  mode,  cooling  will  be  activated  as  required  by  the  water

temperature set point. The set point can be set manually or through

the schedule timer.

Selecting space cooling operation

1

Use the 

 button to switch ON/OFF space cooling ( ).

Icon    appears  on  the  display  as  well  as  the  corresponding

water temperature set point.

The operation LED   lights up.

2

Use the 

 and 

 buttons to set the desired leaving

water temperature.
Temperature  range  for  cooling:  5°C~20°C  (leaving  water

temperature).

Refer  to 

"Programming  space  cooling"  on  page 34

, 

"Programming

space heating" on page 35

 for setup of the schedule timer function.

11.3.5. Space heating operation ( )

Space heating operation can be controlled in two different ways:

based on room temperature,

based on leaving water temperature (default).

The purpose of each operation and how the configuration is done, is

explained below.

Room temperature control

In  this  mode,  heating  will  be  activated  as  required  by  the  room

temperature set point. The set point can be set manually or through

the schedule timer.

INFORMATION

The clock needs to be set manually. Adjust the setting

when  switching  from  summertime  to  wintertime  and

vice versa.

If the controller is set to permission level 2 or 3 (refer

to  "Field  settings"  in  the  installation  manual),  setting

the clock will not be possible.

A power failure exceeding 2 hours will reset the clock

and  the  day  of  the  week.  The  schedule  timer  will

continue  operation,  but  with  a  disordered  clock.

Therefor it will be needed to correct the clock and the

day of the week.

INFORMATION

When  using  room  temperature  control,  space  cooling

operation  based  on  room  temperature  will  have  priority

over leaving water control.
Note that it is possible that the leaving water temperature

becomes lower than the set point if the unit is controlled by

room temperature.

INFORMATION

When  an  external  room  thermostat  is  installed,  the

thermo  ON/OFF  is  determined  by  the  external  room

thermostat. The user interface is then operated in the

leaving control mode and is not functioning as a room

thermostat.

The user interface ON/OFF status always has priority

over the external room thermostat!

Setback  operation  and  weather  dependent  set  point

are not available in cooling operation.

Summary of Contents for HXY080A8V1BF

Page 1: ...INSTALLATION AND OPERATION MANUAL HXY080A8V1BF HXY125A8V1BF System indoor unit...

Page 2: ...rtificaat C 05 Nota como se establece en A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08...

Page 3: ...ion 16 7 4 1 To fix the user interface cover to the indoor unit 16 7 4 2 To close the indoor unit 16 8 Commissioning 17 8 2 Final air purging 17 8 3 Field settings 17 8 3 1 Procedure 17 8 3 2 Detailed...

Page 4: ...gerant of oil and of other parts must be done by an authorized installer and must comply with applicable legislation Units must be treated at a specialized treatment facility for reuse recycling and r...

Page 5: ...erant gas comes into contact with fire WARNING Always recover the refrigerants Do NOT release them directly into the environment Use a refrigerant reclaim unit to evacuate the installation NOTICE Make...

Page 6: ...and or codes that are relevant and applicable for a certain product or domain Service company Qualified company which can perform or coordinate the required service to the product Installation manual...

Page 7: ...h Control close to the indoor unit Room thermostat functionality in the principal space to be heated Room thermostat EKRTWA EKRTR1 You can connect an optional room thermostat to the indoor unit This t...

Page 8: ...valve field supply j User interface slave The under floor heating or heat pump connection is directly connected to the indoor unit The room temperature is controlled by the user interface which is us...

Page 9: ...al capacity in case of heat pump capacity shortage See 9 Installing the optional EKBUHAA 6V3 6W1 heater kit on page 26 for details 6 Preparation 6 1 Preparing installation site Do NOT install the unit...

Page 10: ...high humidity max RH 85 for example a bathroom In places where frost is possible Ambient temperature around the indoor unit should be 5 C The indoor unit is designed for indoor installation only and f...

Page 11: ...nt galvanic corrosion Never use Zn coated parts in the water circuit Because the unit s internal water circuit uses copper piping excessive corrosion may occur Only use appropriate tooling to handle b...

Page 12: ...uit is 100 l No actions or adjustments are required Example 2 The indoor unit is installed at the highest point in the water circuit The total water volume in the water circuit is 350 l Actions Becaus...

Page 13: ...ectrical connections to the fixed wiring All components procured on the site and all electrical construction must comply with the applicable legislation WARNING The indoor unit should have a dedicated...

Page 14: ...nnection 9 52 mm b Refrigerant gas connection 15 9 mm 1 Connect the liquid piping from the outdoor unit to the refrigerant liquid connection of the indoor unit 2 Connect the gas piping from the outdoo...

Page 15: ...duce capacity losses during heating and cooling operations If the temperature is higher than 30 C and the humidity is higher than RH 80 the thickness of the sealing materials should be at least 20 mm...

Page 16: ...able legislation Use only copper wires All field wiring must be carried out in accordance with the wiring diagram supplied with the unit and the instructions given below Never squeeze bundled cables a...

Page 17: ...e Fixation of the user interface to the indoor unit 1 Fix the wallplate of the user interface to the frontplate of the unit For installation of the frontplate see 7 4 1 To fix the user interface cover...

