ESIE15-13B
Field Setting from Outdoor Unit PCB
Field Setting
83
3.2.3 Setting Mode 2
In this mode, settings for the following items can be made.
Press the MODE (BS1) button for 5
seconds and set to “Setting mode 2”.
Press the SET (BS2) button and set the
LED display to a setting item (
∗
1).
↓
Press the RETURN (BS3) button and
decide the item.
<Selection of setting items>
<Selection of setting conditions>
Press the SET (BS2) button and set to
the setting condition you want.
↓
Press the RETURN (BS3) button and
decide the condition.
Press the RETURN (BS3) button and
set to the initial status of “Setting mode
2”.
∗
If you become unsure of how to proceed, push the MODE (BS1) button and return to setting mode 1.
h
: OFF
k
: ON
No.
Display of setting items
Display of setting conditions
Setting items
LED display
Setting condition
LED Display
H1P H2P H3P H4P H5P H6P H7P
H1P H2P H3P H4P H5P H6P H7P
3
Demand 2 operation
bck
h
h
h
h
bck
bck
30% Demand
k
h
h
h
k
h
h
40% Demand (factory set)
k
h
h
h
h
k
h
50% Demand
k
h
h
h
h
h
k
7
Reduced airflow (set to
low noise level 1)
bck
h
h
h
bck
bck
bck
OFF
k
h
h
h
h
h
h
ON
k
h
h
h
h
h
k
11 TeS Lower limit value
bck
h
h
bck
h
bck
bck
0°C
k
h
h
h
h
h
k
2°C (factory set)
k
h
h
h
h
k
h
4°C
k
h
h
h
h
k
k
6°C
k
h
h
h
k
h
h
28 Refrigerant recovery
mode
k
h
k
k
k
h
h
OFF (factory setting)
k
h
h
h
h
h
k
ON
k
h
h
h
h
k
h
33 TeS Lower limit value
k
k
h
h
h
h
k
0°C (factory set)
k
h
h
h
h
h
k
6°C
k
h
h
h
h
k
h
9°C
k
h
h
h
h
k
k
11°C
k
h
h
h
k
h
h
13°C
k
h
h
h
k
h
k
15°C
k
h
h
h
k
k
h
17°C
k
h
h
h
k
k
k
Weather depending control
in cooling
k
h
h
k
h
h
h
34 TcS Upper limit value
k
k
h
h
h
k
h
60°C
k
h
h
h
h
h
k
50°C
k
h
h
h
h
k
h
47°C
k
h
h
h
h
k
k
45°C
k
h
h
h
k
h
h
43°C
k
h
h
h
k
h
k
Weather depending control
in heating
k
h
h
h
k
k
h
Summary of Contents for GQI-Eco Series
Page 2: ......
Page 6: ...ESIE15 13B iv Table of Contents...
Page 14: ...Introduction ESIE15 13B xii...
Page 18: ...Outlook Outdoor Units ESIE15 13B 4 General Information 2 Outlook Outdoor Units...
Page 22: ...Operating range ESIE15 13B 8 General Information...
Page 108: ...Emergency Operation ESIE15 13B 94 Field Setting...