background image

125A8V1BF

VRV IV System indoor unit

4P405267-1C – 2021.04

Installation and operation manual

9

6.2.2. Water circuit requirements

Use the indoor unit only in a closed water system.

Using the system in an open water system will lead to excessive

corrosion.

Maximum  water  temperature  is  45°C  (heating)  and  mimimum

water temperature is 5°C (cooling).

The maximum water pressure is 3 bar.

Provide adequate safeguards in the water circuit to ensure that

the maximum pressure is NOT exceeded.

All  installed  piping  and  piping  accessories  (valve,

connections,…) must withstand the following temperatures.

a Outdoor unit (VRV IV heat pump)

b Indoor unit HXY(080/125)

c Heat exchanger

d Pump

e Shut-off valve

f Motorised 2-way valve (field supply)

g Collector

FCU1...3 Fan coil unit (optional)

FHL1...3 Floor heating loop (optional)

T  Room thermostat (optional)

Shut-off valves delivered with the unit should be installed so that

normal  servicing  can  be  accomplished  without  draining  the

system.

Make  all  water  piping  connections  in  accordance  with  the

applicable legislation and the outlook diagram that is delivered

with the unit, respecting the water inlet and outlet.

Do  NOT  use  excessive  force  when  connecting  the  piping.

Deformation of the piping can cause malfunctioning of the unit.

Provide drain taps at all low points of the system in order to allow

complete drainage of the water circuit.

Provide  a  proper  drain  for  the  pressure  relief  valve  to  avoid

water coming into contact with electrical parts.

Provide  air  vents  at  all  high  points  of  the  system,  which  must

also be easily accessible for servicing. An automatic air purge is

provided  in  the  indoor  unit.  Check  that  the  air  purge  is  NOT

tightened too much, so that automatic release of air in the water

circuit is possible.

Only use  materials  that  are  compatible  with  water  used  in  the

system and with the materials used in the indoor unit.

Check that all components in the field piping can withstand the

water pressure and water temperature.

When  using  non-brass  metallic  piping,  insulate  the  brass  and

non-brass properly so that they do NOT make contact with each

other. This to prevent galvanic corrosion.

Never  use  Zn-coated  parts  in  the  water  circuit.  Because  the

unit's  internal  water  circuit  uses  copper  piping,  excessive

corrosion may occur.

Only  use  appropriate  tooling  to  handle  brass,  which  is  a  soft

material. If NOT, pipes will get damaged.

Select the water piping diameter in relation to the required water

flow and the available external static pressure of the pump. See

"14. Technical Data" on page 40

 for the external static pressure

curves of the indoor unit.

You can find the minimum required water flow for the indoor unit

operation  in  the  following table.  When the water  flow  is lower,

flow malfunction A6 will be displayed and the indoor unit will be

stopped.

It is  strongly recommended to install an additional filter  on the

heating  water  circuit.  Especially  to  remove  metallic  particles

from the field heating piping, it is advised to use a magnetic or

cyclone filter, which can remove small particles. Small particles

may damage the unit and will NOT be removed by the standard

filter of the heat pump system.

If air or dust gets into the water circuit, problems may occur. To

prevent this:

Only use clean pipes

Hold the pipe end downwards when removing burrs.

Cover  the  pipe  end  when  inserting  it  through  a  wall,  to

prevent dust and/or particles entering the pipe.

Use a decent thread sealant to seal connections.

For safety reasons, it is NOT allowed to add any kind of glycol to

the water circuit.

The  installation  must  be  in  compliance  with  the  applicable

legislation  and  may  require  additional  hygienic  installation

measures.

In  accordance  with  the  applicable  legislation,  it  may  be

necessary to install thermostatic mixing valves.

6.2.3. Formula to calculate the expansion vessel pre-pressure

The  pre-pressure  (Pg)  of  the  vessel  depends  on  the  installation

height difference (H):
Pg=0.3+(H/10) (bar)

6.2.4. To check the water volume

The indoor unit has an expansion vessel of 10 litre with a factory set

pre-pressure of 1 bar.
To make sure that the unit operates properly:

You must check the minimum and maximum water volume.

You  might  need  to  adjust  the  pre-pressure  of  the  expansion

vessel.

INFORMATION

The  following  illustration  is  an  example  and  may  NOT

match your system layout.