Page 18: ...tening the mounting screws INFORMATION If next to the standard remote controller the optional remote controller is installed as well Connect the electrical wires of both remote controllers in the same...

Page 19: ...valves Make sure that the shut off valves are correctly installed and fully open Once all checks are fulfilled the unit must be closed only then can the unit be powered on When the power supply to th...

Page 20: ...ng can be programmed in 2 different ways based on the temperature set point both leaving water temperature and room temperature and based on the ON OFF instruction In the following tables both methods...

Page 21: ...LED will stop working When pushing the button The schedule timer for space heating will stop when active at that moment and will start again at the next scheduled ON function The last programmed comma...

Page 22: ...is installed its operation must be enabled by field setting Default 6 01 0 which means no external room thermostat is installed Set 6 01 2 if the optional external room thermostat is installed The ext...

Page 23: ...ccount influence of high ambient temperatures in the measurement 9 02 Setting is not applicable 9 03 Leaving water temperature compensation value for cooling operation 9 04 Setting not applicable A Op...

Page 24: ...20 1 C 02 Set point at low ambient temperature Lo_Ti 40 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 25 25 80 1 C 4 Settings are not applicable 00 Not applicable Do not change the default...

Page 25: ...1 C 03 Set point cooling leaving water minimum temperature 10 5 18 1 C 04 Not applicable Do not change the default value 0 d Settings are not applicable 00 Not applicable Do not change the default va...

Page 26: ...and are blinking 3 Push the button again to leave this mode If no button is pressed the user interface leaves the display mode after 10 seconds Procedure for space heating cooling 1 Check the leaving...

Page 27: ...do not touch a conductive section Do not rinse the unit This may cause electric shocks or fire Play it safe Touch a metal part by hand such as piping sheet metal in order to eliminate static electric...

Page 28: ...heater Refer to 8 3 Field settings on page 17 how to make field settings for field settings related to the EKBUHAA heater kit Other field settings which are explained in the EKBUHAA manual are not app...

Page 29: ...e master VRV DX Indoor Unit Refer to outdoor unit manual for further information Push the or button Display 88 8 starts blinking Display Set desired room temperature e g 22 C The user interface room t...

Page 30: ...s active 16 PUMP ICON This icon indicates that the circulation pump is active 17 OUTDOOR TEMPERATURE DISPLAY When this icon is flashing the outdoor ambient temperature is displayed Refer to 11 3 7 Tem...

Page 31: ...ed by the room temperature set point The set point can be set manually or through the schedule timer Selecting space cooling operation 1 Use the button to switch ON OFF space cooling Icon appears on t...

Page 32: ...t point Activating this operation will result in a lower power consumption than use with a manually fixed leaving water set point During weather dependent operation the user has the possibility to shi...

Page 33: ...time at which setback is started 2 02 Stop time time at which setback is stopped 5 02 Leaving water setback temperature temperature drop A Normal leaving water temperature set point B Leaving water s...

Page 34: ...Time T Temperature set point Room temperature Leaving water temperature INFORMATION By default space cooling based on temperature set point method 1 is enabled so only temperature shifts are possible...

Page 35: ...st action and end with the highest number for the last action This is not a requirement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day a...

Page 36: ...time 8 Use the and buttons to set the leaving water temperature 9 Use the and buttons to set the room temperature 10 Use the button to select to switch cooling and the user interface off 11 Repeat st...

Page 37: ...e 10 Use the and buttons to set the room temperature 11 Use the button to select to switch heating and the user interface off to select automatic temperature calculation for leaving water temperature...

Page 38: ...e selected mode is blinking You can leave programming by pressing the button 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to copy to the n...

Page 39: ...nd value of altered field settings at variance with the default value 11 4 1 Procedure To change one or more field settings proceed as follows 1 Press the button for a minimum of 5 seconds to enter FI...

Page 40: ...bient temperature Hi_A 15 10 20 1 C 02 Set point at low ambient temperature Lo_Ti 40 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 25 25 80 1 C 4 Settings are not applicable 00 Not applicab...

Page 41: ...re not applicable 00 Not applicable Do not change the default value 10 01 Not applicable Do not change the default value 30 02 Not applicable Do not change the default value 15 03 Not applicable Do no...

Page 42: ...g the button In case this procedure for resetting the safety is not successful contact your local dealer For other malfunction codes which may be displayed during the system test run or operation see...

Page 43: ...te YLW Yellow Notes PC L N X2M C COM X1M H H20 R1H X1M X1M only for EKRTR only for EKRTETS only for EKRTW 1 C COM H 1 A6P A6P A7P X801M 4 5 1 2 3 A4P 1 A1P WHT YLW ORG BLU RED BRN BLU BRN RED BLK WHT...

Page 44: ...e on DX cooling cold draft and total efficiency Heating operation a Outdoor Ta CDB WB b Indoor LWC C c Warming up zone d Normal operation range 14 5 ESP curve ESP External Static Pressure Flow Waterfl...

Page 45: ...a 85 65 Power input W 110 135 Water side Heat exchanger Type Brazed plate Quantity 1 Minimal water flow rate d d Flow switch setting l min 15 Nominal water flow rate Cooling a l min 22 9 35 8 Heating...

Page 46: ......

Page 47: ......

Page 48: ...4P405267 1C 2021 04 Copyright 2021 Daikin 3...

Reviews: