Function Details
ESIE15-13B
40
Function and Control
3.2.8 General Electronic Expansion Valve Control
When cooling/heating, PI control of electronic expansion valve is conducted to keep the heat
exchanger outlet subcooling degree constant.
• Target heat exchanger outlet subcooling degree > actual heat exchanger outlet subcooling
degree
The electronic expansion valve will close.
• Target heat exchanger outlet subcooling degree < actual heat exchanger outlet subcooling
degree
The electronic expansion valve will open.
* The value of target heat exchanger outlet subcooling degree varies depending on change of
discharge pipe superheat degree of inverter compressor, etc.
3.2.9 Hot Start Control (Only in Heating Operation)
In heating, when performing a startup, or after the defrosting cycle has been completed, the
indoor fan will be controlled in order to prevent cold air draft and secure the starting
performance (quick pressure build-up).
Indoor unit fan: OFF
Heating operation is turned ON with remote controller.
Indoor unit fan: LL tap
Indoor unit fan: L tap
Indoor unit fan: M tap
(Continuing L tap on indoor unit without M tap equipped)
Indoor unit fan: Set fan speed
Condition
A
Indoor unit heat exchanger temperature > 34°C
B
Indoor unit heat exchanger temperature > indoor suction
air tempe17°C
(+12°C if outdoor air temperature is < 5°C)
C
Indoor unit heat exchanger temperature > indoor suction
air tempe22°C
(+20°C if outdoor air temperature is < 5°C)
&
(
• 1 minute elapsed with LL tap
OR
(
• Condition A is met.
• Condition B is met.
• 3 minutes elapsed after compressor startup
&
(
• 1 minute elapsed with L tap
OR
(
• Condition A is met.
• Condition B is met.
• 5.5 minutes elapsed after compressor startup
&
(
• 1 minute elapsed with M tap
OR
(
• Condition A is met.
• Condition C is met.
• 10.5 minutes elapsed after compressor startup
Summary of Contents for GQI-Eco Series
Page 2: ......
Page 6: ...ESIE15 13B iv Table of Contents...
Page 14: ...Introduction ESIE15 13B xii...
Page 18: ...Outlook Outdoor Units ESIE15 13B 4 General Information 2 Outlook Outdoor Units...
Page 22: ...Operating range ESIE15 13B 8 General Information...
Page 108: ...Emergency Operation ESIE15 13B 94 Field Setting...