M

T

FCU2

FCU3

FHL1

FHL2

FHL3

a

b c

d

e

e

f

g

g

g

g

65°C

Model

Minimum water flow (l/min)

HXY080A8V1B

15

HXY125A8V1B

15

Summary of Contents for HXY080A8V1BF

Page 1: ...INSTALLATION AND OPERATION MANUAL HXY080A8V1BF HXY125A8V1BF System indoor unit...

Page 2: ...rtificaat C 05 Nota como se establece en A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08...

Page 3: ...ion 16 7 4 1 To fix the user interface cover to the indoor unit 16 7 4 2 To close the indoor unit 16 8 Commissioning 17 8 2 Final air purging 17 8 3 Field settings 17 8 3 1 Procedure 17 8 3 2 Detailed...

Page 4: ...gerant of oil and of other parts must be done by an authorized installer and must comply with applicable legislation Units must be treated at a specialized treatment facility for reuse recycling and r...

Page 5: ...erant gas comes into contact with fire WARNING Always recover the refrigerants Do NOT release them directly into the environment Use a refrigerant reclaim unit to evacuate the installation NOTICE Make...

Page 6: ...and or codes that are relevant and applicable for a certain product or domain Service company Qualified company which can perform or coordinate the required service to the product Installation manual...

Page 7: ...h Control close to the indoor unit Room thermostat functionality in the principal space to be heated Room thermostat EKRTWA EKRTR1 You can connect an optional room thermostat to the indoor unit This t...

Page 8: ...valve field supply j User interface slave The under floor heating or heat pump connection is directly connected to the indoor unit The room temperature is controlled by the user interface which is us...

Page 9: ...al capacity in case of heat pump capacity shortage See 9 Installing the optional EKBUHAA 6V3 6W1 heater kit on page 26 for details 6 Preparation 6 1 Preparing installation site Do NOT install the unit...

Page 10: ...high humidity max RH 85 for example a bathroom In places where frost is possible Ambient temperature around the indoor unit should be 5 C The indoor unit is designed for indoor installation only and f...

Page 11: ...nt galvanic corrosion Never use Zn coated parts in the water circuit Because the unit s internal water circuit uses copper piping excessive corrosion may occur Only use appropriate tooling to handle b...

Page 12: ...uit is 100 l No actions or adjustments are required Example 2 The indoor unit is installed at the highest point in the water circuit The total water volume in the water circuit is 350 l Actions Becaus...

Page 13: ...ectrical connections to the fixed wiring All components procured on the site and all electrical construction must comply with the applicable legislation WARNING The indoor unit should have a dedicated...

Page 14: ...nnection 9 52 mm b Refrigerant gas connection 15 9 mm 1 Connect the liquid piping from the outdoor unit to the refrigerant liquid connection of the indoor unit 2 Connect the gas piping from the outdoo...

Page 15: ...duce capacity losses during heating and cooling operations If the temperature is higher than 30 C and the humidity is higher than RH 80 the thickness of the sealing materials should be at least 20 mm...

Page 16: ...able legislation Use only copper wires All field wiring must be carried out in accordance with the wiring diagram supplied with the unit and the instructions given below Never squeeze bundled cables a...

Page 17: ...e Fixation of the user interface to the indoor unit 1 Fix the wallplate of the user interface to the frontplate of the unit For installation of the frontplate see 7 4 1 To fix the user interface cover...

Page 18: ...tening the mounting screws INFORMATION If next to the standard remote controller the optional remote controller is installed as well Connect the electrical wires of both remote controllers in the same...

Page 19: ...valves Make sure that the shut off valves are correctly installed and fully open Once all checks are fulfilled the unit must be closed only then can the unit be powered on When the power supply to th...

Page 20: ...ng can be programmed in 2 different ways based on the temperature set point both leaving water temperature and room temperature and based on the ON OFF instruction In the following tables both methods...

Page 21: ...LED will stop working When pushing the button The schedule timer for space heating will stop when active at that moment and will start again at the next scheduled ON function The last programmed comma...

Page 22: ...is installed its operation must be enabled by field setting Default 6 01 0 which means no external room thermostat is installed Set 6 01 2 if the optional external room thermostat is installed The ext...

Page 23: ...ccount influence of high ambient temperatures in the measurement 9 02 Setting is not applicable 9 03 Leaving water temperature compensation value for cooling operation 9 04 Setting not applicable A Op...

