Field Setting from Remote Controller
ESIE15-13B
76
Field Setting
2.6
I-Demand Function
Purpose
Set a limitation towards the power consumption from the system (e.g. budget control, limit
power consumption during peak moments,..).
Setting
3 different demand setting can be selected by using terminal X801M:
Demand 1
Close contact between COM and contact 1
Demand 2
Close contact between COM and contact 2
Demand 3
Close contact between COM and contact 3
Demand 1
Power consumption limitation in function of setting on DS1:
Demand 2
Power consumption limitation set to 40%.
Demand 3
Forced thermostat OFF.
ON
OFF
DS1
1 2 3 4
X81A
X80A
X800M
X801M
X801M
1
LNOP COM
2
3
1
LNOP
COM
2
3
Power supply connector
(on outdoor PCB X77A)
Transmission connector
(on outdoor PCB X6A)
Output on X801M =
12VDC, 12mA
Maximum wire length =
100 meter
DS1 Setting
Maximum Power
Consumption
1
2
OFF
OFF
60%
ON
OFF
70%
OFF
ON
80%
ON
ON
100%