Page 24: ...20 1 C 02 Set point at low ambient temperature Lo_Ti 40 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 25 25 80 1 C 4 Settings are not applicable 00 Not applicable Do not change the default...

Page 25: ...1 C 03 Set point cooling leaving water minimum temperature 10 5 18 1 C 04 Not applicable Do not change the default value 0 d Settings are not applicable 00 Not applicable Do not change the default va...

Page 26: ...and are blinking 3 Push the button again to leave this mode If no button is pressed the user interface leaves the display mode after 10 seconds Procedure for space heating cooling 1 Check the leaving...

Page 27: ...do not touch a conductive section Do not rinse the unit This may cause electric shocks or fire Play it safe Touch a metal part by hand such as piping sheet metal in order to eliminate static electric...

Page 28: ...heater Refer to 8 3 Field settings on page 17 how to make field settings for field settings related to the EKBUHAA heater kit Other field settings which are explained in the EKBUHAA manual are not app...

Page 29: ...e master VRV DX Indoor Unit Refer to outdoor unit manual for further information Push the or button Display 88 8 starts blinking Display Set desired room temperature e g 22 C The user interface room t...

Page 30: ...s active 16 PUMP ICON This icon indicates that the circulation pump is active 17 OUTDOOR TEMPERATURE DISPLAY When this icon is flashing the outdoor ambient temperature is displayed Refer to 11 3 7 Tem...

Page 31: ...ed by the room temperature set point The set point can be set manually or through the schedule timer Selecting space cooling operation 1 Use the button to switch ON OFF space cooling Icon appears on t...

Page 32: ...t point Activating this operation will result in a lower power consumption than use with a manually fixed leaving water set point During weather dependent operation the user has the possibility to shi...

Page 33: ...time at which setback is started 2 02 Stop time time at which setback is stopped 5 02 Leaving water setback temperature temperature drop A Normal leaving water temperature set point B Leaving water s...

Page 34: ...Time T Temperature set point Room temperature Leaving water temperature INFORMATION By default space cooling based on temperature set point method 1 is enabled so only temperature shifts are possible...

Page 35: ...st action and end with the highest number for the last action This is not a requirement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day a...

Page 36: ...time 8 Use the and buttons to set the leaving water temperature 9 Use the and buttons to set the room temperature 10 Use the button to select to switch cooling and the user interface off 11 Repeat st...

Page 37: ...e 10 Use the and buttons to set the room temperature 11 Use the button to select to switch heating and the user interface off to select automatic temperature calculation for leaving water temperature...

Page 38: ...e selected mode is blinking You can leave programming by pressing the button 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to copy to the n...

Page 39: ...nd value of altered field settings at variance with the default value 11 4 1 Procedure To change one or more field settings proceed as follows 1 Press the button for a minimum of 5 seconds to enter FI...

Page 40: ...bient temperature Hi_A 15 10 20 1 C 02 Set point at low ambient temperature Lo_Ti 40 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 25 25 80 1 C 4 Settings are not applicable 00 Not applicab...

Page 41: ...re not applicable 00 Not applicable Do not change the default value 10 01 Not applicable Do not change the default value 30 02 Not applicable Do not change the default value 15 03 Not applicable Do no...

Page 42: ...g the button In case this procedure for resetting the safety is not successful contact your local dealer For other malfunction codes which may be displayed during the system test run or operation see...

Page 43: ...te YLW Yellow Notes PC L N X2M C COM X1M H H20 R1H X1M X1M only for EKRTR only for EKRTETS only for EKRTW 1 C COM H 1 A6P A6P A7P X801M 4 5 1 2 3 A4P 1 A1P WHT YLW ORG BLU RED BRN BLU BRN RED BLK WHT...

Page 44: ...e on DX cooling cold draft and total efficiency Heating operation a Outdoor Ta CDB WB b Indoor LWC C c Warming up zone d Normal operation range 14 5 ESP curve ESP External Static Pressure Flow Waterfl...

Page 45: ...a 85 65 Power input W 110 135 Water side Heat exchanger Type Brazed plate Quantity 1 Minimal water flow rate d d Flow switch setting l min 15 Nominal water flow rate Cooling a l min 22 9 35 8 Heating...

Page 46: ......

Page 47: ......

Page 48: ...4P405267 1C 2021 04 Copyright 2021 Daikin 3...

Reviews: